Läs gratis den bruksanvisning för Growatt SYN100-XH-30 (4 sidor) i kategorin Solpanel. Guiden har ansetts hjälpsam av 3 personer och har ett genomsnittsbetyg på 4.1 stjärnor baserat på 2 recensioner. Har du en fråga om Growatt SYN100-XH-30 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/4
1
1
1
11.
.
.
..
2
2
2
22.
.
.
..
SYN 100-XH-30 Quick Guide
Overview
Installation
System overview
2.2 Installation requirements
2.1 Electrical parameters
frame or a pole and keep it free from direct sunlight.
2. To ensure heat dissipation, please maintain at least a 300 mm clearance between the SYN 100-XH-
30 and other objects.
3. Place the mounting bracket against the wall/pole and mark the drilling hole positions.
4. Drill holes and mount the bracket. Ensure that the bracket is securely installed.
5. Install the SYN 100-XH-30 onto the mounting bracket.
1 2 3 4 5
6
7 8 9
Normal Loads
Critical Loads
Inverter
Battery
Meter
Backup
Box
CT
Communication cable
Power cable
15°
300
300
300
500
365.0
486.3
92.5
134.7
120.2
Note:
1. The critical load power depends on the power rating
of the inverter and battery.
2. The off-grid function is only available when the XH
inverter is paired with the APX battery system and
the backup box.
Model name
SYN 100-XH-30
Nominal grid
voltage
3W/N/PE
230/400 a.c.V
Range of grid
voltage
312 485 a.c.V
Max. grid
current
125 a.c.A
Max.
continuous
grid current
90 a.c.A
Nominal grid
frequency
50/60Hz
Range of grid
frequency
45 65Hz
Max.
continuous
inverter input
current
58 a.c.A
Max. backup
output current
58 a.c.A
2.3 Installation steps
(1) Front panel
(2) LED indicator
(3) Screw for front panel
(4) Mounting bracket
(9) Waterproof plugs
( ) 5 Grid wiring port
( )6 Inverter wiring port
( ) 7 Load wiring port
( )8 COM wiring port
Dimensions (Unit: mm)
Unit: mm
30.5
82
164
12
16
No.
Name
Size
No.
Name
Size
1
Flat-blade
screwdriver
Φ2&5 mm
2
Hammer
/
3
Allen wrench
Φ5 mm
4
Phillips
screwdriver
Φ5 mm
5
Electric drill
Φ6 mm
6
Wire stripper
/
7
Pliers
/
2 4. Required tools
3 1. Wiring instructions
1. Remove the two screws on the upper cover of the SYN 100-XH-30 to open the upper cover, and do
not remove the cover inside the machine.
2. Twist the plastic cover printed with "Grid" counterclockwise, remove the five waterproof plugs, and
reserve five holes.
3. Route the five power grid cables (L1/L2/L3/N/PE) through the five holes and connect them to the
power grid input terminals and the ground copper bar. Screw torques for tightening the power grid
terminals and ground terminals are shown in the following table.
4. Finally, fasten the plastic cover clockwise. The wiring method is shown in Figure 3.
3
3
3
33.
.
.
..
Recommended cable specifications
Please prepare suitable cables for the connection of the SYN box following the recommended specifications, and the stripped length of the
cables is 10 mm.
Cable
Cable outer
diameter
Cable length
Grid input cable
4-6 AWG
10 m
Inverter input cable
6-8 AWG
20 m
Load output cable
6-8 AWG
20 m
Communication cable
22-26 AWG
20 m
4-6 AWG
10 m
L
10 mm
10 m
4-6 AWG
4-6 AWG
N
10 mm
10 m
PE
10 mm
Grid AC cable
20 m
6-8 AWG
L
10 mm
20 m
6-8 AWG
6-8 AWG
N
10 mm
20 m
PE
10 mm
Load and lnverter AC cable
20 m
20 m
22-26 AWG
22-26 AWG
L
10 mm
N
10 mm
Communication cable
3.1.1 Connecting SYN 100-XH-30 to the Grid
3.1.2 Connecting SYN 100-XH-30 to the Inverter
When connecting the SYN 100-XH-30 to the XH Inverter, you need to connect the AC power cables and the communication cables.
1 2 3 4
5 6
7
2
Note: PE cables need to be crimped with the O-type
terminal in the accessory bag, as shown in
Figure 2.
1
Screw torque
Power grid terminals
26.5 to 31 in*lbs
Ground terminal
13 in*lbs
3
SYN 100-XH-30
Grid
Grid
PE
N
L3 L2 L1
L1
L2
L3
N
PE
Connecting to the Grid
L1
GRID
BYPASS
INVERTER
LOAD
L2 L3 N L1 L2 L3 L1 L2 L3 N L1 L2 L 3 N
1. Twist the plastic cover printed with "Load" counterclockwise,
remove the five waterproof plugs, and reserve five holes.
2. Route the five load cables (L1/L2/L3/N/PE) through the five holes,
connect them to the load circuit breaker terminals (L1/L2/L3), load
connect terminal (N) and the ground copper bar. Screw torques for
tightening the load breaker terminals, ground terminals and load
connect terminals are shown in the following table.
3. Finally, fasten the plastic cover clockwise. The wiring method is
shown to the right:
4
4
4
44.
.
.
..
Indicator description
System state
Indicator status
Green
Red
On-grid Mode
On
Off
Back-up Mode
Blinking (on for 1s, and then Off for 1s)
Off
No communication with the inverter
Off
Blinking (on for 1s, and then Off for 1s)
System fault
Off
On
Firmware upgrade
When the upgrade starts, the yellow light is on or off for 10-20s, and then the yellow
light blinks at intervals of 2s (On for 1s and then Off for 1s).
3.1.3 Connecting SYN 100-XH-30 to the load
1. Twist the plastic cover printed with "Inverter" counterclockwise;
remove the five waterproof plugs, and reserve five holes.
2. Route the five cables of the inverter (L1/L2/L3/N/PE) through
the five holes, connect the cables to the inverter breaker terminals
(L1/L2/L3), inverter connect terminal (N) and the ground copper
bar. Screw torques for tightening the inverter breaker terminals,
inverter connect terminal and ground terminals are shown in the
following table.
3. Finally, fasten the plastic cover clockwise. The wiring method is
shown below:
3.1.2.1 AC power cable connection:
1. Twist the plastic cover printed with "COM" on the machine
counterclockwise; remove the waterproof plug, and reserve the
hole.
2. Route the two communication cables (A/B) (the twisted pair
cables are recommended) and the two BOX EN cables (EN+/EN-)
through the hole, connect them to the CN8 terminals on the control
board. Connect the other end of the cables to the COM terminals of
the inverter, and tighten the screws. The following table lists the
corresponding terminal pins. The wiring method is shown as follows:
3.1.2.2 Communication cable connection:
COM Port
XH Inverter
COM
SYN 100-XH-30
COM
Control Board
RS485 A
PIN 23
PIN 3
CN8
RS485 B
PIN 24
PIN 4
BOX.EN+
PIN 21
PIN 5
BOX.EN-
PIN 22
PIN 6
Screw torque
Inverter breaker terminals
17.5 in*lbs
Inverter connect terminal
17.5 in*lbs
Ground terminal
13 in*lbs
Screw torque
Load breaker terminal
17.5 in*lbs
Load connect terminal
17.5 in*lbs
Ground terminal
13 in*lbs
Load
L1L2 L3 N
N
L3L2L1PE
PE
Backup Loads
Connecting to the AC Loads
SYN 100-XH-30
Connecting the AC cables to the XH Inverter
Connecting the communication cables to the XH Inverter
COM
SYN 100-XH-30
L1
GR ID
BY PASS
IN VE RTE R
LO AD
L2 L3 N L 1 L2 L 3 L1 L 2 L3 N L1 L2 L 3 N
L1
GR ID
BY PASS
IN VE RTE R
LO AD
L2 L3 N L 1 L2 L 3 L1 L 2 L3 N L1 L2 L 3 N
BOX.E N-
BOX.E N+
B
A
CN8
Inverter
1
6
COM
L1L2 L3 N
Inverter
PE
ON
ON
ON
ONON
OFF
OFF
OFF
OFFOFF
N
L1 L 2
PE
Inverter
SYN 100-XH-30
L1
GR ID
BY PASS
IN VE RTE R
LO AD
L2 L3 N L 1 L2 L 3 L1 L 2 L3 N L1 L2 L 3 N
L3