Läs gratis den bruksanvisning för Apc NetShelter ACCS1005 (8 sidor) i kategorin Inte kategoriserad. Guiden har ansetts hjälpsam av 29 personer och har ett genomsnittsbetyg på 4.7 stjärnor baserat på 15 recensioner. Har du en fråga om Apc NetShelter ACCS1005 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/8
Rack Air Containment System (ACCS1000–
ACCS1007)—Overview
Introduction
The Rack Air Containment System (RACS) is a mechanical ducting system that attaches to the front
or rear of an enclosure to provide increased cooling capacity. The RACS is a modular system that
works with APC® NetShelter® SX enclosures and InRow® cooling units to provide maximum
cooling predictability, capacity, and efficiency. By attaching the RACS to the rear of the NetShelter
SX, air expelled from IT equipment is forced to pass through the cooling unit, where it is
conditioned. This ensures that warm exhaust air does not enter the air inlets of installed servers.
Redundant configurations allow maximum availability. Optional front containment configurations
reduce noise and provide additional control of air flow. The RACS components can be attached to a
single enclosure or a group of enclosures. The RACS consists of eight components that can be
installed separately or together, depending on your configuration.
ACCS1000—Rear containment for InRow RC or SC cooling units
ACCS1001—Rear containment for NetShelter SX and InRow RP cooling units
ACCS1002—End caps for any rear- or front-containment configuration
ACCS1003—Front containment for InRow RC or SC cooling units
ACCS1004—Front containment for InRow RP cooling units
ACCS1005—Front containment for NetShelter SX enclosures
ACCS1006—Rear containment for NetShelter SX 750-mm enclosures
ACCS1007—Front containment for NetShelter SX 750-mm enclosures
Features of the RACS
Rear containment—Ensures server exhaust air is returned to the InRow cooling unit for
maximum cooling predictability. Prevents recirculation of hot exhaust air.
Front containment—Ensures cold supply air is not captured by neighboring equipment.
Modular design—Compatible with standard NetShelter SX enclosures, providing maximum
system flexibility and scalability.
Redundant configurations—Provide N + 1 or uding additional InRow 2N redundancy by incl
cooling units.
Clear polycarbonate door inserts—Provide required air containment while allowing visibility
to installed IT equipment and a consistent appearance across enclosures.
Lockable doors—Provide enclosure security.
Noise reduction—Containment of both the front and rear of the enclosure reduces the level of
noise generated by the installed equipment.