Läs gratis den bruksanvisning för System Sensor F-A3384-000 (1 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 11 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 6 recensioner. Har du en fråga om System Sensor F-A3384-000 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/1

F-A3384-000 Air Filter Assembly
INSTALLATION AND MAINTENANCE INSTRUCTIONS
GENERAL DESCRIPTION
The F-A3384-000 replacement air filter for the FAAST™ 8100 series aspiration
detectors comes fully assembled and ready to use. It is a 30 micron filter de-
signed specifically for use with the FAAST system.
FILTER ASSEMBLY REPLACEMENT
The filter is located behind the Display Door under the User Interface Card, as
shown in Figure 1.
FIGURE 1. FRONT VIEW OF DETECTOR WITH DISPLAY DOOR OPEN AND
USER INTERFACE CARD IN PLACE:
USER INTERFACE CARD
ASP-82
To replace the filter perform the procedure in Table 1.
TABLE 1. FILTER REPLACEMENT PROCEDURE
STEP ACTION
1 Before performing maintenance, notify the proper authorities that the
system is undergoing maintenance, and will temporarily be out of ser-
vice. Disable the system to prevent unwanted alarms.
2 Turn off the system by removing the 24 Volt power connector from the unit
or by unplugging the converter from its power outlet.
NOTE: If power is not removed, the unit automatically enters Service
Mode when the screws are removed from the filter. This removes
power from the fan and the sensing chamber. In addition, the filter
fault indicator is illuminated and the urgent relay is set.
3 Open the Display Door, as shown in Figure 1, and remove the User
Interface card in front of the filter.
4 Remove the two Philips head screws securing the filter to the unit,
as shown in Figure 2.
5 Replace the entire filter assembly, as shown in Figure 3, with a new
unit by pulling the old filter out and sliding a new filter assembly
back into position.
6 Torque the two Philips head screws to 6in-lb (0.7N-m) or ¼ turn
past “lightly snug”. DO NOT OVER TIGHTEN.
7 Carefully reinstall the User Interface card.
1 I56-3743-003
©2016 System Sensor. 06-10
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
I56-3743-003
FILTER MOUNTING SCREWS
(DO NOT OVERTIGHTEN)
ASP90-01
FIGURE 3. REMOVABLE AIR FILTER ASSEMBLY:
FILTER MOUNTING SCREWS
(DO NOT OVERTIGHTEN)
ASP91-01
FIGURE 2. FILTER MOUNTING SCREWS WITH USER INTERFACE
CARD REMOVED:
Produktspecifikationer
Varumärke: | System Sensor |
Kategori: | Inte kategoriserad |
Modell: | F-A3384-000 |
Behöver du hjälp?
Om du behöver hjälp med System Sensor F-A3384-000 ställ en fråga nedan och andra användare kommer att svara dig
Inte kategoriserad System Sensor Manualer
14 September 2024
14 September 2024
14 September 2024
3 September 2024
2 September 2024
28 Augusti 2024
28 Augusti 2024
28 Augusti 2024
26 Augusti 2024
26 Augusti 2024
Inte kategoriserad Manualer
- Stinger
- Livington
- Create
- 8BitDo
- Sonicsmith
- Goldtouch
- Kernau
- Nicols
- Tork
- Technics
- Williams Sound
- Polk
- Intel
- Metz
- Perfecta
Nyaste Inte kategoriserad Manualer
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025
9 April 2025