Läs gratis den bruksanvisning för CyberPower OL8K10KRT3UTF (2 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 18 personer och har ett genomsnittsbetyg på 4.3 stjärnor baserat på 9.5 recensioner. Har du en fråga om CyberPower OL8K10KRT3UTF eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/2

OL8K10KRT3UTF Step-Down Transformer
For mission-critical enterprise applications requiring maximum power protection.
The CyberPower Smart App Online
OL8K10KRT3UTF rack/tower step-down
isolation transformer converts 208V input
voltage originating from utility power, a
UPS, or a generator to 120V output.
A 10-foot, NEMA L6-30P power cord
connects the OL8K10KRT3UTF to input
power. Over temperature protection
safeguards your OL8K10KRT3UTF from
damage if the internal heat exceeds safe
operating parameters.
A Three-Year Warranty ensures that this
extended battery module has passed
our highest quality standards in design,
assembly, material or workmanship.
UPS Compatibility
• Smart App Sinewave*
• Smart App Online*
Features
• 5000W
• Converts 208V from Utility Power,
UPS and Generator to 120V Output
• 120V 50/60Hz Output
• Over Temperature Protection
• Rack/Tower Form Factor
• 3-Year Limited Warrant

OL8K10KRT3UTF Step-Down Transformer
For mission-critical enterprise applications requiring maximum power protection.
©CyberPowerSystems(USA)IncAllrightsreservedCyberPowerreservestherighttochangewithoutpriornoticeproductofferingsorspecifications
GENERAL
Type Step-Down Transformer
Over Temperature Protection Yes
UPS Compatibility*
OL3000RTXL2UHV
OL6000RT3U
OL6000RT3UPDU
OL6KRT3UHW
OL8000RT3U
OL8000RT3UPDU
OL8KRT3UHW
OL10000RT3U
OL10000RT3UPDU
OL10KRT3UHW
PR5000LCDRTXL5U
PR6000LCDRTXL5U
INPUT
Nominal Input Voltage 208Vac
Input Voltage Range 200Vac – 240Vac
Input Frequency Range 50/60Hz
Input Amperage 30A (Derated 24A)
Plug Type NEMA L6-30P
Cord Length 10'
OUTPUT
VA 5,000 (5.0 kVA)
Watts 5,000 (5.0 kW)
Nominal Output Voltage 120Vac and 208Vac
Frequency 50/60Hz
Outlets - Total 16
Outlet Type
(12) NEMA 5-20R
(2) NEMA L6-20R
(2) NEMA L6-30R
Overload Protection Output Circuit Breakers
PHYSICAL
Form Factor Rack/Tower
Installed Rack Height 3U
Mounting Hardware Included
Enclosure Contruction Steel
Dimensions (WxHxD) (in.) 17 x 5.25 x 26
Dimensions (WxHxD) (mm.) 433 x 132 x 660
Weight (lbs.) 159.7
Weight (kg.) 72.6
Shipping Specifications
Dimensions (WxHxD) (in.) 23.6 x 14.9 x 35.4
Dimensions (WxHxD) (mm.) 600 x 378 x 900
Weight (lbs.) 195.8
Weight (kg.) 89
ENVIRONMENTAL
Operating Temperature 32 °F to 104 °F / 0 °C to 40 °C
Operating Humidity 0% - 90% non-condensing
Operating Elevation 0-10000 feet (0-3000 meters)
Storage Temperature -4°F to 113°F / -20°C to 45°C
Storage Relative Humidity 0% - 95% non-condensing
Storage Elevation 0-50000 feet (0-15000 meters)
Online Thermal Dissipation 898 BTU/hr
Audible noise at 1.5M from surface
of unit 55 dBA
CERTIFICATIONS
Safety UL, cUL, CE
Environmental RoHS Compliant
WARRANTY
Product Warranty 3 Years Limited
Produktspecifikationer
Varumärke: | CyberPower |
Kategori: | Inte kategoriserad |
Modell: | OL8K10KRT3UTF |
Behöver du hjälp?
Om du behöver hjälp med CyberPower OL8K10KRT3UTF ställ en fråga nedan och andra användare kommer att svara dig
Inte kategoriserad CyberPower Manualer
3 April 2025
8 Januari 2025
8 Januari 2025
8 Januari 2025
4 Januari 2025
4 Januari 2025
24 December 2024
12 Oktober 2024
10 Oktober 2024
10 Oktober 2024
Inte kategoriserad Manualer
- Losi
- Vivotek
- Axxess
- SolidDrive
- Digitalinx
- Glem Gas
- Veber
- Quadro
- Vanish
- Level Mount
- Silverline
- Vipack
- Hotpoint
- Doepke
- Gill
Nyaste Inte kategoriserad Manualer
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025