Unvented water heater

3
“Enactment of Directive 2012/19/EU governing electrical and electronic waste (WEEE)”
The barred bin symbol on the appliance and its packaging indicates that the product must be scrapped separately from other waste at
the end of its service life. The user must therefore hand the equipment over to a sorted waste disposal facility for electro-technical and electronic
equipment at the end of its service life.
Alternatively, he may return the equipment to the retailer at the time of purchase of a new equivalent type of appliance. Electronic equipment of size less than
25 cm can be handed over to any electronics equipment retailer whose sales area is at least 400 m2 for disposal free of charge and without
any obligation to purchase new product.
Sorted waste collection for recycling, treatment and environmentally compatible scrapping contributes to the prevention of damage to the
environment and promotes reuse/recycling.
62

9
The power consumption data in the table and the other information given in the Product Data
Sheet (Enclosure A to this manual) are defined in relation to EU Directives 812/2013 and
814/2013.
Products equipped with regulator knobs have the thermostat positioned in the setting
condition at its set <ready to use> position shown in the Data Sheet (Enclosure A), used by
the manufacturer to declare the appliance's energy class.
This appliance is conforming with the international electrical safety standards IEC
60335-1 and IEC 60335-2-21.
The CE marking of the appliances attests its conformity to the following EC Directives,
of which it satisfies the essential requisites:
- LVD Low Voltage Directive: EN 60335-1, EN 60335-2-21, EN 60529, EN 62233, EN 50106.
- EMC Electro-Magnetic Compatibility: EN 55014-1, EN 55014-2, EN 61000-3-2, EN
61000-3-3.
- RoHS2 Risk of Hazardous Substances: EN 50581.
- ErP Energy related Products: EN 50440.
- EN 12897:2006
Water Regulations and Byelaws
These regulations and byelaws ensure a good supply of wholesome water, and that
only approved materials, pipes and fittings are used to convey water.
Building Regulations
These are a statutory document and take priority over all other regulations and
recommendations. The installation of an unvented hot water system of over 15 litres
is classified as a “Controlled Service” and Regulation G3 applies. To meet the
requirements of the regulation, installation of an unvented system should be
undertaken by a “competent installer”.
All installations of unvented hot water storage systems having a capacity of more than
15 litres should be notified to the relevant Local Authority by means of building notice
or by the submission of full plans. It is important to note that it is a criminal offence to
install an unvented hot water storage system over 15 litres without notifying the Local
Authority.
Delivery
The products are supplied with the following:
Unvented water heater (with factory-fitted T&P model 30L) x1
Wall bracket x1
Pressure relief valve set at 6 bar x1
Dielectric junctions x2
Tundish (model 30L only) x1
Expansion Vessel (model 30L only) x1
Check Valve (model 30L only) x1
Pressure reducing Valve (model 30L only) x1

3) The pipe diameter must be at least one pipe size larger than the nominal outlet size
of the safety device unless it’s total equivalent hydraulic resistance exceeds that of a
straight pipe 9 m long.
i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at
least 2 sizes larger than the nominal outlet size of the safety device. Between 18
m and 27 m at least 3 times larger, and so on.
Bends must be taken into account in calculating the flow resistance.
See fig..5 and Table 2.
4) The discharge pipe must have a vertical section of pipe at least 300 mm in length,
below the tundish before any elbows or bends in the pipe work.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the tundish and the final point of discharge,
but where this is not possible or practically difficult; there should be clear visibility at
one or other of these locations. Examples of acceptance are:
i) Ideally below a fixed grating and above the water seal in a trapped gully.
ii) Downward discharges at a low level; i.e. up to 100 mm above external surfaces
such as car parks, hard standings, grassed areas etc. These are acceptable providing
that where children may play or otherwise come into contact with discharges, a wire
cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii) Discharges at high level; i.e. into a metal hopper and metal down pipe with the
end of the discharge pipe clearly visible (tundish visible or not). Or onto a roof capable
15
600 mm Max.
300 mm
Min.
Temperature & pressure
relief valve
Metal discharge pipe (D1) from
temperature & pressure relief valve.
to tundish.
Metal discharge pipe (D2) from tundish
with continuous fall. See Table 2 and worked
example.
Tundish
Fixed grating
Trapped gulley
Discharge below
fixed grating.
(see page 6 for
alternative points
of discharge).
Fig.. 4
Suggest ways of terminating discharge pipes safely

of withstanding high temperature discharges of water 3 m from any plastic guttering
systems that would collect such a discharge (tundish visible).
iv) Where a single pipe serves a number of discharges, such as in blocks of flats, the
number served should be limited to not more than 6 systems so that any installation
can be traced reasonably easily. The single common discharge pipe should be at least
one pipe size large than the largest individual discharge pipe to be connected. If
unvented hot water storage systems are installed where discharges from safety
devices may not be apparent i.e. in dwellings occupied by the blind, infirm or disabled
people, consideration should be given to the installation of an electronically operated
device to warn when discharge takes place. Note: The discharge will consist of
scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may
be damaged by such discharges.
16
Valve outlet size Minimum size of
discharge pipe D1*
Minimum size of
discharge pipe D2*
from tundish
Maximum
resistance allowed,
expressed as a
length of pipe (i.e.
no elbow or bends)
Resistance created
by each elbow or
bend
G 1/2 15 mm 22 mm
28 mm
35 mm
Up to 9 m
Up to 18 m
Up to 27 m
0.8 m
1.0 m
1.4 m
G 3/4 22 mm 28 mm
35 mm
42 mm
Up to 9 m
Up to 18 m
Up to 27 m
1.0 m
1.4 m
1.7 m
G 1 28 mm 35 mm
42 mm
54 mm
Up to 9 m
Up to 18 m
Up to 27 m
1.4 m
1.7 m
2.3 m
Table 2
Sizing of copper discharge pipe “D2”for common temperature valve outlets.
Worked example
The example below is for a G 1/2”temperature & pressure relief valve with a discharge
pipe (D2) having 4 no. elbows and length of 7 m from the tundish to the point of
discharge.
From Table 2
Maximum resistance allowed for a straight length of 22 mm copper discharge pipe
(D2) from G 1/2”T & P valve is 9 m.
Subtract the resistance for 4 no. 22 mm elbows at 0.8 m each = 3.2 m.
Therefore the maximum permitted length equates to: 5.8 m.
As 5.8 m is less than the actual length of 7 m therefore calculate the next
largest size.
Maximum resistance allowed for a straight length of 28 mm pipe (D2) from G 1/2”T &
P valve equates to: 18 m.
Subtract the resistance for 4 no. 28 mm elbow at 1.0 m each = 4 m.
Therefore the maximum permitted length equates to: 14 m
As the actual length is 7 m, a 28 mm (D2) copper pipe will be satisfactory.
Produktspecifikationer
Varumärke: | Ariston |
Kategori: | Panna |
Modell: | Aures Slim Multi |
Behöver du hjälp?
Om du behöver hjälp med Ariston Aures Slim Multi ställ en fråga nedan och andra användare kommer att svara dig
Panna Ariston Manualer

4 Mars 2025

29 Januari 2025

28 Januari 2025

26 Januari 2025

26 Januari 2025

11 Januari 2025

10 Januari 2025

10 Januari 2025

24 Juli 2024

21 Juli 2024
Panna Manualer
- Panna Thermoflow
- Panna AEG
- Panna Buderus
- Panna A.O. Smith
- Panna Bosch
- Panna Thermona
- Panna LEMET
- Panna Wesen
- Panna Strom
- Panna Elson
- Panna Atlantic
- Panna Morco
- Panna Fakir
- Panna Inventum
- Panna Bulex
Nyaste Panna Manualer

9 April 2025

8 April 2025

7 April 2025

7 April 2025

7 April 2025

7 April 2025

6 April 2025

6 April 2025