Operating instructions
Electronic pressure sensor
PK57xx
80229749 / 00 03 / 2020
Set
UK
2
1 1 Preliminary note
1.1 Symbols used
Instruction
> Reaction, result
[…] Designation of keys, buttons or indications
Cross-reference
Important note
Non-compliance may result in malfunction or interference
Information
Supplementary note
2 Safety instructions
The device described is a subcomponent for integration into a system.
- The manufacturer is responsible for the safety of the system.
- The system manufacturer undertakes to perform a risk assessment and to
create a documentation in accordance with legal and normative requirements
to be provided to the operator and user of the system. This documentation
must contain all necessary information and safety instructions for the operator,
the user and, if applicable, for any service personnel authorised by the manuf-
acturer of the system.
Read this document before setting up the product and keep it during the entire
service life.
The product must be suitable for the corresponding applications and environ-
mental conditions without any restrictions.
Contents
1 1 Preliminary note 2 ................................................................................................
1.1 Symbols used 2 ................................................................................................
2 Safety instructions 2 ...............................................................................................
3 Functions and features 3 ........................................................................................
4 Installation............................................................................................................4
5 Electrical connection 4 ............................................................................................
6 Setting / operation................................................................................................5
3
UK
Only use the product for its intended purpose (→ Functions and features).
Only use the product for permissible media (→ Technical data).
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
Installation, electrical connection, set-up, programming, configuration, operati-
on and maintenance of the product must be carried out by personnel qualified
and authorised for the respective activity.
Protect units and cables against damage.
3 Functions and features
The pressure sensor detects the system pressure and switches the output
OUT (pin 4):
In case of increasing pressure, OUT closes when the set Set value is reached.
In case of falling pressure OUT opens when the Set value less the fixed hyste-
resis is reached.
The hysteresis is fixed to 2 % of the final value of the measuring range.
Application
Type of pressure: relative pressure
Order
number Measuring range
Pressure resistance
(max. permissible
pressure)
Bursting pressure
bar MPa bar MPa bar MPa
PK5722 0...100 0...10 200 20 1000 100
PK5723 0...25 0...2,5 60 6 500 50
Avoid static and dynamic overpressure exceeding the specified max. per-
missible pressure by taking appropriate measures!
The indicated bursting pressure must not be exceeded!
Even if the bursting pressure is exceeded only for a short time, the unit may
be destroyed! ATTENTION: risk of injury!!
If the cable length exceeds 30 m or if used outside buildings, there is a risk
of overvoltage pulses from external sources. We recommend to use the
unit in protected operating environments and to limit overvoltage pulses to
max. 500 V.