Hager TYA664BN Bruksanvisning
                    Hager
                    
                    Inte kategoriserad
                    
                    TYA664BN
                
                                
    Läs gratis den bruksanvisning för Hager TYA664BN (2 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 8 personer och har ett genomsnittsbetyg på 4.7 stjärnor baserat på 4.5 recensioner. Har du en fråga om Hager TYA664BN eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
                        Sida 1/2
                    
                    
                    
1 6LE002798A
6LE002798A
z
TYA664BN
4 channel dimmer with output 
combination 600W
Bn?.:  
M
`
Safety instructions
Electrical equipment may only be installed and 
assembled by a qualified electrician in accor-
dance with the relevant installation standards, 
guidelines, regulations, directives, safety and 
accident prevention regulations of the country.
Failure to comply with these instructions may 
result in damage to the device, fire or other 
hazards.
Hazard due to electric shock. Disconnect be-
fore working on the device or replacing lumi-
naires. Take into account all circuit breakers 
that supply dangerous voltages to the device.
Hazard due to electric shock. The device is not 
suited for safe disconnection of the mains sup-
ply. Even when the device is switched o, the 
load is not galvanically separated from the 
mains supply.
Do not connect any LED or compact fluores-
cent lamps that are not expressly suitable for 
dimming. The device can be damaged.
Do not connect lights with integrated dimmer. 
Do not connect capacitive load and inductive 
loads together on the same output.
The permissible maximum load per device 
must not be exceeded.
Making output combination using dierent 
phases will definitively damage the product. 
Output combinations cannot be done if the 
phases used on L1, L2, L3 and L4 are dierent.
These instructions are an integral component 
of the product and must be retained by the end 
user.
Design and layout of the device
(1)
(2)
(3) (4)
(5) (6)
(7)
(9)
(8)
(10)
Figure 1 : Device overview
(1)  Slide switch auto/min/max/  (min/max 
slide switch settings are unavailable by default 
on TYA664BN., it must be activated in ETS)
(2)  Illuminated button for dimming mode 
(3)  KNX bus connection terminal
(4)  Connection of load
(5)  Labelling field with cover
(6)  Illuminated programming button
(7)  Operation button for manual operation with 
status LED
(8)  Control LED overheating protection
(9)  Control LED short-circuit and overload pro-
tection per output
(10)   Mains connection
Function
System information
This device is a product of the KNX system and 
corresponds to the KNX guidelines. Detailed 
specialised knowledge obtained from KNX training 
courses  
is required for understanding. The planning, instal-
lation and commissioning of the device is carried 
out with the help of KNX-certified software. 
system link commissioning:
The function of the device is software-dependent. 
The software is to be taken from the product 
database. You can find the latest version of the 
product database, technical descriptions as well 
as conversion and additional support programmes 
on our website.
Functional description
The device has four load outputs that can be con-
nected to dierent phases. It works with automatic 
load detection depending on the connected load 
in the phase cut-on or phase cut-o and enables 
switching and dimming via the KNX bus of:
 -Incandescent lamps and halogen lamps
 -Low-voltage halogen lamps with conventional 
or electronic transformer 
 -dimmable LED and energy-saving lamps 
Additionally, the device has a learn function for 
more ecient control of energy-saving lamps and 
230 V LED lamps. 
Output combination
The 4 channels can be combined together with 
dierent allowed combinations in order to dim 
more powerful loads.
Before an ETS download the device will automat-
ically run a test to recognize if the cabling made 
matches with one of the authorized combinations, 
after an ETS download the device will automat-
ically run a test to recognize if the cabling made 
matches with the “output combination” parameter 
filled in ETS.
Authorized combinations:
(1)-(2)-(3)-(4)
(1+2)-(3)-(4)
(1+2+3)-(4)
(1+2+3+4)
(1)-(2)-(3+4)
(1+2)-(3+4)
If another not-allowed output combination is 
detected the product will indicate with the red leds 
on the buttons which output group is not allowed/ 
in default.
Correct use
 -Dimming of electric loads   230 Vv
 -Installation on DIN rail according to DIN EN 
60715 in distribution box
Product characteristics
 -Status display of the output on the device
 -Manual activation of the output on the device 
possible, building site operation
 -Automatic load detection
 -Setting the minimum and maximum dimming 
value 
 -Timer functions
 -Scene function
 -Forced position by higher-level controller
 -Combination of the outputs to dim more power
Short-circuit and overload protection
Short-circuit and overload are signalled via the 
control LED (9). The load is throttled (see Trouble-
shooting).
Overheating protection
Overheating of the device is signalled by a perma-
nent light of the control LED (8). The connected 
load is throttled (see Troubleshooting).
Operation
Manual operation
Bus and mains power supply are present.
 zPush switch (1) to position  .
Manual operation is switched on, the output can 
be controlled using the operation button (7).
  During manual operation, the controller is deac-
tivated via the KNX bus.
  system link commissioning:  
Depending on the programming, the manual 
operation is activated permanently or for a time 
period configured via the application software. 
If the manual operation is disabled via the ap-
plication software, no activation takes place.
Or:
 zMove switch (1) to position auto.
The manual operation is switched o. Oper-
ation takes place solely via the KNX bus. The 
output adopts the brightness predefined by the 
bus controller.
Operating output in manual operation
Operation takes place by a short or long press on 
the operation button (7) (table 1). 
  If the integrated LED flashes when pressing the 
operation button, no load is connected.
P
P
P
Status  Performance when pressing 
the button 
Load is swit-
ched o. 
Status LED of 
the button (7) 
is o.
Short press on button: 
Switch ON the connected load. 
LED lights up.
Long press on button: 
Dim up to maximum bright-
ness. Status LED of button (7) 
lights up.
Load is swit-
ched on.
Status LED of 
the button (7) 
lights up.
Short press on button: 
Switch OFF the connected 
load. Status LED of button (7) 
goes out.
Long press on button: 
Changes the current brightness. 
Dimming takes place in the op-
posite direction of the last dim-
ming operation until maximum 
or minimum brightness.
Table 1 : Manual operation
Information for electricians
Installation and electrical connection
DANGER!
Touching live parts can result in an electric 
shock!
An electric shock can be lethal!
Disconnect  the  connecting  cables  before 
working  on  the  device  and  cover  all  live 
parts in the area!
CAUTION!
Impermissible  heating  if  the  load  of  the 
device is too high!
The device  and  the  connected  cables may 
get damaged in the connection area!
Do  not  exceed  the  maximum  current 
carrying capacity!
 Observe temperature range. Provide sucient 
cooling.
 zMount device onto DIN rail in accordance with 
DIN EN 60715.
Connect device
Fig 2 : Installation/removal with  
plug-in terminals 
P
(11)
L
N
Figure 3 : Device connection 1-phase
L1
L2
N
(11)
Figure 4 : Device connection multi-phase
(11)  Load
 zConnect bus cable via connecting terminal (3).
 zConnect load (11) on the lower terminal strip (4) 
of the device. 
  To ensure proper functioning of the device the 
terminal blocks N1 and L1 have to be wired 
with mains power. If mains is missing on L1 the 
product will be totally blocked.
L
N
Figure 5 : Output combination (1+2+3+4)
P
L
N
Figure 6 : Output combination (1+2)-(3+4)
Start-up
system link: Loading physical address and 
application software
The switch for manual operation (1) is in position 
auto.
 zSwitch on mains voltage.
 zSwitch on bus voltage 
 zPress programming button (5).
The button lights up.
  If the button does not light up, no bus voltage 
is present.
 zLoad the physical address into the device. 
Status LED of the button goes out.
 zLoad application software. 
 zNote down the physical address on the label-
ling field (5).
Start up the device.
 zSwitch on mains supply.
Functional test
The functionality of the outputs is displayed via the 
status LED of the operation button (7).
LED status  Meaning of the signal
LED lights up  
permanently
Load is activated
LED flashes No load connected
Setting minimum and maximum dimming value 
on the device
The device is ready for operation.
 zSetting brightness value
  The brightness value can be set by manual 
operation on the device or by the programmed 
dimming button of an operating unit.
 zSet switch (1) to max. in order to apply the set 
brightness as maximum dimming value.
Or:
 zSet switch (1) to min. in order to apply the set 
brightness as minimum dimming value.
 zKeep the operation button (7) pressed for more 
than 3 s.
The status LED flashes twice. The set bright-
ness value is saved.
  If the minimum or maximum dimming value are 
outside the setting range, the status LED (7) 
flashes permanently after the save operation.
Setting dimming mode on the device
In the factory setting, the device performs an 
automatic load detection for ohmic, inductive and 
capacitive loads and selects the suitable dimming 
performance. If the load type is known, this can 
P
P
P
be specified on the device without performing an 
automatic load detection.
The device is ready for operation.
 zKeep the dimming mode button (2) pressed until 
the status LED of the operation button (7) flashes. 
 zSelect the channel for which you wish to 
change the dimmer mode by pressing on 
button (7).
 zBriefly press the dimming mode button (2) repeat-
edly until the coloured lighting of the button (2) 
displays the desired operating mode (Table 2).
 zKeep the dimming mode button (2) pressed un-
til the lighting of the button (2) flashes quickly.
While the button is flashing quickly, the 
selected operating mode is set. After that, the 
operating mode is displayed for approx. 3 s 
before the button goes out.
  If the setting is not confirmed by holding down 
the button, the device will revert to its previous 
dimming mode after 2 minutes.
  If the operating mode selected is not suitable 
for the connected load, the dimming channel 
will reset to "factory setting" automatically.
Lighting  
button (2)
Dimming mode
yellow Energy-saving lamps1)
purple Capacitive load
blue Inductive load
red  LED load
green taught-in load1)
white automatic load setting (factory 
setting)
1)  The load for the selected dimming mode is only taught 
in for approx. 30 s. This can lead to temporary impair-
ment of the lighting. 
Table 2
Displaying dimming mode
 zBriefly press the dimming mode button (2).
The coloured lighting of the button will display the 
current operating mode for approx. 3 s (Table 2). 
Teach in the load of an operating unit via the 
button
When teaching in the connected load, the dim-
ming performance for compact fluorescent lamps 
and LED lamps is optimised.
The device is ready for operation. The dimming 
button of an operating unit has been programmed 
with the taught-in output.
 zPress the dimming button 5 times briefly, then 
keep the button pressed until the load switches 
o.
  The short press is independent of the config-
ured operating performance on the operating 
unit ( 5 x On, 5 x O or 5 x On/O)
 zPress button once briefly.
The teach-in procedure lasts approx. 30 s. To 
optimise the dimming performance, a dimming 
operation is performed. After teaching in, the 
connected load lights up at maximum bright-
ness and flashes once. The teach-in process is 
complete.
   Depending on the connected load, the mini-
mum brightness may change due to the teach-
in process.
Resetting taught-in loads in the device 
The device can be reset to automatic load detec-
tion, e.g. after replacing luminaires. 
  Automatic load detection is particularly suitable 
for loads that can be dimmed clearly in the phase 
cut-on or phase cut-o ("conventional loads").
P
P
P
P
P
The device is ready for operation. The dimming 
button of an operating unit has been programmed 
with the taught-in output.
 zPress the dimming button 5 times briefly, then 
keep the button pressed until the load switches 
o.
  The short press is independent of the config-
ured operating performance on the operating 
unit ( 5 x On, 5 x O or 5 x On/O).
  If the dimming button is no longer pressed 
within the next 10 seconds, the learned dim-
ming principle is retained.
 zPress button 2 times briefly.
The load flashes twice. The automatic load 
detection is enabled again.
Appendix
Technical data
supply voltage   230 V , + 10%/-15 %  v
via mains  240 V , +/-6% v
Supply voltage KNX/EIB 21 ... 32 V    s
  SELV
Current consumption KNX/EIB  2.4 mA
Consumption without load  780 mW
Fan-in  1
Product consumption  1W max
Product power dissipation  2,4W max
Operating altitude  2000 m. max
Pollution degree  2
Surge voltage  4 kV
Degree of protection of housing  IP 20
Degree of protection of housing under front panel
  IP30
IK (impact protection)  04
Overvoltage class  III
Dimension   10 modules, 10 x 17.5 mm
Connection capacity  0.75 mm²…2.5 mm²
Operating temperature  -5 …+ 45°C
Storage temperature  - 20 …+ 70°C
Upstream circuit breaker   10 A up to 2300W
  16 A between 2300W and 2400W
Load that can be connected per output
Output Combination - 230 V~ incandescent lamps, 
halogen lamps
- 12 V~ / 24 V~ halogen lamps 
with conventional transformer
- 12 V~ / 24 V~ halogen lamps 
with electronic transformer
- 12 V~ / 24 V~ energy-saving 
lamps (CFL)/LED lamps with 
dimmable driver
Min Max
1 output independent 
channel
5W
(1 driver)
600W
(10 drivers)
2 outputs combined in 
1 channel
300W
(5 drivers)
1200W
(16 drivers)
3 outputs combined in 
1 channel
600W
(8 drivers)
1800W
(22 drivers)
4 outputs combined in 
1 channel
900W
(11 drivers)
2400W
(28 drivers)
Output Combination - Dimmable 230V~ energy-sav-
ing lamps (CFL)/ LED lamps
Min Max
1 output independent 
channel
5W
(1 lamp)
120W
(10 lamps)
2 outputs combined in 
1 channel
40W
(5 lamps)
240W
(16 lamps)
3 outputs combined in 
1 channel
80W
(8 lamps)
360W
(22 lamps)
4 outputs combined in 
1 channel
120W
(11 lamps)
480W
(28 lamps)
*Driver limitations need to be respected only for energy 
saving lamps used with drivers.
P
P
  Conventional or electronic transformers should 
not be operated with less than 75% of their 
nominal load.
Troubleshooting
Manual operation not possible
Cause 1 : Switch (1) not moved to  .
Move switch to  .
Cause 2 : Manual operation has not been enabled 
(system link)
Enable manual operation via application soft-
ware.
Connected loads do not light up
Cause 1 : Electronic short-circuit and overload 
protection has triggered, control LED (9) lights up/
flashes.
Reduce connected load, check wiring and 
repair if necessary.
Cause 2 : Overheating protection has triggered, 
control LED (8) lights up. 
Reduce connected load, provide sucient 
cooling, increase distance to adjacent devices.
Cause 3 : Phase L1 is missing, phase L1 presence 
is necessary for any output to work
Cause 4 : The phase (L1, L2, L3, L4) of the respec-
tive output (Output 1, 2, 3 or 4) is missing
Cause 5 : Before an ETS download, the cabled 
output combination doesn’t correspond to an 
authorized output combination
Cause 6 : After an ETS download, the output 
combination doesn’t correspond to the output 
combination parameter set in ETS
Bus operation is not possible
Cause 1 : Bus voltage is not present.
Check bus connection terminals for correct 
polarity.
Check bus voltage by briefly pressing the 
programming button (6), red LED lights up 
if bus voltage is present. If mains voltage is 
present without bus voltage, the red LED is lit 
up permanently.
Cause 2 : Manual operation is active. Switch (1) is 
in position  .
Move switch (1) to position  .auto
P
Correct Disposal of This product    
(Waste Electrical & Electronic Equipment).
(Applicable in the European Union and  
other European countries with separate    
collection systems).
This marking shown on the product or its literature 
indicates that it should not be disposed with other 
household waste at the end of its working life. 
To prevent possible harm to the environment or 
human health from uncontrolled waste disposal,
please separate this from other types of waste and 
recycle it responsibly to promote the sustainable 
reuse of material resources.
Household users should contact either the retailer 
where they purchased this product, or their local 
government office, for details of where and how 
they can take this item for environmentally safe 
recycling.
Business users should contact their supplier and 
check the terms and conditions of the purchase 
contract. This product should not be mixed with 
other commercial waste for disposal.
Usable in all Europe  and in Switzerland M
L3
Produktspecifikationer
| Varumärke: | Hager | 
| Kategori: | Inte kategoriserad | 
| Modell: | TYA664BN | 
Behöver du hjälp?
Om du behöver hjälp med Hager TYA664BN ställ en fråga nedan och andra användare kommer att svara dig
Inte kategoriserad Hager Manualer
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         2 April 2025
                        
                    
                                                            
                        
                         1 April 2025
                        
                    
                                                            Inte kategoriserad Manualer
- AquaMAX
- PcDuino
- JennAir
- Omnilux
- INOGENI
- Heller
- Lively
- Lahti Pro
- E-Power
- Cybex
- Giga Copper
- Nitek
- Vonroc
- Coolaroo
- W'eau
Nyaste Inte kategoriserad Manualer
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025
                        
                    
                                                            
                        
                         9 April 2025