Dormakaba ISPSFPD-1.5 Bruksanvisning

Läs gratis den bruksanvisning för Dormakaba ISPSFPD-1.5 (8 sidor) i kategorin kontroll system för säkerhets åtkomst. Guiden har ansetts hjälpsam av 4 personer och har ett genomsnittsbetyg på 4.8 stjärnor baserat på 2.5 recensioner. Har du en fråga om Dormakaba ISPSFPD-1.5 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/8
PDD-FT-1.5
Fire Panel Interface
With EOL Trigger
Installation and Specifications Manual
PDD-FT-1.5
InstallatIon
ISPSFPD-1.5
PCN18003
R04-18GR-1
© 2018 dormakaba Canada Inc.
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.com
Details
The PDD-FT board is a fire panel control interface. This board can be used to control DC
output based on a fire alarm control panel. Two outputs switch state on alarm.
Features
• NonLatchingorLatchingmode
• Universal12VDCor24VDCOperation
• Reversepolarityprotected
• NormallyON&NormallyOFFOutput
• OutputLED’sindicatecondition
• OutputscanbeTriggeredwith:
1)N/OorN/CSwitchwithSupervisedEndofLineResistor(EOL)
2)N/CSwitchwith(OVR)override
3)N/CSwitchwithAUX-INauxiliary
4)Groundonanytriggerinputwhen(GRN)Jumperisenabled
• FormCDPDTContactsIndicatesTriggerStatus
• 1.5AmpTransferRelayContacts
• Autoormanualresetbyjumperselection
Installation Instructions
1. MountthePDD-FTboardinasuitablelocationincloseproximitytothepowersupply.
Note:
a) Groundfaultdetectionwillonlyworkifconductivestandoffsareusedandpower
supplyenclosureisproperlygrounded.
b) Asthisdevicecanbeusedtopowermultipledevicesensurethatallwiringisofan
appropriategaugeforthedevicesbeinginstalled.
c) ThisRCIboardisforuseinacontrolledenvironment.ThePDD-FT-1.5and
alldevicesconnectedtoorpoweredthroughthePDD-FT-1.5shallbeinstalledwithin
thesamecontinuousbuildingstructure.Installationmustbeinaccordancewith
localbuildingandfirecodes.CheckwithAuthorityHavingJurisdiction(AHJ)for
detailspriortoinstalling.
d) Allpowerlimitedwiringmustbeaminimumof.25”fromnon-powerlimitedwiring.
e) Maximumtorqueof7in*lbforblackinputandoutputterminals.
2.Connect“INPUT”terminalstooutputofDCsupply,payingcloseattentiontopolarityof
DCoutputfrompowersupply.
3.ConnectdevicestobepoweredtooutputterminalsofPDD-FTcontrolboard,paying
closeattentiontopolarityrequirements.Minimum22AWGandmaximumdistance
of6170ft.forfieldwiring.
4.Setjumpers(RST,OVR,AUX,andGRN)asrequiredforproperinstallation.
2

Produktspecifikationer

Varumärke: Dormakaba
Kategori: kontroll system för säkerhets åtkomst
Modell: ISPSFPD-1.5

Behöver du hjälp?

Om du behöver hjälp med Dormakaba ISPSFPD-1.5 ställ en fråga nedan och andra användare kommer att svara dig




kontroll system för säkerhets åtkomst Dormakaba Manualer

kontroll system för säkerhets åtkomst Manualer

Nyaste kontroll system för säkerhets åtkomst Manualer