Läs gratis den bruksanvisning för Hager NCN101A (5 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 8 personer och har ett genomsnittsbetyg på 4.0 stjärnor baserat på 8 recensioner. Har du en fråga om Hager NCN101A eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/5
4.44 General Catalogue • Protection Devices • Technical
Transformer/Motor Protection
Transformer Protection
Tables 19 & 20 show the recommended MCB’s for the protection of
single phase (230V) and three phase (400V) transformers.
Single Phase 230V
Recommended MCB
Transformer
Rating (VA)
Primary
Current
NBN NCN NDN
500.22 -16
1000.43 -26
2000.87 -36
2501.09 646
3001.30 1046
4001.74 1066
5002.1716 10 6
7503.2616 10 6
10004.3525 16 10
250010.8763 40 20
500021.74 -6332
750032.60 --50
1000043.48 --63
Three Phase 400V
Recommended MCB
Transformer
Rating (VA)
Primary
Current
NBN NCN NDN
5000.72 -36
7501.08 646
10001.44 1066
20002.8816 10 6
30004.3325 16 10
40005.7732 20 10
50007.2140 25 16
750010.8263 32 20
1000014.43 -5025
1500021.64 -6332
2000028.86 --50
2500036.07 --63
Motor Circuit Protection
Tables 28,29,30 and 31 give general recommendations for the
selection of circuit breakers and HRC fuses for the protection of
motor power circuits and are based on the assumptions shown in
Table 28 for a cage motor running at approximately 1400 Rev/Min.
Motor RatingDOL Starting
Conditions
Assisted Start Conditions
Up to 0.75kW5 x FLC for 6 secs2.5 x FLC for 15 secs
1.1 to 7.5kW6 x FLC for 10 secs2.5 x FLC for 15 secs
11 to 75kW7 x FLC for 10 secs2.5 x FLC for 15 secs
90 to 160kW6 x FLC for 15 secs2.5 x FLC for 20 secs
1 Phase 230V DOL Starting
Recommended Circuit Breaker
kWhpFLC A(A)
NBN
(A)
NCN
(A)
NDN
Fuse
(A)
0.180.252.816 10 10 10
0.250.333.216 10 10 16
0.370.53.516 10 10 16
0.550.754.820 16 16 16
0.751.06.225 20 20 20
1.1 1.5 8.7 40252525
1.52.011.850 32 32 32
2.23.017.5 -505040
3.04.020 -63 63 50
3.755.024- - - 63
5.57.536- - - 80
7.51047- - - 100
3 Phase 400V Assisted Starting Star-Delta
Recommended Circuit Breaker
kWhpFLC A(A) NCN(A) NDNHRC Fuse (A)
346.3 161016
45.5 8.2 201016
5.57.511.2 321620
7.510 14.440 25 25
11 15 21 50 32 32
15 20 27 -40 35
18.525 32 -50 40
22 30 38 -63 50
30 40 51 --63
37 50 63 --80
45 60 76 --80
55 75 91 --100
75100 124 --160
90125 154 --200
110 150 183 --200
132 175 219 --250
150 200 240 --315
160 220 257 --315