Läs gratis den bruksanvisning för Daikin BDGTA34 (4 sidor) i kategorin Luftkonditionering. Guiden har ansetts hjälpsam av 3 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 2 recensioner. Har du en fråga om Daikin BDGTA34 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/4
WARNING CAUTION
Read through this Installation Manual before installing.
WARNING
Installer must apply for standard installation guidance.
• Please perform the installation work, select insulation, and perform heat insulation construction in accordance with
the laws and regulations of each country.
For specifications of connection piping, refer to Table 1 below.
• Piping is limited to newly installed piping.
Even with newly installed piping, remove places to which brazing material is adhered, or which have been burnt by the burner.
• Please keep minimum wall thickness of the pipe for installation.
• Do not disassemble the GAS TIGHT JOINT.
When working in high places, work must be performed with a stable scaffold.
• Carry out the work of connecting the GAS TIGHT JOINT one location at a time, making sure each location is secure.
(Do not perform simultaneous work on 2 or more locations between the same outdoor and indoor unit)
• Do not use the GAS TIGHT JOINT which has been dropped.
The GAS TIGHT JOINT cannot be re-used if it has already been inserted into the piping, temporarily fixed, and removed.
Do not turn the nut in the loosening direction.
INSTALLATION MANUAL
SDGTB06
·
09
·
12
·
15
·
19
·
22
·
28
SDGTB0906
·
1209
·
1512
·
1915
·
2219
·
2522
·
2825
·
3428
BDGTA34
·
41, SDGTLB22
·
28
3V022006-1A
GAS TIGHT JOINT
The case which may cause
dangerous situation such as
death or severe injury, at the
same time, it may cause
property damage when
mis-operated.
The case which may cause
dangerous situation such as
injury or minor injury, at the
same time, it may cause
property damage when
mis-operated.
R410A, R32 UNIT ONLY
Removing the thermal insulation
material (copper pipe)
1
1) Be careful not to damage the pipe.
2) If using insulated copper pipe, cut in a
cylindrical direction, not in a lengthwise
direction.
(Cylindrical direction)
(Lengthwise direction)
R32: Type BDGTA34/41 are not applicable in the EU
Table 1 : Specication of connection piping
Standard
ASTM B280 ASTM B88 (Type L) EN12735
Model name
Size (O.D.) O60 H58 Thickness (mm)
O60
O50
H58 Thickness (mm) R220 R250 R290 Thickness (mm)
Same diameter Different diameter
SDGTB06
SDGTB0906
φ6.35
0.762±0.08
0.80±0.08
1.00±0.13
SDGTB09
SDGTB1209
φ9.52
0.813±0.08
0.762±0.08
0.80±0.08
1.00±0.13
SDGTB12
SDGTB1512
φ12.7
0.813±0.08
0.889±0.11
0.80±0.08
0.91±0.09
1.00±0.13
SDGTB15
SDGTB1915
φ15.88
0.889±0.11
1.016±0.11
0.91±0.09
1.00±0.13
SDGTB19
SDGTB2219
φ19.05
1.07±0.10
1.07±0.11
1.00±0.13
1.25±0.19
SDGTB22
SDGTLB22 SDGTB2522
φ22.22
1.14±0.10
1.14±0.11
1.00±0.13
1.25±0.19
1.63±0.25
SDGTB2825
φ25.4 *2
1.00±0.13
SDGTB28
SDGTLB28
SDGTB3428
φ28.58
1.27±0.10
1.27±0.13
1.00±0.13
1.25±0.19
1.63±0.25
BDGTA34
φ34.92
1.40±0.15
1.40±0.15
1.25±0.19
1.63±0.25
BDGTA41
φ41.28
1.52±0.15
1.52±0.15
1.25±0.19
1.63±0.25
Notes) 1. “–” : No settings
2. *2 : For connection to the stop valve outlet pipe only.