F220 Series Detectors with
F220-B6/C/E/R Bases
Installation Manual
en English manual
2en | Legal F220 Series Detectors with F220-B6/C/E/R Bases
4998138694 -04 | 2007.01 Installation Manual Bosch Security Systems, Inc.
1 Legal
1.1 Trademarks
CleanMe® is a registered trademark of GE Interlogix in the
United States and/or other countries.
Chamber Check® is a registered trademark of Bosch Security
Systems, Inc. in the United States.
Chambermaid™ is a trademark of Bosch Security Systems, Inc.
in the United States.
ENVI-RO-TECH™ is a trademark of Tech Spray L.P.
TECHSPRAY® is a registered trademark of Tech Spray L.P.
1.2 Required Maintenance and Testing
Keep the detector calibrated for proper operation. NFPA 72,
The National Fire Alarm Code, recommends performing
calibration tests at installation, then every other year.
Depending on local regulations, calibration testing might be
required more than once a year.
Perform functional testing yearly.
Test the calibration (to meet NFPA 72) using either the magnet
test or measuring the calibration with a calibrated product from
No Climb Products Ltd. Quickly determine the calibration by a
visual inspection of the detector’s LED (refer to Section 4.4
Flash Rate and Trouble Indication on page 22). These tests
confirm whether or not the detector is within its factory marked
calibration range.
At least once a year vacuum or wipe the external part of the
detector clean. Pay particular attention to the detector screens
in areas of heavy insect activity or dust. To clean the chamber,
i
NOTE! Notify all concerned parties before any
maintenance or testing of the fire alarm system and upon
completion of these activities.
F220 Series Detectors with F220-B6/C/E/R Bases General Information | en 3
Bosch Security Systems, Inc. Installation Manual 4998138694 -04 | 2007.01
use a can of clean, dry compressed air (such as TECHSPRAY
ENVI-RO-TECH Duster) which is available at office and alarm
supply stores. Shorten the plastic tube that comes with the
compressed air to about 2 in. (5 cm). Place the tube or needle
valve through the Chambermaid valve in the bottom of the
detector (refer to Figure 2.2 on page 7).
2 General Information
This document covers mounting, wiring, power requirements,
testing, and maintenance for the F220-B6, F220-B6C, F220-B6E,
and F220-B6R Detector Bases and the F220 Series Heat and
Photoelectric Smoke Detectors. Install them according to
NFPA 72.
For installation guidelines, refer to Installation Considerations
for Smoke and Fire Detectors (P/N: 26715).
2.1 F220-B6 Series Detector Bases
2.1.1 Compatible Control Panels
Two-wire:
i
NOTE! Do not paint the detectors. Paint or other foreign
matter covering the detector can prevent smoke
detection.
i
NOTE! For proper system installation, read and
understand NFPA-72 before installation.
i
NOTE! Bosch Security Systems, Inc. makes no claim
written, oral, or implied that the F220 Series Detectors
work with any two-wire control panels except those
specified in the Base Compatibility chart in Technical
Service Note (P/N: 4998148185).