Läs gratis den bruksanvisning för Emko SMR1P1-00-00-01-00 (5 sidor) i kategorin ej kategoriserat. Guiden har ansetts hjälpsam av 2 personer och har ett genomsnittsbetyg på 3.7 stjärnor baserat på 1.5 recensioner. Har du en fråga om Emko SMR1P1-00-00-01-00 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/5

11 ENG IPERTU-SMRXXX 02 V01_0824
Semi Universal Analog Input & Analog Output Extension Modules
General Specicaons :
* Modules have 2 or 4 input channels according to module type
* Analog input types (each analog
input can be set in different type
individually) :
- Cu-50, PT100, PT1000, PTC, NTC, mV or
- V, mA
* ON/OFF kontrol, PID kontrol, AutoTune, SelfTune
* According to module type; 4 or 2 analog output (V/mA)
* Modbus RTU communicaon protocol with RS485
* USB Device (For device conguration)
* Modular connecon (up to 16 modules including itself)
* Led indicators:
- Power Supply, USB, RS-485
- Analog Input error led indicators
- Acve Output led indicators
SMR1P1-00-01-00-01_1
SMR1P1-00-03-00-03_1
SMR1P1-00-20-00-01_1
SMR1P1-00-21-00-03_1
Technical Specicaons
Module Type SMR1P1-00-01-00-01 SMR1P1-00-03-00-03 SMR1P1-00-20-00-01 SMR1P1-00-21-00-03
Supply Voltage - 28,8 VDC)
Power Consumpon 3W 4W 3W 4W
Communicaon RS-485 Modbus RTU
USB Device Mini USB, USB 2.0
Analog Inputs
Number of Inputs 4 2 4 2
Input Sensor Type Cu-50, PT-100, PT-1000, PTC, NTC, mV V, mA
Measurement Range
/ Resoluon
Cu-50 -200 ....
-328 ....
PT-100 -200 ...
-328 ...
PT-1000 -200 ...
-328 ...
PTC -50 .....
-58 .....
NTC -50 .....
-58 .....
mV 0 .........
V 0 ......... +2V / 1 mV
0 ......... +5V / 1 mV
0 ......... +10V / 1 mV
2 ......... +10V / 1 mV
mA 0 .........
4 .........
ADC resoluon 15 bit
Input Impedance
Voltage type inputs Other type inputs
mA type inputs
Overall accuracy % 0.2 (full scale)
Response me Per channel
300msec
150 msec 150 msec 150 msec
Average function
The aritmec average of the last read measurements according to the specied average
number of samples
Fault detecons 1- short circuit, 2- sensor break, 3- over range
Analog Outputs
Number of Outputs 2 x V / mA 4 x V / mA 2 x V / mA 4 x V / mA
Output range 0-10V or 0-20mA (only one tpe can be selected in the same me)
Overall accuracy % 0.5 (in the full scale measurement range)
Output Resistance For voltage output for current output
Response me ~200 msec
Led Indicators
Power
Always ON if the power input is in working limits, ashes 0.1s when undervoltage detected
Flashes 1s if the communicaon between Master and Slave module broken

12 ENG IPERTU-SMRXXX 02 V01_0824
Flashes 0.2s ON / 2s OFF if the device in Software Boot Mode
USB
Always ON if the USB cable plugged, ashes during data transfer
RS485
Flashes during Modbus data transfer
Analog Input
Always OFF in normal operaon
Always ON in case of fault detecon (Sensor Break, Short Circuit, Over Range)
Flashes during PID auto-tune or self-tune process ongoing
Analog Output ON when output acve, OFF otherwise
Operaon / Storage Environment
Operaon Temp. -
Storage Temp. -
Isolation
* There is no isolaon between Power, RS485 and USB
* There is no isolaon between Analog Inputs
* There is no isolaon between Analog Outputs
* 500 VAC between Analog Input and Power Input
* 500 VAC between Analog Output and Power Input
* 500 VAC between Analog Input and Analog Output
Modbus Parameters Addresses
Address
R/W
Parameter Name Denion Default
Modbus Parametreleri
40001 R/W ID Modbus ID can be set between 1 255 1
40002 R/W Baud Rate (kbps)
0- 1200 3- 9600 6- 57600
1- 2400 4- 19200 7- 115200
2- 4800 5- 38400
6
40003 R/W Stop Bit 0- 1 Bit 1- 2 Bit 0
40004 R/W Parity 0- None 1- Even 2- Odd 0
Cihaz Parametreleri
40005 R Reserved
In case of Master Mode, shows number of connected
Slave Modules
-
40006 R Type/Bus Order
b15-b8 : module types according to code :
SMR1P1-00-01-00-01_1 = 0xB3
SMR1P1-00-03-00-03_1 = 0xB1
SMR1P1-00-20-00-01_1 = 0xB4
SMR1P1-00-21-00-03_1 = 0xB2
b7-b0 : module bus order :
0- Master module
N-
17- Single module (No other device on bus)
-
40007 R Version
HW and SW versions displayed on a bitwise basis
b15-b12 : Hardware Version
b11-b6 : Soware Major Version
b5-b0 : Soware Minor Version
-
40008 R/W
Error Status
2
Error status displayed on a bitwise basis
b0 : Low Power Supply Voltage Level
b1 : Analog Input could not read
b2 : RS485 communication meout error
1
b8 : Error in slave module number
1
b9 : Error in slave module type
1
b10 : Error in communicaon between slave modules
1
b15-b12 : The number of the Slave module in which the
error was detected
Note-1 : Error bits are only valid for Master Module.
Note-2 : In case of communication timeout error arises in
Master Module, communicaon between slave modules
interrupted. By wring 3083 to the relavent address, the
error bit cleared and the communicaon started again.
-

13 ENG IPERTU-SMRXXX 02 V01_0824
40009 R/W
Timeout Duration
60s)
3
Address R/W
Parameter Name Denion Default
AI0 AI1 AI2 AI3 Analog Input Parameters
40011 R/W
Temperature
Display Unit
Applies to all Analog Input sensor types except
type V or mA.
0- 1-
0
40012
40013
40014
40015
R/W
Sensor Type
SMR1P1-00-01-00-01 SMR1P1-00-20-00-01
SMR1P1-00-03-00-03 SMR1P1-00-21-00-03
for above module types: for above module types:
0- Cu-50 0- 0-2V
1- PT100 1- 0-5V
2- PT1000 2- 0-10V
3- PTC 3- 2-10V
4- NTC 4- 0-20mA
5- mV 5- 4-20mA
0
40016
40017
40018
40019
R/W
Sensor Oset
Value
Depending on the sensor type, values
of measuring range can be entered. For dotted
types, the value must be entered as p3-x10
0
40020
40021
40022
40023
R/W
Average Sample
Number
Number of last sample readings in Analog Input
for average input value calculaon. Value can be
set between (1 20)
4
40024
40025
40026
40027
R Average Value Average analog input value -
40028
40029
40030
40031
R Present Value Present analog input value -
40032
40033
40034
40035
R Errors
Stores error status in the relavant input in bitwise
form
b0 : Sensor Break, Value : 32767
b1 : Short Circuit, Value : 32766
b2 : Over Sample, Value : 32765
-
AI0> AI1> AI2>
3
AI3>
3
Control Parameters
40041
40063
40085
40107
R/W
Control Type
0- Passive (In case of this situaon, related relay
can be controlled manually)
1- PID Mode Acve
2- ON-OFF Mode Acve
3- Manual Proporonal
0
40042
40064
40086
40108
R/W
Set Value
Can be set between (MinScale
MaxScale) values.
For dotted type, value can be set as x10
0
40043
40065
40087
40109
R/W
Set Oset
Can be set between (-MaxScale/2 MaxScale/2)
values. For doed type, value can be set as x10
0
40044
40066
40088
40110
R/W
Hysteresis
Used in ON-OFF mode, can be set between (0
(MaxScale MinScale)/2) values. For doed type,
value can be set as x10
0
40045
40067
40089
40111
R/W
Minimum Scale
Can be set between (MinMeasRange MaxScale)
values. For doed type, value can be set as x10
Alt
40046
40068
40090
40112
R/W
Maximum Scale
Can be set between (MinScale MaxMeasRange)
values. For doed type, value can be set as x10
40047
40069
40091
40113
R/W
Heang Proporo.
Can take values between (0 1000) 100
40048
40070
40092
40114
R/W
Heang Integral Can take values between (0 3600) 100
40049
40071
40093
40115
R/W
Heang Derivave
Can take values between (0 1000) 250
40050
40072
40094
40116
R/W
Cooling Proporo. Can take values between (0 1000) 100
40051
40073
40095
40117
R/W
Cooling Integral Can take values between (0 3600) 100
40052
40074
40096
40118
R/W
Cooling Derivave Can take values between (0 1000) 250
40053
40075
40097
40119
R/W
Output period Can take values between (1 150s) 1
40054
40076
40098
40120
R/W
Heang/Cooling 0- Heang 1- Cooling 0
Produktspecifikationer
Varumärke: | Emko |
Kategori: | ej kategoriserat |
Modell: | SMR1P1-00-00-01-00 |
Behöver du hjälp?
Om du behöver hjälp med Emko SMR1P1-00-00-01-00 ställ en fråga nedan och andra användare kommer att svara dig
ej kategoriserat Emko Manualer
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
ej kategoriserat Manualer
- Stiga
- RGV
- Antec
- GARANTIA
- Vulcan
- IOGEAR
- Nitecore
- Lorelli
- Celly
- Electrolux
- Thermex
- Aspes
- Midea
- KitchenAid
- Zodiac
Nyaste ej kategoriserat Manualer
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025
20 Juni 2025