TEF ZEOS-C Bruksanvisning

Läs nedan 📖 manual på svenska för TEF ZEOS-C (2 sidor) i kategorin Inte kategoriserad. Denna guide var användbar för 2 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/2
www.tefbrandbeveiliging.nl Tel: 0180 - 554555
FIRE ALARM DETECTOR
TECHNICAL SPECIFICATIONS
INSTALLATION
INSTALLING THE BASE
To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat
against terminals and fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard
electrical junction boxes.
INSTALLING THE HEAD
Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on
base. Fit the detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit .
Test the detectors as described below.
TESTING
All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and
reconnected at the conclusion of testing. After powering the detector, check to see the indicator LED flashing every 5 seconds. If the LED
fails to flash, it indicates the non-functioning of the detector or fault wiring. Re-check the wiring or replace the detector if necessary.
SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When
sufficient smoke has entered, the detector will signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make
sure to clear smoke out of the chamber before resetting in order to keep the detector at its current sensitivity setting.
HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can
be met by some domestic hair dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of
several cms, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. Upon alarm
immediately remove the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to activate within 60
seconds, confirm connections and programming. If necessary replace unit. Note: After testing, check that the system is returned to
normal operation. Notify the appropriate authorities that the testing procedure has been completed and the system is active again.
MAINTENANCE
The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a
low power vacuum cleaner. >> DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR
Detector Head
Detector Base
Alignment Marks
ZEOS-C
ma_zeosc_01_010001_en_180716
MADE IN PORTUGAL - EU
10 V to 30 V DC
Heat: 7 uA / Smoke: 33 uA / Smoke & Heat: 35 uA
24 mA - Alarm LEDs
According to EN54-5 or/and EN54-7
0.5-2.5 mm²
20 seconds max.
White / ABS
95% RH Non-Condensing
0°C to 50°C / -10°C to 85°C
100 mm (D) x 50 mm (H) inc. base / 144 g inc. base
ORION, ORION MINI, ORION EX, ORION-PLUS, QUAD ZMU and ZMU
SUPPLY VOLTAGE
CURRENT - QUIESCENT
CURRENT - DEVICE IN ALARM
SENSITIVITY
CABLE SIZE
RESET/START-UP TIMES
COLOUR / CASE MATERIAL
MAX. HUMIDITY
NORMAL / TRANSIENT OPER. TEMPERATURE
DIMENSIONS / WEIGHT
COMPATIBILITY
ORDER CODE DESCRIPTION
ZEOS-C-S
ZEOS-C-H
ZEOS-C-SH
| CERTIFICATE |
PHOTOELECTRIC SMOKE DETECTOR
RATE OF RISE/FIXED TEMP HEAT DETECTOR
MULTISENSOR SMOKE & HEAT DETECTOR
1328-CPR-0705
1328-CPR-0706
1328-CPR-0704
MECHANICAL SPECIFICATION
www.tefbrandbeveiliging.nl Tel: 0180 - 554555
DETECTOR BASE - CONNECTIONS
NOTE: Positive terminal of remote indicator should be connected to terminal 4.
-Zone IN
PANEL
ZONE
First Detector
Last Detector
-Zone OUT
Remote
Indicator
E.O.L.
+Zone
Remote
Indicator
(*)
Install optional Schottky diode
to comply with BS5839
head removal clause.
*)

Produktspecifikationer

Varumärke: TEF
Kategori: Inte kategoriserad
Modell: ZEOS-C
Färg på produkten: Zwart
Vikt: 910 g
Bredd: 50 mm
Djup: 162 mm
Höjd: 120 mm
Husmaterial: Aluminium
Internationell säkerhetskod (IP): IP30
Strömförbrukning (max): 10.08 W
Certifiering: CE\nEN 61000-6-4 \nEN 61000-6-2\nIEC 60068-2-27\nIEC 60068-2-6
Inspänning: 9 - 48 V
Nätverksstandard: IEEE 802.1D, IEEE 802.1p, IEEE 802.3, IEEE 802.3u, IEEE 802.3x
Säkerhetsalgoritmer som stöds: SNMP
Förvaringstemperatur: -20 - 80 °C
Webbaserad hantering: Ja
VLAN=support: Ja
Auto MDI/MDI-X: Ja
Virtuella LAN-funktioner: Tagged VLAN, Port-based VLAN
Stapelbar: Nee
Växlingskapacitet: - Gbit/s
MAC-ställbar: 2000 entries
10G-stöd: Nee
Dataflödeshantering: Ja
IGMP snokar: Ja
Växlingstyp: Managed
Antal grundläggande switchande RJ-45 Ethernet-portar: 7
Konsolport: RS-232
Typ grundläggande switchande RJ-45 Ethernet-portar: Fast Ethernet (10/100)
Antal modulplatser SPF: 2
Spanning tree protokoll: Ja
Koppar Ethernet-kabelteknik: 10BASE-T, 100BASE-TX
Automatisk förhandling: Ja
Strömförbrukning (typiskt): 8.4 W
Drifttemperatur (TT): 0 - 60 °C
Relativ luftfuktighet i drift (VV): 0 - 95 procent
DIN-skena montering: Ja
Lagra och vidarebefordra: Ja
Fiberoptisk kontakt: FX
Kabelteknik för fiber-ethernet: 100BASE-FX
Terminalblockport: Ja

Behöver du hjälp?

Om du behöver hjälp med TEF ZEOS-C ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad TEF Manualer

TEF

TEF ZEOS-C Bruksanvisning

1 Augusti 2024

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer