Hager JKM02 Bruksanvisning

Läs gratis den bruksanvisning för Hager JKM02 (1 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 7 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 4 recensioner. Har du en fråga om Hager JKM02 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/1
5.60 General Catalogue • Modular Devices • Technical
Dimension Diagrams (mm)
Please allow space above and below the meter for cable connections.
6770
90
95
45
2
Home Page
(Unit will default to this
page after 60 seconds)
3 Phase Average L-N
Active Energy
Load 1 and 2
x 4x 3
Voltage
Line to Line Per Phase
3 Phase Average L-N
Reactive Energy
Load 1 and 2
Power Factor 3 Phase Average
Frequency
Load 1
Voltage
Line to Neutral Per Phase
x 1
3 Phase Average L-N Voltage
Active Energy kWh - Load 1
Active Energy kWh - Load 2
Active Power
Three Phases
Load 1
Reactive Power
Three Phases
Load 1
Apparent Power
Three Phases
Load 1
Total Active Power
Three Phases
Load 1 and 2
As above - Load 2
As above - Load 2
As above - Load 2
As above - Load 2
Total Reactive Power
Three Phases
Load 1 and 2
Total Apparent Power
Three Phases
Load 1 and 2
Active Power
Max. Demand
Load 1 and 2
Current
Per Phase - Load 2
Current
Per Phase - Load 1
x 2
Active Power
Max. Demand
Load 1 and 2
JKM0 2
PAGE
1 2 3 4 5 6 7
Cu rrent
In pu t 1
1
Cu rrent
In pu t 2
1
PRG
INT
8 159 10 11 12 13 14 16 17 1 8 19
L-NkW h
Avg
V
1
2
Button Selection
Split Load, Dual CT input meter
4 Module DIN rail mounting
Single phase or 3 phase (4 wire) network
balanced or unbalanced load
Built-in dual energy pulse output, one
for each load and RS485 MODBUS
communication
Wide range of measured parameters
(see table below)
High quality backlit LCD display
330mV current transformer input
Active energy class 1 (EN62053-21)
Reactive energy class 2 (EN62053-23)
THD upto 31st harmonic for voltage and
current
3-phase: 140…460Vac measured voltage
Single phase: 80…265Vac measured
voltage
Self supplied auxiliary
Programmable CT ratio 5…10,000A per
load
Programmable VT ratio
Frequency 45/65Hz
Selectable CT phase correction allows
reversal of L1 and L3
Weight 200g
Function Diagram
Multifunction Power Meter - Dual CT Connection
Panel Mounting - LCD Display - JKM02

Produktspecifikationer

Varumärke: Hager
Kategori: Inte kategoriserad
Modell: JKM02

Behöver du hjälp?

Om du behöver hjälp med Hager JKM02 ställ en fråga nedan och andra användare kommer att svara dig