Automatic Transfer Switch
USER'S MANUAL
Table of Contents
Overview 1 .................................................................................
Model List 1 ...............................................................................
Product Contents 2 ..................................................................
For 1U Models 2 .............................................................................................
For 2U Models 3 ............................................................................................
Product Features 4 ..................................................................
Front/Rear Panel Description (1U 15A Models) 4 ............................
Technical Specifications 4 ........................................................................
Front/Rear Panel Description (1U 20A Models) 5 ...........................
Technical Specifications 5 .........................................................................
Front/Rear Panel Description (2U 30A Models) ..........................6
Technical Specifications 6 .........................................................................
Front/Rear Panel Description (2U 32A Models) 7 ...........................
Technical Specifications 7 .........................................................................
Installation Guide 8 ..................................................................
ATS PDU Configuration 8 ..........................................................................
Front Mounting 9 ..........................................................................................
For 1U Models 9 .......................................................................................
For 2U Models 10 ....................................................................................
Rear Mounting .......................................................................................... 1 1
For 1U Models .....................................................................................1 1
For 2U Models 13 ....................................................................................
Replacing LCD Panel 15 .............................................................................
Electrical Installation 15 .............................................................................
Power Cord Locking - For IEC Type ATS PDU 16 ............................
Input Power Cord 16 ..............................................................................
Output Power Cord 16 ..........................................................................
Network Installation 17 ...............................................................................
Operation 18 ..............................................................................
Remote Management 18 ............................................................................
Web ........................................................................................................18
Telnet and SSH 18 ...................................................................................
SNMP 18 .....................................................................................................
Local Management 18 .................................................................................
LCD Operation 18 ...................................................................................
LED Indicators 19 ....................................................................................
Environmental Monitoring (optional) 19 ........................................
Device Reset 19 .......................................................................................
Unattended/Automatic Shutdown 19 .............................................
Firmware Upgrade..............................................................20
ATS PDU 20 ..............................................................................................
LCD ...................................................................................................... 2 1
RMCARD 23 ..............................................................................................
Troubleshooting 25 .................................................................
Conformance Approvals 26 ....................................................
Customer Service & Warranty .......................................... 27
Appendix A-Hyper Terminal 28 .............................................
Appendix B-Power Device Network Utility 29 ....................
1
Overview
CyberPower Automatic Transfer Switches PDUs with dual input for power
provide redundant and increased reliability for critical devices with a single
power plug. Users can define the preferred input power source. When a
selected source is unstable or unavailable, the ATS PDU will switch to the
second power source to constantly provide power to connected devices. The
entire ATS PDU series are designed with LED and LCD interfaces for users
to easily observe power status and device load. On-site power management
is accomplished as users can configure power settings, via LCD interface,
according to local power condition. Available in both switched and metered/
monitored configurations, users have a broad base of options to select the
ATS PDU that best fits their needs.
WARNING: This automatic transfer switch has dual power cords (A & B) to
provide redundant power sources to devices with single power supplies and
can be plugged into separate compatible sources* to ensure continuous
access. Users select the preferred source as the primary input. CyberPower
Smart App Online and Sinewave series UPS are highly recommended for use
as the power source.
* Only sine wave AC power sources are compatible with this ATS PDU. Note:
Simulated sine wave AC power sources are NOT compatible.
Model List
Switched Series Metered/Monitored Series
1U 1U
PDU15SW10ATNET PDU15M10AT
PDU20SW10ATNET PDU20M10AT
PDU20SWT10ATNET PDU20MT10AT
PDU20SWHVT10ATNET PDU20MHVT10AT
PDU15SWHVIEC12ATNET PDU15MHVIEC12AT
PDU20SWHVIEC10ATNET PDU20MHVIEC10AT
PDU20SWHVCEE10ATNET* PDU20MHVCEE10AT*
2U 2U
PDU30SWT17ATNET PDU30MT17AT
PDU30SWHVT19ATNET PDU30MHVT19AT
PDU32SWHVCEE18ATNET* PDU32MHVCEE18AT*
*Selected models may not be available in certain regions. Please contact your
CyberPower sales team for more information.
Safety Precautions
Read the following before installing or operating the Automatic Transfer
Switches (ATS) PDU:
Use only the supplied hardware to attach the mounting brackets.
The ATS PDU must be plugged into a single phase three-wire, grounded
outlet on a circuit that is protected by a fuse or circuit breaker. For
PDU15xxxxx series, please use a 15A circuit protector. For PDU20xxxxx
series, please use a 20A circuit protector. For PDU30xxxxx series,
please use a 30A circuit protector. Connection to any other type of
power outlet may result in a electrocution hazard.
Do not use extension cords or adapters with these ATS PDUs.
Never install an ATS PDU or associated wiring or equipment during a
lightning storm.
Ensure that the power cord, plug, and socket are in good condition.
To prevent the risk of fire or electrocution, this ATS PDU should
be installed in a temperature and humidity controlled indoor area
free of conductive contaminants. Do not install this ATS PDU where
excessive moisture or heat is present.
Before using, please check to ensure the package contains all the
items shown below. If there are missing parts, please contact your
local CyberPower sales team for technical support.
Check
3
For 2U Models
Product Contents
ATS PDU
Mounting Bracket x 2 24 (M4x8) Bracket Mounting Screws
(Includes eight spares)
6 (M5x12) Rack Mounting Screws/
6 Washers (Includes two spares for each)
Cord Retention Tray X 2 8 (M3x4) Cord Retention Tray
Mounting Screws
Cable Ties
Qty.: 30 (NEMA Outlet)
Qty.: 50 (IEC Outlet)
RJ45/DB9 Serial Port
Connection Cable
Jumper (Switched type only)
User's Manual, Registration & Software Download Cards
U
s
e
rs
M
a
nu
a
l
Registration
Card
PowerPanel
Management Software
4
Product Features
Technical Specifications
Switched Series Metered Series
Model Name PDU15SW10ATNET PDU15SWHVIEC12ATNET PDU15M10AT PDU15MHVIEC12AT
Input
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Frequency 50/60Hz
Derated Input Current 12A 12A(UL)/10A(CE) 12A 12A(UL)/10A(CE)
Plug Type (2) NEMA 5-15P (2) IEC-320 C14 (2) NEMA
5-15P (2) IEC-320 C14
Power Cord Type SR (14 AWG) Socket SR (14 AWG) Socket
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Derated Output Current 12A 12A(UL)/10A(CE) 12A 12A(UL)/10A(CE)
Outlet Type NEMA 5-15R IEC-320 C13 NEMA 5-15R IEC-320 C13
Outlet Number 10 12 10 12
Transfer Time Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD Yes, with optional
RMCARD
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 1.75" x 9.3"/433mm x 44mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32oF to 113oF/0oC to 45oC
Safety Approvals
Certifications UL 60950-1
FCC Class A
UL 60950-1
CE, FCC Class A
UL 60950-1
FCC Class A
UL 60950-1
CE, FCC Class A
* All specifications are subject to change without notice.
NEMA Type
IEC Type
A. SNMP/HTTP Network Slot
Allows users to remotely control and monitor the ATS PDU when installed
with CyberPower’s Remote Management Card.
B. Serial Port (RJ45 modular port)
Use serial port to connect with PC and execute local control of the ATS PDU.
C. Source Indicator
Indicates Source A or B is in use. When both sources are normal, selected
source shows constant green LED while another source shows blinking
green LED.
D. Output Indicator
Indicates load condition of the ATS PDU.
E. Multifunction LCD Readout
Displays various ATS PDU information such as power and load conditions.
F. Select Button
Use to control the LCD screen and toggle through the available
informational options.
G. Enter Button
Use to choose selected items, enter to next level menu or return to
previous menu.
H. AC Inlet/AC Power Cord
Use to connect ATS PDU to utility power or UPS.
I. Ground Stud
Use to ground the ATS PDU.
J. AC Output Receptacles
Provides power distribution for connected equipment.
K. Outlet Indicator (switched series only)
When the LED is on, the outlet is providing power to connected
equipment.
Front/Rear Panel Description (1U 15A Models)
Provides SNMP Card Co mmunication
Expansion Port
Select
Ente r
PDU20SWHVIEC10ATNET
A
B
Source Output
- Normal
- Warning
- Overloa d
QCN-0000003-00
Serial Port
A B C D E F G
H I K
J
H I K
J
SOURC E A SOURC E B
8 9 103 4 6
1 2 3 4 5 6 7 8 9 10 11 1 2
SOU RCE A
SOU RCE B
5
Product Features
Front/Rear Panel Description (1U 20A Models)
NEMA Type
IEC Type
A. SNMP/HTTP Network Slot
Allows users to remotely control and monitor the ATS PDU when installed
with CyberPower’s Remote Management Card.
B. Serial Port (RJ45 modular port)
Use serial port to connect with PC and execute local control of the ATS PDU.
C. Souce Indicator
Indicates Source A or B is in use. When both sources are normal, selected
source shows constant green LED while another source shows blinking
green LED.
D. Output Indicator
Indicates load condition of the ATS PDU.
E. Multifunction LCD Readout
Displays various ATS PDU information such as power and load conditions.
F. Select Button
Use to control the LCD screen and toggle through the available
informational options.
G. Enter Button
Use to choose selected items, enter to next level menu or return to
previous menu.
H. AC Inlet/AC Power Cord
Use to connect ATS PDU to utility power or UPS.
I. Ground Stud
Use to ground the ATS PDU.
J. AC Output Receptacles
Provides power distribution for connected equipment.
K. Outlet Indicator (switched series only)
When the LED is on, the outlet is providing power to connected
equipment.
Technical Specifications
Switched Series Metered Series
Model Name
PDU20SW10ATNET PDU20SWHVT10ATNET PDU20M10AT PDU20MHVT10AT
PDU20SWHVCEE10ATNET PDU20MHVCEE10AT
PDU20SWT10ATNET PDU20MT10AT
PDU20SWHVIEC10ATNET PDU20MHVIEC10AT
Input
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Frequency 50/60Hz
Derated Input Current 16A
Plug Type
(2) NEMA 5-20P (2) NEMA L6-20P (2) NEMA 5-20P (2) NEMA L6-20P
(2) IEC 309 16A (2) IEC 309 16A
(2) NEMA L5-20P (2) NEMA L5-20P
(2) IEC-320 C20 (2) IEC-320 C20
Power Cord Type SR (12AWG) SR (12AWG) SR (12 AWG) SR (12AWG)
Socket Socket
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Derated Output Current 16A
C13: 12A (UL)
10A (CE)
C19: 16A
16A
C13: 12A (UL)
10A (CE)
C19: 16A
Outlet Type NEMA 5-20R (8) IEC C13
(2) IEC C19 NEMA 5-20R (8) IEC C13
(2) IEC C19
Outlet Number 10 8+2 10 8+2
Transfer Time Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD Yes, with optional
RMCARD
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 1.75" x 9.3"/433mm x 44mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32oF to 113oF/0oC to 45oC
Safety Approvals
Certifications UL 60950-1
FCC Class A
UL 60950-1
FCC Class A UL 60950-1
FCC Class A
UL 60950-1
FCC Class A
UL 60950-1
CE, FCC Class A
UL 60950-1
CE, FCC Class A
* All specifications are subject to change without notice.
Provides SNMP Card Co mmunication
Expansion Port
Select
Ente r
PDU20SWT10ATNET
A
B
Source Output
- Normal
- Warning
- Overloa d
QCN-0000002-00
Serial Port
A B C D E F G
H I K
J
H I K
J
SOURC E A SOURCE B
3 4 5 6 7 8 9 1021
SOURC E A
SOURC E B
1 2 3 4 5 6 7 8 9 10
6
Provides SNMP Card Communication
Expansion Port
Serial Port
Selec t
Ente r
PDU30SWT17ATNET
A
B
Source Output
- Normal
- Warning
- Overloa d
QCN-0000005-00
B1
B2
B3
A B C D E F G
H
H
K
K
J
I
I
J
L
L
SOURCE A
SOURCE B
BANK 1
(20A)
BANK 2
(20A)
BANK 3
(24A)
L5-30R
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
BANK 1
SOURC E A
SOURC E B
(20A)
BANK 2 (2 0A)
BANK 3 (2 4A)
L6-30R
19
1 2 3 4
10 11 12 13
5 6 7 8
14 15 16 17
9
18
NEMA Type
IEC Type
A. SNMP/HTTP Network Slot
Allows users to remotely control and monitor the ATS PDU when installed
with CyberPower’s Remote Management Card.
B. Serial Port (RJ45 modular port)
Use serial port to connect with PC and execute local control of the ATS PDU.
C. Source Indicator
Indicates Source A or B is in use. When both sources are normal, selected source
shows constant green LED while another source shows blinking green LED.
D. Output Indicator
Indicates load condition of the ATS PDU.
E. Multifunction LCD Readout
Displays various ATS PDU information such as power and load conditions.
F. Select Button
Use to control the LCD screen and toggle through the available
informational options.
G. Enter Button
Use to choose selected items, enter to next level menu or return to previous
menu.
H. AC Inlet/AC Power Cord
Use to connect ATS PDU to utility power or UPS.
I. AC Output Receptacles
Provides power distribution for connected equipment.
J. Outlet Indicator (switched series only)
When the LED is on, the outlet is providing power to connected equipment.
K. Circuit Breaker
Provides output overload protection.
L. Ground Stud
Use to ground the ATS PDU.
Technical Specifications
Switched Series Metered Series
Model Name PDU30SWT17ATNET PDU30SWHVT19ATNET PDU30MT17AT PDU30MHVT19AT
Input
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Frequency 50/60Hz
Derated Input Current 24A
Plug Type (2) NEMA L5-30P (2) NEMA L6-30P (2) NEMA L6-30P(2) NEMA L5-30P
Power Cord Type SR (10 AWG)
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 100-120V 200-240V 100-120V 200-240V
Derated Output Current 5-20R: 16A
L5-30R: 24A
C13: 12A
C19: 16A
L6-30R: 24A
5-20R: 16A
L5-30R: 24A
C13: 12A
C19: 16A
L6-30R: 24A
Derated Output Current
(each bank) 20A
Bank Number 2
Outlet Type (16) NEMA 5-20R
(1) NEMA L5-30R
(16) IEC C13
(2) IEC C19
(1) NEMA L6-30R
(16) NEMA 5-20R
(1) NEMA L5-30R
(16) IEC C13
(2) IEC C19
(1) NEMA L6-30R
Outlet Number 17 19 17 19
Circuit Breaker Yes
Transfer Time Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD
Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD Yes, with optional
RMCARD
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 3.5" x 9.3"/433mm x 88mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32oF to 113 oF/0
oC to 45
oC
Safety Approvals
Certifications UL 60950-1, FCC Class A
* All specifications are subject to change without notice.
Product Features
Front/Rear Panel Description (2U 30A Models)
7
Product Features
Front/Rear Panel Description (2U 32A Models)
A. SNMP/HTTP Network Slot
Allows users to remotely control and monitor the ATS PDU when
installed with CyberPower’s Remote Management Card.
B. Serial Port (RJ45 modular port)
Use serial port to connect with PC and execute local control of the
ATS PDU.
C. Source Indicator
Indicates Source A or B is in use. When both sources are normal,
selected source shows constant green LED while another source
shows blinking green LED.
D. Output Indicator
Indicates load condition of the ATS PDU.
E. Multifunction LCD Readout
Displays various ATS PDU information such as power and load
conditions.
F. Select Button
Use to control the LCD screen and toggle through the available
informational options.
G. Enter Button
Use to choose selected items, enter to next level menu or return to
previous menu.
H. AC Inlet/AC Power Cord
Use to connect ATS PDU to utility power or UPS.
I. AC Output Receptacles
Provides power distribution for connected equipment.
J. Outlet Indicator (switched series only)
When the LED is on, the outlet is providing power to connected
equipment.
K. Circuit Breaker
Provides output overload protection.
L. Ground Stud
Use to ground the ATS PDU.
Technical Specifications
Switched Series SeriesMetered
Model Name PDU32SWHVCEE18ATNET PDU32MHVCEE18AT
Input
Nominal Voltage 200-240V
Frequency 50/60Hz
Max. Input Current 32A
Plug Type (2) IEC 309 32A
Power Cord Type SR (10 AWG)
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage 200-240V
Derated Output Current
C13: 10A
C19: 16A
Derated Output Current
(each bank) 20A
Bank Number 2
Outlet Type (16) IEC C13
(2) IEC C19
Outlet Number 18
Circuit Breaker Yes
Transfer Time Typical: 8-12ms
16ms max @ 60Hz/ 18ms max @ 50Hz
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
SNMP/ HTTP Capable Yes, with RMCARD Yes, with optional
RMCARD
Connectivity RJ45 (Serial Port)
Sensor Capable Optional
Physical
Dimension (W x H x D) 17.05" x 3.5" x 9.3"/433mm x 88mm x 236mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 13100 ft/4000 m
Temperature 32oF to 113oF/0oC to 45oC
Safety Approvals
Certifications CE, FCC Class A
* All specifications are subject to change without notice.
A B C D E F G
Provides SNMP Card Commu nication
Expansion Port
Select
Enter
A
B
Source Outpu t
- Normal
- Warning
- Overload
B1
B2
Serial Port
QCN-0000021-00 PDU32SWHV CEE18ATNET
H
I
J K L
BANK 1 (20A)
BANK 2 (20A )
1 2 3 4
13121110 14 15 16 17
8765 9
18
8
Installation Guide
ATS PDU Configuration
WARNING: This automatic transfer switch has dual power cords (A & B) to
provide redundant power sources to devices with single power supplies and
can be plugged into separate compatible sources* to ensure continuous
access. Users select the preferred source as the primary input. CyberPower
Smart App Online and Sinewave series UPS are highly recommended for use
as the power source.
* Only sine wave AC power sources are compatible with this ATS PDU. Note:
Simulated sine wave AC power sources are NOT compatible.
CyberPower Online UPS
Utility Power Utility Power
CyberPower Online UPS
SOURCE A
SOURCE B
CyberPower ATS PDU
Equipment Loads
Best Configuration
Minimum Acceptable Configuration
CyberPower Sinewave UPS
Utility Power
CyberPower ATS PDU
ON/OFF
SELE CT
SOURCE A
(Preferred Source)
SOURCE B
Equipment Loads
9
Installation Guide
Front Mounting
Step 1. Mounting Bracket Installation
Use the provided Mounting Bracket Screws (16) to attach the
Mounting Brackets (2) to the ATS PDU.
Step 2. Cord Retention Tray Installation (optional)
Adjust the length of the Cord Retention Tray till the screw hole on the
Tray and ATS PDU are aligned. Attach the Cord Retention Tray to the
ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws.
Tighten the Cord Retention Tray with the screw on it.
Step 3. ATS PDU Mounting
Use the provided Washers (4) and Screws (4) to secure the ATS PDU
to your existing rack system.
Note: You may also use the screw sets provided by the rack to secure
the ATS PDU.
Please only use the provided screws for the entire installation process.
For 1U Models
10
Installation Guide
Step 4. Cable Ties (Optional)
Use the provided Cable Ties to fasten each cord to the Cord
Retention Tray.
For 2U Models
Step 1. Mounting Bracket Installation
Use the provided Mounting Bracket Screws (16) to attach the
Mounting Brackets (2) to the ATS PDU.
Step 2. Cord Retention Tray Installation (optional)
Adjust the length of the Cord Retention Trays till the screw hole on
the Trays and ATS PDU are aligned. Attach the Cord Retention Trays
to the ATS PDU with the 8 supplied Cord Retention Tray Mounting
Screws. Tighten the Cord Retention Trays with the screw on it.
Front Mounting
11
Installation Guide
Step 3. ATS PDU Mounting
Use the provided Washers (4) and Screws (4) to secure the ATS PDU
to your existing rack system.
Note: You may also use the screw sets provided by the rack to secure
the ATS PDU.
Step 4. Cable Ties (Optional)
Use the provided Cable Ties to fasten each cord to the Cord
Retention Tray.
Rear Mounting
For 1U Models
Step 1. Mounting Bracket Installation
Use the provided Mounting Bracket Screws (16) to attach the
Mounting Brackets (2) to the ATS PDU.
Front Mounting
12
Installation Guide
Rear Mounting
If you plan on attaching the Cord Retention Tray to the ATS PDU, use
the provided Mounting Bracket Screws (8) to attach the Mounting
Brackets (2) to the ATS PDU.
Step 2. Cord Retention Tray Installation (optional)
Adjust the length of the Cord Retention Tray till the screw hole on the
Tray and ATS PDU are aligned. Attach the Cord Retention Tray to the
ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws.
Tighten the Cord Retention Tray with the screw on it.
Step 3. ATS PDU Mounting
Use the provided Washers (4) and Screws (4) to secure the ATS PDU
to your existing rack system.
Note: You may also use the screw sets provided by the rack to secure
the ATS PDU.