Läs gratis den bruksanvisning för CyberPower 2POSTKIT (2 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 3 personer och har ett genomsnittsbetyg på 4.5 stjärnor baserat på 2 recensioner. Har du en fråga om CyberPower 2POSTKIT eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/2

2-POST RACKMOUNT KIT
INSTALLATION INSTRUCTIONS
K01-0000935-00
Step 1: Position the unit in the rack
Select the proper holes in the rack for positioning the unit in the
rack. Insert the cage nuts (Not needed for threaded rack)
Front:
Position 1,2,4,5
Rear:
Position 2,4
1
2
3
4
5
6
1U
2U
3U
Rack mount
rail
Rack mount ear (2U)
Rack mount ear
(3U)
INSTALLATION
UNPACKING
CAUTION! It is strongly recommended to have an additional
person assist with this installation process if the UPS or module is
heavy.
CAUTION! It is strongly recommended that the 2 post rack be
bolted to the floor prior to the installation of the UPS or module.
CAUTION! 2POSTKIT can be used with 1U, 2U, 3U, 4U, 5U and up
equipment but the weight cannot exceed 202 lbs.
CAUTION! One kit needed for each UPS or module. The technician
should not stack other UPS units or modules on top of the first unit
or module without using any mounting hardware or additional
2-post kits.
2-POST RACKMOUNT KIT INSTALLATION INSTRUCTIONS
This manual contains important instructions that should be
followed during installation of this 2-post rackmount kit
(2POSTKIT) into 2-post rack, along with the placement of a UPS or
other modules.
CAUTION! It is strongly recommended that the UPS or module be
installed with the kit at the bottom of the rack.
CAUTION! Prior to installing the UPS or other module, remove
internal batteries to reduce the weight of the UPS or other module.
Refer to the battery replacement section in the related user
manual for instructions.
2-POST RACKMOUNT KIT INSTALLATION INSTRUCTIONS
M5 cage nut (12) M5X12L black
pan head screws (8)
Rackmount left shelf Rackmount right shelf
2POSTKIT

OL1000RTXL2U, OL1000RTXL2UN, OL1500RTXL2U,
OL1500RTXL2UN, OL2200RTXL2U, OL2200RTXL2UN,
OL3000RTXL2U, OL3000RTXL2UN, OL3000RTXL2UHVN,
OL5KRTHD, OL6KRTHD, OL8KRTHD, OL10KRTHD,
OL1000ERTXL2U, OL1500ERTXL2U, OL2000ERTXL2U,
OL3000ERTXL2U, OL5KERTHD, OL6KERTHD, OL8KERTHD,
OL10KERTHD, OL6KRT, OL6KRTF, OL6KRTMB, OL6KRTMBTF,
OL6KRTHW, OL8KRT, OL8KRTF, OL8KRTMB, OL8KRTMBTF,
OL8KRTHW, OL10KRT, OL10KRTF, OL10KRTMB, OL10KRTMBTF,
OL10KRTHW, OL6000ERT3U, OL6000ERT3UD, OL6000ERT3UP,
OL8000ERT3U, OL8000ERT3UD, OL8000ERT3UP,
OL10000ERT3U, OL10000ERT3UD, OL10000ERT3UP, OL5KSTF,
OL6KSTF, OL10KSTF, OL6000RT3UTAA, OL6KRT2UTFHWIORTAA
PR750RT2U, PR1000RT2U, PR1500RT2U, PR2000RT2U,
PR2200RT2U, PR3000RT2U, PR750RTXL2U, PR1000RTXL2U,
PR1500RTXL2U, PR2000RTXL2U, PR2200RTXL2U,
PR3000RTXL2U, PR2200RTXL2UA, PR3000RTXL2UA,
PR2200RTXL2UHVA, PR3000RTXL2UHVA, PR1000RT2UN,
PR1500RT2UN, PR2000RT2UN, PR2200RT2UN, PR3000RT2UN,
PR1500RTXL2UN, PR2000RTXL2UN, PR2200RTXL2UN,
PR3000RTXL2UN, PR2200RTXL2UAN, PR3000RTXL2UAN,
PR2200RTXL2UHVAN, PR3000RTXL2UHVAN, PR750ERT2U,
PR1000ERT2U, PR1500ERT2U, PR2000ERT2U, PR2200ERT2U,
PR3000ERT2U, PR750ERTXL2U, PR1000ERTXL2U,
PR1500ERTXL2U, PR2000ERTXL2U, PR2200ERTXL2U,
PR3000ERTXL2U, PR2200ERTXL2UA, PR3000ERTXL2UA,
PR2200ERTXL2UAN, PR3000ERTXL2UAN, PR1000RTXL2UTAA,
PR1500RTXL2UTAA, PR2000RTXL2UTAA, PR3000RTXL2UTAA
Step 4: Secure the unit to the rack
Secure the unit to your rack with four screws at the front of the
rack. (Holes 2 and 5 as shown below) Once completed, perform the
same steps 1-4 for the other module.
Step 3: Rackmount ears installation
If there is a dust cover on the side, remove it from screw hole.
Attach the included rackmount ears to the center holes on the
sides of the unit by using the screws as shown below.
2-POST RACKMOUNT KIT INSTALLATION INSTRUCTIONS
Position 5
Position 2
INSTALLATION
COMPATIBILITY LIST FOR CYBERPOWER PRODUCT
Step 2: Adjust rackmount kit to fit your rack and secure the kit
The mounting depth of the kit can adjust from 2.9 inches to 3.9
inches (7.4 cm to 10 cm).
Adjust the depth to match your rack depth. Secure each
rackmount kit to your rack with four screws at the front of the rack
(square holes 1 and 4 as shown below). Secure the kit to the rear
of the rack with four screws (square holes 2 and 4 as shown below).
Position 2
Position 4
Position 2
Position 4
Position 4
Position 1
Position 4
Position 1
INSTALLATION
Cyber Power Systems, Inc. | www.CyberPowerSystems.com
For USA and Canada | 4241 12th Ave East, Suite 400, Shakopee, MN 55379 | Toll-free: 877.297.6937
For all other regions | Please visit our website for local contact information.
Copyright © 2021 Cyber Power Systems, Inc. All rights reserve.
BP36V60ART2U, BP72V60ART2U, BP144VL2U01, BP192VL2U01,
BPE36V60ART2U, BPE72V60ART2U, BPE36V60ART2US,
BPE72V60ART2US, BPE144VL2U01, BPE192VL2U01, BP240VL3U01,
BP240VL3U02, BPE240V30ART3U, BPE240V50ART3U,
BPE240V30ART3US, BPE240V50ART3US, BP48VP2U01,
BP48VP2U02, BP48VP2U03, BP48VP2U02TAA
Produktspecifikationer
Varumärke: | CyberPower |
Kategori: | Inte kategoriserad |
Modell: | 2POSTKIT |
Behöver du hjälp?
Om du behöver hjälp med CyberPower 2POSTKIT ställ en fråga nedan och andra användare kommer att svara dig
Inte kategoriserad CyberPower Manualer
3 April 2025
8 Januari 2025
8 Januari 2025
8 Januari 2025
4 Januari 2025
4 Januari 2025
24 December 2024
12 Oktober 2024
10 Oktober 2024
10 Oktober 2024
Inte kategoriserad Manualer
- Signature
- A3
- FOX ESS
- Raveland
- Aspes
- Antec
- Intellijel
- Ziehl
- Insect Lore
- Victor Technology
- Reginox
- Salton
- Venta
- Samlex
- Acer
Nyaste Inte kategoriserad Manualer
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025