    Läs gratis den bruksanvisning för Gossen Metrawatt SINEAX TV815 (2 sidor) i kategorin Mätutrustning. Guiden har ansetts hjälpsam av 20 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 10.5 recensioner. Har du en fråga om Gossen Metrawatt SINEAX TV815 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
                        Sida 1/2
                    
                    
                    
SINEAX TV815 
Current / voltage
Isolating amplifi er
173 063 10.14
SINEAX TV815  ENGLISH 4/4
SINEAX TV815  ENGLISH 3/4SINEAX TV815  ENGLISH 2/4SINEAX TV815  ENGLISH 1/4
1. Safety instructions
1.1 Symbols
The symbols in these instructions point out risks and have the following meaning:
Smooth and safe operation requires that these operating instructions be read 
and understood!
Warning in case of risks.
Non-observance can result in malfunctioning.
Non-observance can result in malfunctioning and personal injury.
Information on proper product handling.
1.2 Intended use
•  The purpose of the SINEAX TV815  isolating amplifi er is to galvanically isolate input signals 
from output signals, to amplify them and/or transform them to another level or another 
signal type (current or voltage). 
•  The device is intended for installation in industrial plants and meets the requirements of 
EN 61010-1.
•  Manufacturer is not liable for any damage caused by inappropriate handling, modifi cation or 
any application not according to the intended purpose.
1.3 Commissioning
•  Installation, assembly, setup and commissioning of the device has to be 
carried out exclusively by skilled workers.
•  Observe manufacturer’s operating instructions. Do not operate the device 
outside of the limit values stated in the operating instructions. Check all 
electric connections prior to commissioning the plant.
•  Safety measures should be taken to avoid any danger to persons, any 
damage of the plant and any damage of the equipment due to breakdown 
or malfunctioning of the device.
•  Decommission the device if its safe operation is no longer possible (e.g. in 
case of visible damages). Disconnect all connections. Send the device  to 
our plant or to one of our authorised service centres.
1.4 Repair work and modifi cations
Repair work and modifi cations shall exclusively be carried out by the manufac-
turer. In case of any tampering with the device, the guaranty and warranty claim 
shall lapse. We reserve the right of changing the product to improve it.
1.5 Disposal
The disposal of devices and components may only be realised in accordance 
with good professional practice observing the country-specifi c regulations 
(applicable within the European Union and other European countries with a 
separate collection system).
1.6 Transport and storage
Transport and store the devices exclusively in their original packaging. Do not 
drop devices or expose them to substantial shocks.
2. Scope of delivery
1 Isolating amplifi er SINEAX TV815
1 Operating instructions in German, French and English
4.4 Environmental conditions
Operating temperature  -20…+60 °C
Storage temperature  -40…+85 °C
Humidity  30...90 % at 40 °C (non-condensing)
Area of application  Indoor areas up to 2000 m  above sea level
Degree of pollution  2
Voltage supply  Class 2
4.5 Severe operating conditions
Severe operating conditions are:
• High power supply voltage (> 30 V DC / > 26 V AC)
• Power supply of the input sensor
• Use of the output on generated current (active).
When the modules are installed side by side, it may be necessary to separate them by at least 
5mm in the following cases: 
• If control box temperature exceeds 45 °C and at least one of the severe operating conditions 
exists
• If control box temperature exceeds 35 °C and at least two of the severe operating conditions 
exist.
4.6 Regulations
The device complies with 
the following standards:
EN 61000-4-5 (Surge protection of inputs, outputs/power 
supplies)
EN 61000-6-4/2002 (Electromagnetic interference, industrial 
environments)
EN 61000-6-2/2005 (Electromagnetic compatibility, 
industrial environments)
EN 61010-1/2001 (Safety)
All circuits have to be insulated with double insulation against  
circuits carrying hazardous voltages. 
If using a galvanically isolated power supply unit, a fuse of max. 2.5 A should 
be installed.
5. Mounting instructions
The signal converter is designed to be mounted on rails according to DIN 46277.
Mounting of signal converter 
on the rail
1.  Place the signal converter onto the top 
part of the rail.
2.  Press the signal converter downwards.
Removing the signal converter 
from the rail
1.  Use a screwdriver (as shown in the 
fi gure) as a lever.
2.  Turn the signal converter downwards.
For optimum function and longevity, ensure adequate ventilation of the signal. 
We  recommend  installation  in  vertical  position.   Avoid  installing  the  signal 
converter  above  devices  generating  heat. We  recommend  installing  it  at  the 
bottom of the switch cabinet.  
6. Installation instructions
6.1 Input selection
The input type is selected by setting the DIP switch group SW1.
Each input type corresponds to a certain number of scale  start  and  end  values  which  may  be 
selected by setting DIP switch group SW2.
The table below lists the possible START and END values according to the input type selected.
Note for all tables:
The symbol 
 indicates that the DIP switch is in ON position.
No entry means the DIP switch is in OFF position! 
SW2: START / END
START END Type
1 2 3 4 5 6 Voltage Current
0 V 0 mA
400 mV 1 mA
1 V 4 mA
2 V -1 mA
-5 V -5 mA
-10 V -10 mA
-20 V -20 mA
100 mV 1 mA
200 mV 2 mA
500 mV 3 mA
1 V 4 mA
5 V 5 mA
10 V 10 mA
20 V 20 mA
3. General features
•  Input: Voltage, current.
•  Power supply of the sensor in 2-wire technology: 20 V DC stabilised, max. 20 mA protected 
against short circuits.
•  Measurement on galvanically isolated analog output with active/passive output for voltage 
and current.
•  Selection of input type, START-END, output mode (zero determination, scale reversal), 
output type (mA or V) by means of DIP switch.
•  Indication of available power supply, of scale exceedance or setup error on the front side 
via LED.
•  Galvanic 3-way isolation: Test voltage 1500 V AC.
4. Technical data
4.1 General
Power supply
10…40 V DC, 19…28 V AC, 50…60 Hz, max. 2,5 W; 1,6 W at 24 V 
DC with output 20 mA
Input
Voltage: -20 … +20 V, input impedance 1 MΩ,
max. resolution 15 bit + sign
Current: -20 … +20 mA, input impedance ~50 Ω, 
max. resolution 1 μA
Output
Voltage: 0…10 V / 2…10 V, minimum load 2 kΩ
Current: 0…20 / 4…20 mA, maximum load 600 Ω
Resolution 1.25 mV for voltage output / 2.5 μA for current output
Sample rate 240 sps at a resolution of 11 bit + sign
Response time 35 ms at a resolution of 11 bit
4.2 Accuracy data
Reference conditions 
Ambient temperature  25 °C
Power supply  24 V
Error in relation to maxi-
mum measuring range:
Voltage/current input Voltage output (*1)
Basic accuracy
(at reference ) 
0.1 % 0.3 %
Temperature infl uence 0.01 % /°K 0.01 % / °K
Linearisation error 0.05 % 0.01 %
Other EMI (*2): < 1 %
Data memory  EEPROM for all confi guration data; memory period >40 years
(*1) Values to be added to the errors relating to the input selected
(*2) EMI: Electromagnetic interference
4.3 Installation data
Design Top-hat rail housing
Material PBT (black)
Connections Coded, pluggable screw terminals 0.2...2.5 mm
2
Housing ingress protection IP20
Weight 200 g
Dimensions
100 mm
17,5 mm
112 mm
SW1: INPUT TYPES 
Input types
1 2 3 4
V
mA
Note: Set the DIP switches while 
module is powered down. This avoids 
electrostatic discharges which might 
damage the module.
6.2 Free setting of START and END for measuring
The START and END keys allow the free setting of the start and end values of the scale within 
the measuring range set by means of the DIP switches. This procedure requires a suitable signal 
generator which is able to provide the desired end or start values of the scale.
The procedure is as follows: 
1.  Use the respective DIP switches to set the desired input type as well as START and END for the 
measurement which contain the desired scale start and end value for the measurement.
2.  Switch on power supply.
3.  Attach a generator or calibrator for the signal to be measured or transmitted.
4.  Set the generator to the desired scale start value.
5.  Press the START key for at least 3 s. The green LED on the front panel will fl ash to indicate that 
the value has been stored.
6.  Repeat step 4 and 5 for the desired END value.
7.  Remove power supply of the module and set the DIP switches of group SW2 for the setting of 
START and END values to the OFF position.
Now the module is confi gured for the desired start and end value of the scale. To reprogram it, 
also for other input types, simply repeat the entire process.
6.3 Output selection
DIP switches Nos. 7 and 8 of the SW2 group allow the setting of the respective output with or 
without zero determination, and normal or reversed output. The DIP switch group SW3 lets you 
select the output type.
Note: Set the DIP switches while module is powered down. This avoids electrostatic 
discharges which might damage the module. 
SW2: OUTPUT MODE  SW3: OUTPUT TYPES
7 8 Output type 1 2 Output
0…20 mA / 0…10 V
Voltage
4…20 mA / 2…10 V Current
Normal
Reversed
6.4 LED indications on the front panel
LED (green) Meaning 
Fast fl ashing
(Freq.: 1 fl ash/s)
Outside measuring range  or internal fault
Slow fl ashing
(Freq. = 2 fl ash./s)
DIP switch setting error 
Continuously on Indicates presence of power supply
Produktspecifikationer
| Varumärke: | Gossen Metrawatt | 
| Kategori: | Mätutrustning | 
| Modell: | SINEAX TV815 | 
Behöver du hjälp?
Om du behöver hjälp med Gossen Metrawatt SINEAX TV815 ställ en fråga nedan och andra användare kommer att svara dig
Mätutrustning Gossen Metrawatt Manualer
                        
                         4 Februari 2025
                        
                    
                                                            
                        
                         10 Januari 2025
                        
                    
                                                            
                        
                         26 September 2024
                        
                    
                                                            
                        
                         25 September 2024
                        
                    
                                                            
                        
                         24 September 2024
                        
                    
                                                            
                        
                         23 September 2024
                        
                    
                                                            
                        
                         22 September 2024
                        
                    
                                                            
                        
                         22 September 2024
                        
                    
                                                            
                        
                         21 September 2024
                        
                    
                                                            
                        
                         21 September 2024
                        
                    
                                                            Mätutrustning Manualer
- Oregon Scientific
 - Lund
 - Cocraft
 - Silvercrest
 - Ideal
 - Vimar
 - Honeywell
 - Reely
 - Seek Thermal
 - Arya
 - Jonard Tools
 - SRS
 - Topcom
 - Water-i.d.
 - Delta Ohm
 
Nyaste Mätutrustning Manualer
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025
                        
                    
                                                            
                        
                         3 April 2025