    Läs gratis den bruksanvisning för Qubino ZMNHXD8 (1 sidor) i kategorin Mätutrustning. Guiden har ansetts hjälpsam av 19 personer och har ett genomsnittsbetyg på 4.5 stjärnor baserat på 10 recensioner. Har du en fråga om Qubino ZMNHXD8 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
                        Sida 1/1
                    
                    
                    
3-Phase Smart Meter 
ORDERING CODE 
Z-WAVE FREQUENCY 
ZMNHXD1 
868,4 MHz 
ZMNHXD2 
921,4 MHz 
ZMNHXD3 
908,4 MHz 
ZMNHXD4 
869,0 MHz 
ZMNHX  D5
916,0 MHz 
ZMNHXD8 
865,2 MHz 
This  3-Phase  Smart  Meter  is  used  for  energy 
measurements  in  three-phase  electrical  power  network 
and  can  be  used  in  residential,  industrial  and  utility 
applications.  Meter  measure  energy  directly  in  4-wire 
networks  according  to  the  principle  of  fast  sampling  of 
voltage  and  current  signals.  A  built-in  microprocessor 
calculates  energy,  power  and  power  factor  from  the 
measured signals.  
The  module  can  be  controlled  through  Z-wave  network 
and  it  acts  as  repeater  in  order  to  improve  range  and 
stability of Z-wave network. 
It is designed to be mounted on DIN rail. 
Installation  
  To  prevent  electrical  shock  and/or  equipment 
damage,  disconnect  electrical  power:  remove  main 
fuse  or  put  on  OFF  position  a  main  disconnection 
switch (or circuit breaker if it is compliant to standard 
IEC947-2), before installation or any servicing.  
  Make  sure,  that  no  voltage  is  present  in  the 
installation.  
  Prevent  the  disconnecting  device  from  being 
switched on accidentally. 
  Connect the module according to electrical diagram.  
  Locate  the  antenna far  from metal  elements  (as  far 
as possible).  
Danger of electrocution!  
  Module  installation  requires  a  great  degree  of  skill 
and  may  be  performed  only  by  a  qualied  and 
licensed electrician. 
  Even  when  the module is  turned o,  voltage  may be 
present on its terminals. 
 Note! 
Do  not  connect  the  module  to  loads  exceeding 
recommended  values.  Connect  the  module  only  in 
accordance to the below diagrams. Improper connections 
may be dangerous. 
Electrical  installation  must  be  protected  by  over  current 
protection  fuse      must  be with  rated  current  up  to  80A,it
used according  to wiring diagram  to  achieve appropriate 
overload protection of the module. 
Package contents 
 3-Phase Smart Meter 
Electrical diagram 230VAC 
Notes for the diagram: 
L1 I,  L2
I, L3I
Live input 
Ni 
Neutral input 
L1 O, L2
O, L3O 
Live output 
No 
Neutral output 
16 
Input for IR external relay/Ext. relay 
15 
Output for External relay (max. 3W) 
S 
Service button (used to add or remove 
module from the Z-Wave network). 
LED1 
Green  -  Power  on  (solid)  /  no  ID 
(blinking  slow  1s)  /  Inc./Exc.  mode 
(blinking fast 0,5s)    
LED2 
Yellow  on    output  on  (any)  /  Yellow –
o    outputs  o  (both)  /  Blinking  IR –
communication error 
IR 
Output for IR external relay (BICOM) 
500imp/kWh 
Red  -  lse  rate  (On    no  load Pu –
indication) 
Measurements 
Voltage 
V 
Current 
I 
Power   Active– 
W 
Power   Active total Import– 
kWh 
Power   Active total Export –
kWh 
Energy   Reactive– 
var 
Energy   Reactive total– 
kvarh 
Energy   Apparent total– 
kVAh 
Power Factor 
PF 
External relays  
It is possible to connect two external relay to Smart Meter 
module.  One  controlled  by  built-in  optical  (IR) 
communication  port  on  the  side,  second  controlled  by 
output on terminal 1  5.
Module  Inclusion  (Adding  to  Z-wave 
network) 
 Connect module to power supply  
 enable add/remove mode on main controller 
 auto-inclusion  (works  for  about  2  minutes  after 
connected to power supply) or 
 press service button   between 2 and 6 seconds S
NOTE:  For  auto-inclusion  procedure,  rst  set  main 
controller into inclusion mode and then connect module to 
power supply. 
Module  Exclusion/Reset  (Removing 
from Z-Wave network) 
 Connect module to power supply  
 enable  add/remove  mode  on  main  controller and 
press S button between 2 and 6 seconds 
 press service button   between  and 20 seconds . S6 
The reset is only possible rst minute after the 
power on  
By this function all parameters    of the module are set to 
default values and own ID is deleted. 
If service button S is pressed more than 2 and less than 6 
seconds module is excluded, but conguration  
parameters   are not set to default values. 
Technical Specications  
Main terminals  1(L I, L2I, L3I, NO, L1O, L2O, L3O, NO) 
Contacts capacity:  2.5 ... 16 (25) mm
2 
Connection screws:   M5
Max torque:  3.5 Nm (PZ2) 
Optional terminals (DI, DO) 
Contact capacity:  1 ... 2.5 mm
2 
Screws:   M3
Max torque:  1.2   Nm
Measuring input: 
Type (connection):  three phase ( ) 4u
Basic current (Ib   5 A ):
Maximum current (Imax):   A 80
Minimum current (Imin):  0.25 A 
Starting current:  20 mA 
Reference voltage (Un):  /400V 3X230V
Power consumption at Un:  8 VA < 
Nominal frequency (fn):  50 and 60 Hz 
Accuracy: 
Active energy and power:   
Standard   62053- :  class 1 EN 21
Standard EN 50470-   class B 3:
Reactive energy:   
Standard EN 62053-23:  class 2 
LED: 
Colour:  red 
Pulse rate:  500 imp/kWh 
Led on:  no load indication 
Optical communication: 
Type:   IR  -  used  to  control 
BICOM432- -  40 IR
Input (  16):
Rated voltage:   230 V (± 20%)
Input resistance:  450 kOhm 
LCD: 
Display 7+1 digit (100Wh resolution) 
Safety: 
Indoor Meter:  yes 
Degree of pollution:  2 
Protection class:   II
AC voltage test:  4 kV 
Installation Category:  300 Vrms cat. III 
Standard:  EN 50470 
Ambient conditions and EMC: 
According standards for indoor active energy Meters. 
Temperature  and  climatic  condition  according  to 
EN  -  62052 11
Ambient conditions and Safety: 
According standards for indoor active energy Meters. 
Temperature  and  climatic  condition  according  to 
EN  -  62052 11
Dust/water protection:  IP20 
Operating temperature:  -10 ...   55°C
Storage temperature:  -  40 ... 70°C
Enclosure material:  self extinguish 
  complying UL94 V 
Indoor Meter:  yes 
Degree of pollution:  2 
AC voltage test:  4 kV 
Standard:  EN 50470 
Distance:   up  to  30  m  indoors 
(depending  on  building 
materials) 
Weight (with packaging):   (  220g 240g)
Frequency range:                 868.4 MHz* -Wave           , Z
Installation                        Din rail 35mm (EN 60715)           
Dimensions (W x H x D):    53,6   x 65           x 84 mm
Package dimensions  
(W x H x D):                                70mm       56 x 86 x 
Colour  RAL 7035 
* Depends on ordering code 
EC Directives conformity: 
EC Directive on Meas. Instruments 2004/22/EC 
EC Directive on EMC 2004/108/EC 
EC Directive on Low Voltage 2006/95/EC 
EC Directive WEEE 2002/96/EC 
Dimensional drawings: 
Important disclaimer 
Z-Wave wireless communication is inherently not always 
100% reliable, and as such, this product should not be 
used in situations in which life and/or valuables are solely 
dependent on its function. 
Warning! 
Do  not  dispose  of  electrical  appliances  as  unsorted 
municipal waste, use separate collection facilities. Contact 
your  local  government  for  information  regarding  the 
collection  systems  available.  If  electrical  appliances  are 
disposed  of in  landlls  or  dumps, hazardous  substances 
can leak into the groundwater and get into the food chain, 
damaging your health and well-being. When replacing old 
appliances with new once, the retailer is legally obligated 
to  take  back  your  old  appliance  for  disposal  at  least  for 
free of charge. 
This user manual  is subject  to  change and  improvement 
without notice. 
Goap d.o.o. Nova Gorica 
Ulica Klementa Juga 007 
5250 Solkan 
Slovenia 
E-mail:    info@qubino.com
Tel:       +386 5 335 95 00 
Web:     www.qubino.com 
Date: 15. .2017 04
Document: Qubino_3-Phase-Smart Meter 
PLUS_v1  .0_eng
For more informatio please look at extended manual. 
Produktspecifikationer
| Varumärke: | Qubino | 
| Kategori: | Mätutrustning | 
| Modell: | ZMNHXD8 | 
Behöver du hjälp?
Om du behöver hjälp med Qubino ZMNHXD8 ställ en fråga nedan och andra användare kommer att svara dig
Mätutrustning Qubino Manualer
                        
                         16 September 2024
                        
                    
                                                            
                        
                         16 September 2024
                        
                    
                                                            
                        
                         16 September 2024
                        
                    
                                                            
                        
                         16 September 2024
                        
                    
                                                            
                        
                         16 September 2024
                        
                    
                                                            Mätutrustning Manualer
- Oregon Scientific
- Nedis
- Trumeter
- Microlife
- Cablexpert
- Corentium
- TDE Instruments
- GMW
- Arya
- Finder
- Weidmüller
- Cocraft
- SRS
- Megger
- Eastron
Nyaste Mätutrustning Manualer
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025