Emko ESM 1500N Bruksanvisning

Läs gratis den bruksanvisning för Emko ESM 1500N (1 sidor) i kategorin ej kategoriserat. Guiden har ansetts hjälpsam av 2 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 1.5 recensioner. Har du en fråga om Emko ESM 1500N eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/1
ESM-1500N
Digital Temperature Indicator
- Temperature Measurement
- Economical
- Easy to Use
- DIN RAIL Mounting
SPECIFICATIONS
INPUT
NTC : NTC (10k @25°C)W
Thermocouple (TC) : J, K (IEC 584.1) (ITS90)
Thermoresistance (RTD) : 2-wire PT 100, PT 1000 (IEC
751)(ITS90)
Measurement Range : It is in ordering information
Accuracy : ±1% of scale
Cold Junction Compensation : Automatically ±0.1°C/1°C
Sensor Break Protection:Upscale
Sampling Cycle :3 samples per second
DISPLAY
Process Display :
ESM-1500N : 9 mm Red 3 digits LED display
POWER SUPPLY
Supply Voltage :
100-240 V ( -15%, +10% ) 50/60 Hz - 2.2VA
230 V ( ±15% ) 50/60 Hz - 2.2VA V
115 V ( ±15% ) 50/60 Hz - 2.2VAV
24 V ( ±15% ) 50/60 Hz - 2.2VA V
24 V ( -15%, +10% ) 50/60 Hz - 2.2VA W
Z- 2.2W
V
10...30 V
ENVIRONMENTAL RATINGS and PHYSICAL
SPECIFICATIONS
Operating Temperature: -30...80°C
Humidity : 0-90%RH (none condensing)
Protection Class: IP20
Weigth:
ESM-1500N : 150 gr.
Dimension:
ESM-1500N : 90x 35mm, Depth: 61.2mm
Mounting:
ESM-1500N : DIN RAIL Mounting Type
Protection Against Mechanical Impacts : 1Joule (IK06)
Instruction Manual. ENG ESM-1500N 01 V02 04/22
Front Panel
- 3 Digits display
- PTC input or
NTC input or
J Type Thermocouple Input or
K Type Thermocouple Input or
2-wire PT-100 or PT-1000 Input
- Adjustable temperature offset value
Electrical Wiring
If the measured temperature value is lower (bigger) than the real
t value, measured value can be adjusted by emperature temperature
adding offset value.
Offset value is changed by pressing Increment(decrement) button. For
incrementing(decrementing) the offset value increment(decrement)
button must be pressed continuously. After pressing the
Increment(decrement) button for 10 seconds firstly, the temperature
value is incremented (decremented) 0.1 (for BC=09,13,15,19) or
1 (for BC=05, 10, 11, 12, 14, 18) per second during increment
(decrement) button is pressing.
°C
°C
Note: There are 2 hidden buttons under the front panel.
Technician must press to the points on the front panel which
are shown above for using decrement and increment buttons.
Temperature
Indicator
Temperature Calibration
A BC D E FG HI /
/
U
V W Z/
/
0 00 1 0 0
ESM-1500
00
Temp.Sensor which is given with ESM 1500
V
Supply VoltageA
0
None
1
PTC-M6L40.K1.5 (PTC Air probe with 1.5 m silicon cable)
2
PTCS-M6L30.K1.5.1/8”(PTC Liquid probe with 1.5 m silicon cable)
3
NTC-M5L20.K1.5 (NTC Probe, thermoplastic moulded with
1.5 m cable for cooling application)
0
Ordering Information
Hidden Increment
button
Hidden Decrement
button
Temperature
Display
4
NTC-M6L50.K1.5 (NTC Probe, stainless steel housing with
1.5 m cable for cooling application)
9
Customer
Input Type
BC
Scale(°C)
12
05
09
J ,Fe CuNi IEC584.1(ITS90)
PTC (Note-1)
-50°C 150°C
0°C 800°C
-19.9°C 99.9°C
PT 100 , IEC751(ITS90)
10
K ,NiCr Ni IEC584.1(ITS90)
-50°C 400°C
0°C 999°C
11
PT 100 , IEC751(ITS90)
14
-50°C 400°C
PT 1000 , IEC751(ITS90)
13
-19.9°C 99.9°C
PT 1000 , IEC751(ITS90)
15
PTC (Note-1)
-19.9°C 99.9°C
18
-50°C 100°C
NTC (Note-1)
19
-19.9°C 99.9°C
NTC (Note-1)
Note-1 : If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
Temperature sensor is given with the device. For this reason,
If input type is selected as PTC, sensor type (V = 0,1 or 2) or
If input type is selected as NTC, sensor type (V = 0,3 or 4) must be
declared in ordering information.
ESM-1500N
ESM-1500N
ESM-1500N
ESM-1500N
ESM-1500N
Temperature Indicator
ESM-1500N
24V ( ± 15% ) 50/60Hz - 2.2VA V
3
115V ( ± 15% ) 50/60Hz - 2.2VA V
4
230V ( ± 15% ) 50/60Hz - 2.2VA V
5
24V ( -15%, +10% ) 50/60Hz - 2.2VA W
2
10...30 V - 2.2WZ
8
100-240V ( -15%, +10% ) 50/60Hz - 2.2VA V
1
Temperature Sensor Input
Fuse
Power
Supply
Switch
TC
PTC, N PT-100, PT- 1000TC,
N
L
1A T
21
6
7
a
a
a
a
a
Temperature Indicator
ESM-1500N
230V V
115V V
24V V
24V W
10...30 V Z
100-240V V
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Bursa Organize Sanayi Bölgesi, (Fethiye OSB Mah.)
Ali Osman Sönmez Bulvarı, 2. Sokak, No:3 16215
BURSA/TÜRKİYE
Tel : +90 224 261 19 00 Fax : +90 224 261 19 12
Bursa Organize Sanayi Bölgesi, (Fethiye OSB Mah.)
Ali Osman Sönmez Bulvarı, 2. Sokak, No:3 16215
BURSA/TÜRKİYE
Tel : +90 224 261 19 00 Fax : +90 224 261 19 12
Note-1 : External fuse is recommended.
Note-2 : Stranded cable cross section: 1,5mm², Solid cable cross-section: 2,5mm²
The stripping length is 7 to 9 mm.
Note-3 : Supply cables must comply with the requirements of IEC 60277 or IEC 60245.
9
Customer

Produktspecifikationer

Varumärke: Emko
Kategori: ej kategoriserat
Modell: ESM 1500N

Behöver du hjälp?

Om du behöver hjälp med Emko ESM 1500N ställ en fråga nedan och andra användare kommer att svara dig