Hager LVS00100SP Bruksanvisning

Hager Strömbrytare LVS00100SP

Läs gratis den bruksanvisning för Hager LVS00100SP (3 sidor) i kategorin Strömbrytare. Guiden har ansetts hjälpsam av 11 personer och har ett genomsnittsbetyg på 5.0 stjärnor baserat på 6 recensioner. Har du en fråga om Hager LVS00100SP eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/3
LVS00100SP
LVS00100SP
NH-Fuse switch vertical desgin LV NH00 100mm 3pole M8
Technical properties
Architecture
Number of poles 3 P
Type of pole 3 P
Main electrical features
Rated operational voltage Ue 690 V
Voltage
Rated impulse withstand voltage 8 kV
Electric current
Cut off current 100 kA
Rated current for Ue=500V AC according to
IEC 61439-1 5.3.2 160 A
Rated current for Ue=690V AC according to
IEC 61439-1 5.3.2 160 A
Rated current 160 A
Rated short-time withstand current 1s 5 kA
Rated conditional short-circuit current for
Ue=400V IEC 61439-1 3.8.10.4 100 kA
Rated conditional short-circuit current for
Ue=690V IEC 61439-1 3.8.10.4 100 kA
Fuse-links test rated cond. short-circuit
current Ue=400V IEC 61439-1 3.8.10.4 160 A
Fuse-links test rated cond. short-circuit
current Ue=500V IEC 61439-1 3.8.10.4 160 A
Fuse-links test rated cond. short-circuit
current Ue=690V IEC 61439-1 3.8.10.4 160 A
Conventional free air thermal current with
Trennmesser and std. cross section 220 A
Conv. free air therm.current w/fuse-links
and std.cross sect. IEC60947-1 4.3.2.1 160 A
Rated conditional short-circuit current for
Ue=500V IEC 61439-1 3.8.10.4 100 kA
Electric current / temperature
Rating current 40°C 160 A
Rating current 45°C 152 A
Rating current 50°C 144 A
Rating current 55°C 136 A
Rating current 60°C 128 A
Subject to technical modifications
Rating current 65°C 120 A
Rating current 70°C 112 A
Fuse
Fuse Size NH00
Dimensions
Height of installed product 123 mm
Length 401 mm
Width of installed product 50 mm
Busbar distance 100 mm
Power
Total power loss under IN 20 W
Loss power at full load 56 W
Maximum Power loss of the Fuse-Link
installed in device 12 W
Dissipated energy in cable 36.46 W
Endurance
Electric endurance in number of cycles 200
Total service life (mechanical and electrical
Materials
Copper weight of the product 645 g
Silver weight of the product 1.45 kg
Material Plastic/metal
Installation, mounting
Tightening torque 14Nm
Torque at mounting on busbar 14 Nm
Connection
Connection cross-sect. flexible conductor 4 - 95mm²
Connection cross-sect. rigid cable 4 / 95mm²
Type of connection Screw connection
Standards
Rated duties according to IEC 60947-1 4.3.4 Continuous operation
Operation of switching devices according to
IEC 60947-1 2.4
depending manual operation (of a mechanical
switching device)
Utilisation category for Ue=400V AC
according to IEC 60947-3 Table 5 AC-23B
Utilisation category for Ue=500V AC
according to IEC 60947-3 Table 5 AC-22B
Utilisation category for Ue=690V AC
according to IEC 60947-3 Table 5 AC-22B
European directive WEEE concerned
Standard cross section according to IEC
60947-1 Tables 9 and 10 70 mm²
Subject to technical modifications
Safety
Protection index IP IP2X
Halogen free Yes
Use conditions
Operating temperature -25…55 °C
Degree of pollution according to IEC 60664 /
IEC 60947-2 3
Storage/transport temperature -40…70 °C
Subject to technical modifications

Produktspecifikationer

Varumärke: Hager
Kategori: Strömbrytare
Modell: LVS00100SP

Behöver du hjälp?

Om du behöver hjälp med Hager LVS00100SP ställ en fråga nedan och andra användare kommer att svara dig




Strömbrytare Hager Manualer

Strömbrytare Manualer

Nyaste Strömbrytare Manualer