ABB CMS-700 Bruksanvisning
ABB
Mätutrustning
CMS-700
Läs nedan 📖 manual på svenska för ABB CMS-700 (72 sidor) i kategorin Mätutrustning. Denna guide var användbar för 6 personer och betygsatt med 3.8 stjärnor i genomsnitt av 3.5 användare
Sida 1/72

—
CMS-700 User manual
—
CIRCUIT MONITORING SYSTEM
CMS-700
User manual
• Energy transparency at branch level for optimal load distribution
• Measurements of all kinds of currents (DC, AC, or mixed) up to 160A
• Simplified installation thanks to quick mounting of sensors
• Smart commissioning in only a few minutes
• Easy retrofitting and upgrades thanks to the flexible, modular design


CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS) 3
005 Use and Storage of the Manual
006 General Information
007 Packaging Contents
008–011 Product Overview
012–013 Measurements and Events Definition
014 Memory Architecture
015–018 Components of CMS system
019–022 Installation Guide
023–024 Wiring Diagrams
025–028 Initial Commissioning
029–030 Web User Interface Overview
031–049 WEB UI – Settings
050 WEB UI – Mains
051 WEB UI – Branches
052 WEB UI – Energy
053 WEB UI – Energy / Events
054–059 Modbus
060–062 Simple Network Management
Protocol – SNMP
063–067 Modbus and SNMP Mapping
068 FAQ
—
Table of contents

CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS) 9
—
Product Overview
—
Reset button
There is a recessed button to restart the device or for resetting it to a defined as-delivered condition.
• Pressing the button for 3 to less than 6 seconds restarts the device with current settings
• Pressing the button for more than 10 seconds resets the device to the factory settings
Do not switch off the device during the reset process.
—
LEDs
Two LEDs indicate respectively the status of the device and the one of the network.
1. LED Status
Display Function
Off Device is off
Green on Device is ready
Green flashing slowly Firmware is ready, Web server is loading
Orange flashing slowly Firmware update ongoing
Orange on Booting
Red on Booting error
2. LED Network
Display Function
Off LAN is not connected
Green on LAN is connected
Green flashing Network traffic

14 CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
—
Memory Architecture
The measured values of the main power network and those of the 96 outputs
are stored in the following memory areas:
Stored values
Mains
• Voltage [V]: L1, L2, L3
• Current [A]: L1, L2, L3, N
• Power factor [-]: L1,L2,L3
• THD U [%]: L1, L2, L3
• THD I [%]: L1, L2, L3, N
• Active power[W]: L1, L2, L3
• Apparent power [VA]: L1, L2, L3
• Reactive power [VAR]: L1, L2, L3
• Active power summation [W]
• Apparent power summation [VA]
• Reactive power summation [VAR]
• Active energy [Wh]: L1, L2, L3
• Apparent energy [VAh]: L1, L2, L3
Branches
• Current (TRMS, AC, DC) [A]
• Active power [W]
• Active energy [Wh]
These values of the respective stacks can be exported as a CSV-file
and pulled into an FTP or sent by email.
Time reference
The measured values are provided with a UTC time stamp. UTC (Universal Coordinated Time)
stands for the location-independent world time in seconds.

16 CMS-700 SYSTEM CIRCUIT MONITORING SYSTEM (CMS)
System Pro M, SMISSLINE S800 DIN rail Cable tie
Mounting method for all MCBs, RCDs,
RCBOs with
twin terminals
for MCBs
(S200, SMISSLINE) and
RCBOs (SMISSLINE)
for fuse
holders E90
(1000VDC)
for all S800 devices
with cage terminals
universally
usable
universally
usable
Open-core sensors
AC accuracy* of ≤ ± 1.0%
The laying method
influences the accuracy.
18-mm over all width
CMS-120xx (80 A) CMS-120PS CMS-120LA -CMS-120DR CMS-120CA
CMS-121xx (40 A) CMS-121PS CMS-121LA CMS-121FH CMS-121DR CMS-121CA
CMS-122xx (20 A) CMS-122PS CMS-122LA CMS-122FH CMS-122DR CMS-122CA
Solid-core sensors
AC accuracy* of ≤ ± 0.5%
18-mm over all width
CMS-100xx (80 A) CMS-100PS CMS-100S8 CMS-100DR CMS-100CA
CMS-101xx (40 A) CMS-101PS CMS-101S8 CMS-101DR CMS-101CA
CMS-102xx (20 A) CMS-102PS CMS-102S8 CMS-102DR CMS-102CA
25-mm over all width
CMS-200xx (160 A) CMS-200S8 CMS-200CACMS-200DR
CMS-201xx (80 A) CMS-201S8 CMS-201DR CMS-201CA
CMS-202xx (40 A) CMS-202S8 CMS-202DR CMS-202CA
* All accuracy specifications refer to the relevant full scale value and apply to 25°C
—
Sensors overview
—
Components of CMS system
Produktspecifikationer
Varumärke: | ABB |
Kategori: | Mätutrustning |
Modell: | CMS-700 |
Behöver du hjälp?
Om du behöver hjälp med ABB CMS-700 ställ en fråga nedan och andra användare kommer att svara dig
Mätutrustning ABB Manualer

22 Augusti 2024

18 Augusti 2024

14 Augusti 2024

2 Augusti 2024
Mätutrustning Manualer
- Mätutrustning Crowcon
- Mätutrustning Steinberg
- Mätutrustning Weltron
- Mätutrustning Kogan
- Mätutrustning Megger
- Mätutrustning Albrecht
- Mätutrustning Truelife
- Mätutrustning Amprobe
- Mätutrustning Etymotic
- Mätutrustning Sonel
- Mätutrustning Wentronic
- Mätutrustning Blebox
- Mätutrustning Janitza
- Mätutrustning Greisinger
- Mätutrustning Digitus
Nyaste Mätutrustning Manualer

3 April 2025

3 April 2025

3 April 2025

3 April 2025

3 April 2025

3 April 2025

3 April 2025

3 April 2025

3 April 2025

3 April 2025