Sida 1/24
Installation
and Operation
Instructions
GF 3 BV
ALLAGASH
B-Vent Gas Heater
WARNING:
IF THE INFORMATION IN THESE INSTRUCTIONS
ARE NOT FOLLOWED EXACTLY, A FIRE OR
EXPLOSION MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE
PERFORMED BY A QUALIFIED INSTALLER,
SERVICE AGENCY OR LICENSED GAS SUPPLIER.
WHAT TO DO IF YOU SMELL GAS:
DO NOT TRY TO LIGHT ANY APPLIANCE.
DO NOT TOUCH ANY ELECTRICAL
SWITCHES.
DO NOT USE THE PHONE IN YOUR
BUILDING. IMMEDIATELY CALL YOUR GAS
SUPPLIER FROM A NEIGHBORS PHONE.
FOLLOW YOUR GAS SUPPLIERS
INSTRUCTIONS.
IF YOU CANNOT REACH YOUR GAS
SUPPLIER, CALL THE FIRE DEPARTMENT.
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES
INSTRUCTIONS DANS CETTE NOTICE POUR
REDUIRE AU MINIMUM LE RISQUE DINCENDIE
OU POUR EVITER TOUT DOMMAGE MATERIEL,
TOUTE BLESSURE OU MORTALITE.
NE PAS ENTREPOSER NI UTILISER DESSENCE
NI OU LIQUIDES INFLAMMABLES DANS LE
VOISINAGE DE CET APPAREIL OU DE TOUT
AUTRE APPAREIL.
LINSTALLATION LE SERVICE DOIVENT ETRE
EXECUTES PAR UN INSTALLATEUR
QUALIFIE, AGENCE DE SERVICE OU LE
FOURNISSEUR DE GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.
NE PAS TENTER DALLUMER LAPPAREIL
NE TOUCHEZ A AUCUM NTERRUPTEUR.
NE PAS VOUS SERVIR DES TELEPHONES SE
TROUVANT DANS LE BATIMENT OU VOUS
VOUS TROUVEZ.
APPELEZ IMMEDIATEMENT VOTRE
FOURNISSEUR DE GAZ CHEZ UN VOISIN. SUIVEZ
LES INSTRUCTIONS DU FOURNISSEUR.
SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE
DES INCENDIES.
US
Warnock Hersey
C
THIS STOVE IS SHIPPED AS A
NATURAL GAS STOVE ONLY.
IF USE WITH PROPANE IS
DESIRED, THE STOVE MUST BE
CONVERTED TO USE WITH
PROPANE. FOR YOUR
CONVENIENCE THE STOVE IS
SHIPPED WITH A PROPANE
CONVERSION KIT.
Model: Allagash B-Vent
Gas Stove
Manufactured and
Distributed by:
tul A.S.A.
Fredrikstad, Norway
tul North America
Portland, Maine
TABLE OF CONTENTS:
WELCOME TO JØTUL......................3
STANDARDS......................................................4
GENERAL INFORMATION.........................4
LOCATION.....................5
FLOOR PROTECTION........................6
STOVE CLEARANCES....................6
ALCOVE................................................6
PARALLEL INSTALLATION..................6
CORNER INSTALLATION......................6
MANTEL, CEILING AND TRIM.............6
VENTING REQUIREMENTS.................7
HEARTHMOUNT...................................8
VENTING GRAPH.................................9
GAS CONVERSION..........................10
GAS CONNECTION.........................12
GAS PRESSURE.........................12
HIGH ALTITUDE INSTALLATIONS..............13
AIR SHUTTER ADJUSTMENTS..................14
INSTALLING THE LOG SET............15
INSTALLING DECORATIVE PIPE BRACKETS....15
INSTALLING THE BLOWER..............................16
REMOTE/THERMOSTAT.................................17
SPILL SWITCH OPERATION.............................17
CHECKING THE SYSTEM...................18
OPERATION OF APPLIANCE...........................19
MAINTENANCE..............................................19
REPLACEMENT PARTS....................................21
ILLUSTRATED PARTS .......................22
LIGHTING INSTRUCTIONS ........Inside Back Cover
THIS OWNERS OPERATING AND INSTRUCTIONS MANUAL IS DESIGNED TO
GIVE YOU A SAFE, EFFICIENT, DEPENDABLE INSTALLATION OF YOUR
ALLAGASH B-VENT GAS STOVE.
PLEASE READ THESE INSTRUCTIONS IN THEIR ENTIRETY AND MAKE THEM
AVAILABLE TO ANYONE USING OR SERVICING THE GAS STOVE.
SUGGESTED TOOL LIST FOR
INSTALLLATION AND SERVICE:
*External regulator (for LPG only)
*Piping which complies with local code
*Manual shutoff valve
*Sediment trap
*Tee joint
*Pipe wrench
*Pipe sealant
*10mm open end wrench
*1/2, 7/16 open end wrench
*Phillips head screwdriver
*Flat head screwdriver
*1/4 nut driver
*Gloves
*Safety glasses
*Torx T20 screwdriver
*Leak test solution
2
3
28
22 3/4
WELCOME TO JØTUL:
Congratulations on the purchase of your new
Jøtul gas stove.
We at Jøtul are very happy you have made the
decision to warm your hearth with a Jøtul product.
Your new Jøtul Allagash has inherited the benefits
learned from more than 140 years of producing
stoves. Jøtul is the worlds largest manufacturer
of solid fuel burning appliances and has been
making cast iron wood and coal stoves since 1853.
The Allagash incorporates the most advanced gas
technology with the warm traditional style of cast
iron. With proper care and operation, your new
Jøtul will last many, many years.
The Jøtul Allagash gas stove is a gravity vented
gas fireplace heater. The Allagash B-Vent gas
stove can only be vented vertically directly to
the outside, using type B-vent pipe.
The Jøtul Allagash gas stove is designed to operate
on NATURAL GAS or PROPANE only. For
safe and efficient operation the stove is equipped
with a millivolt gas control valve with a piezo
ignitor. Electrical power is only required when
operating the OPTIONAL forced air blower, if
installed on the stove (part # 129161).
Input Rates
The input rate on the Allagash gas stove is 24,000
BTU/hr maximum input on the high setting for
both natural gas and propane, adjusted down to
19,000 BTU/hr minimum on the low setting, for
both natural gas and propane.
Natural gas 24,000 BTU/hr. maximum input
19,000 BTU/hr. minimum input
Propane 24,000 BTU/hr. maximum input
19,000 BTU/hr. minimum input
C E N T ER
OF REAR
EXIT IS
23
HEIGHT
OF TOP
EXIT IS
27 1/2
13 1/4
22 3/4
18 1/2
4
STANDARDS:
This appliance complies with National Safety
standards and is tested and listed by ITS,
Intertek Testing Services
Middleton, WI
In addition, the Allagash gas stove complies with
and has been tested and listed as a gravity vented
gas fieplace heater and listed to:
ANSI Z21.88-1998(NFPA 54)
CSA 2.33-M98 for Canada.
DO NOT ATTEMPT TO ALTER OR
MODIFY THE CONSTRUCTION OF THE
APPLIANCE OR ITS COMPONENTS. ANY
MODIFICATION OR ALTERATION WILL
VOID THE WARRANTY, CERTIFICATION
AND LISTING OF THIS APPLIANCE.
GENERAL INFORMATION:
THIS HEATER MUST BE INSTALLED
AND MAINTAINED BY A QUALIFIED
SERVICE AGENCY.
The installation and repair of this appliance must
be done by a qualified service person. Failure
to properly install and maintain this heater could
result in an unsafe or hazardous installation,
which may result in a fire, explosion, property
damage, personal injury or loss of life.
This appliance should be inspected before use
and at least annually. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative
that control compartments, burners and
circulating air passageways of the appliance be
kept clean.
Sassurer que le bruleur et le compartiment des
commandes sont propres. Voir les instructions
dinstallation et dutilisation qui accompagnent
lappareil.
The installation must conform to local codes. Your
local tul dealer can assist you in determining
what is required in your area for a safe and legal
installation. Some areas require a permit to install
a gas burning appliance. Always consult your local
building inspector or authority having jurisdiction
to determine what regulations apply in your area.
REMEMBER Your local officials have final
authority in determining if a proposed installation
is acceptable. Any requirement that is requested
by the local authority having jurisdiction, that is
not specifically addressed in THIS manual,
defaults to local code. In the absence of local
codes, the installation requirements must comply
with the current National codes. In the U.S. these
requirements are established in the National Fuel
Code, ANSI Z223.1.(NFPA 54). In Canada, the
codes have been established in CAN/CGA B149
Fuel Installation Code.
Installer lappareil selon les codes ou reglements
locaux, ou, en labsence de tels reglements, selon
les Codes dinstallation CAN/CGA-B149.
DO NOT OPERATE THIS STOVE IF ANY
PART HAS BEEN UNDER WATER.
Immediately call a qualified service technician
to inspect the heater and to replace any part of
the control system and any gas control which has
been under water.
Ne pas se servir de cet appareil sil a ete plonge
dans leau, completement ou en partie. Appeler
un technicien qualifie pour inspecter lappareil et
remplacer toute partie du systeme de controle et
toute commande qui ont ete plonges dans leau.
Do not operate the Allagash gas stove with the
glass front removed, cracked or broken.
Replacement of the glass should be done by a
licensed or qualified service person. Only remove
glass for routine service. Always handle glass
carefully.
Pour utilisation avec les portes en verre cerifiers
aved lappareil seulemend ou Ne pas utiliser avec
des portes on verre.
4
THIS APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY OR FLUE
SERVING ANY OTHER APPLIANCE OF
ANY KIND.
LOCATION:
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns; However, proper venting systems and
access to the fuel supply are also important issues.
Due to the high surface temperatures of the
Allagash, always consider the proximity of traffic
ways, furniture, draperies, etc.
This appliance may be located on or near
conventional construction materials.
HOWEVER,
always maintain the proper clearances to
combustibles, as this provides adequate
ventilation air around the appliance.
The following clearances and hearth requirements
are the minimum requirements when installing
the Allagash gas stove near or on combustible
surfaces. Always provide adequate access around
the appliance for servicing and proper operation.
A combustible surface is anything that can burn
(i.e. sheet rock, wall paper, wood, fabrics etc.).
These surfaces are not limited to those that are
visible and also include materials that are behind
non-combustibles.
If you are not sure of the combustible nature of
a material, consult your local fire officials.
Remember,Fire Resistant materials are
considered combustible: they are difficult to
ignite, but will burn. Also, fire-rated sheet rock
is considered combustible.
The Allagsh B-Vent gas stove is not to be
connected or installed using any warm air duct
system.
Always maintain the proper clearances to the
appliance for the proper flow of combustion and
ventilation air to the stove.
Hot Surfaces
The Allagash gas stove will, during normal
operation, reach high surface temperatures
therefore:
·Due to the high operating temperatures this
appliance should be located out of traffic
and away from furniture and draperies.
·Children and adults should be alerted to the
hazards of high surface temperatures and
should stay away to avoid burns or clothing
ignition.
·Young children should be supervised while
they are in the same room as the Allagash
gas stove.
·Clothing or other flammable materials
should not be placed ON or NEAR the
Allagash gas stove.
·Surveiller les enfants. Garder les vetements,
les meubles, lessence ou autres liquides a
vapeur inflammables loin de lappareil.
·NEVER store or use gasoline or any other
flammable vapors or liquids in the vicinity
of the Allagash gas stove.
·Never burn any other materials in your
Allagash gas stove, it is strictly designed for
use with natural gas or propane fuel ONLY.
·Any safety screen, glass or guard removed
for servicing the appliance must be replaced
prior to operating the appliance.
Blower/Electrical Hazard
When the Allagash gas stove is installed with the
optional forced air Blower Kit (part #129161) the
stove must be electrically grounded in accordance
with local codes or, in the absence of local codes,
with the current NFPA 70- National Electrical
Code or CSA C22.1-Canadian Code.
The Allagash Blower Kit is already supplied with
a three-prong (grounding) plug for protection
against shock hazard and should be plugged
directly into a properly grounded three-prong
receptacle.
DO NOT CUT OR REMOVE THE
GROUNDING PRONG FROM THE PLUG.
Always unplug the Blower when performing
routine service to the Allagash gas stove.
5
STOVE CLEARANCES:
Minimum clearances for the Allagash B-Vent
gas stove are as follows:
Rear clearance =2(50mm)
(measured from draft hood)
Ceiling =18(460mm)
(measured from top of stove)
Corner clearance =3(76mm)
(measured from rear corners)
Right side clearance = 4(102mm)
Left side clearance = 10 (255mm)
(for access to the lighting instructions)
All venting components must be installed in
accordance with the terms of their listing and
manufacturers instructions. Refer to the pipe
manufacturers instructions for proper pipe
clearances. Any horizontal venting requires a
2 (50mm) top clearance off top of pipe.
6
FLOOR PROTECTION:
The Allagash gas stove CANNOT be installed
directly on carpeting, vinyl flooring, linoleum or
Pergoã.
If it is desired to install this appliance on any
combustible material OTHER THAN WOOD,
a floor pad must be installed that is either metal,
wood or a listed hearth pad. This floor protection
must extend the full width and depth of the
appliance. It is not necessary to remove the
carpeting, vinyl or linoleum from underneath the
floor protection. Minimum hearth protection
under the Allagash B-Vent gas
stove:
22 3/4 wide X 18 3/4 deep
ALCOVE
Minimum Alcove Width = 41(1042mm)
(minimum side clearance in an alcove becomes 8
on right side of stove and 10 on left side of stove).
Maximum Alcove Depth = 24(610mm)
Minimum Alcove Height (off stove)= 18(460mm)
(minimum height off top casting of stove).
Pipe clearances =see manufacturers listing.
Note: the hearth requirements are the same when
using the optional short leg package.
CORNER INSTALLATION
PARALLEL INSTALLATION
4
(102 mm)
10
(255mm)
left side
wall
right side
wall
2 (50mm) from
draft hood
3
76mm
3
76mm
MANTEL OR
TRIM
DEPTH
19or greater in depth
6- 18 in depth
2- 5 in depth
MINIMUM
CLEARANCES
TO TOP
PLATE
OF STOVE
A = 18 (460mm)
B = 12 (305mm)
C = 5 (127mm)
1 trim = 1 (25mm)
MANTEL, CEILING AND TRIM
1 trim only
A
B
C
When decorative 6 pipe is installed to cover
the venting any Listed Flexible Gas liner must
be connected directly to the stoves draft hood.
Use of single wall connector pipe as a vent is
prohibited for use with the Allagash B-Vent stove.
A firestop is required at every floor.
Any venting that is exposed above the first
floor, regardless of attic space or living space,
must be enclosed. Always maintain the
required clearance from all sides of the vertical
vent system according to manufacture.
Installation of any components not
manufactured or approved by Jøtul or failure
to meet all clearance requirements will void
all warranties and could result in property
damage, bodily injury, or serious fire.
Never modify any venting component, or use
any damaged venting product.
THE GAS APPLIANCE AND VENT
SYSTEM MUST BE VENTED DIRECTLY
TO THE OUTSIDE OF THE BUILDING,
AND NEVER ATTACHED TO A
CHIMNEY SERVING A SOLID FUEL OR
GAS BURNING APPLIANCES.
BE SURE TO MAINTAIN THE PROPER
CLEARANCES TO COMBUSTIBLES AS
DEFINED IN THIS MANUAL AND IN
THE INSTRUCTIONS PROVIDED WITH
EACH VENTING COMPONENT.
When installing at an altitude above 2000 the
minimum vertical rise becomes 12 from the
draft hood.
If more than two feet of venting is exposed to
the outside, the entire exterior vent system
must be enclosed in an insulated chase system.
8
Listed termination
cap required
Storm collar
required
Recommended
damper sealing plate
to seal flue chamber
to prevent heat loss
Allagash B-Vent gas
stove
Always maintain
the proper
clearance to mantel
and trim
Allagash B-Vent gas stove vented into a
masonry or prefabricated fireplace.
Maximum
offset is 4
Type B vent or
Listed Flexible
Gas Liner. On
outside chimneys
tul recommends
the use of Type B
vent to help keep
the gases warm and
rising.
max. height 35
min. height 7
Top sealing
achor plate
WA R NI N G : FA I LU RE TO P O S IT IO N TH E PA RT S IN
ACCORDANCE
WITH THIS DIAGRAM OR FAILURE TO USE
ONLY PARTS SPECIF ICALLY APP ROVED WITH THIS
APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR
PERSONAL
INJURY.
8. Adjust the air shutter on the burner tube to allow
for the proper mixing of air and gas. See Figure 2.
The correct settings: natural 1/4 open
propane 1/4 open
WHEN RE-INSTALLING THE BURNER TUBE BE SURE
THAT THE TUBE IS PULLED FORWARD IN THE
MOUNTING HOLES, SECURE WITH THE TWO 1/4
SCREWS.
9. Change the pilot orifice. FROM WITHIN
THE FIREBOX, PULL THE PILOT
HOOD OFF THE PILOT ASSEMBLY.
Using a 4mm allen wrench thread out the pilot
orifice (counter clockwise). Replace with the
appropriate orifice: See Figure 3.
#51or natural gas
#30 for propane
Tighten orifice into the base of the pilot
assembly. Be sure the orifice is threaded tightly
and flush with the base.
10. Replace pilot hood onto pilot assembly.
14. Install the identification labels to the stove so
that they can be seen by any person that may be
servicing the stove.
15. Reassemble the stove, apply gas to the system
and check for gas leaks including all stove lines
before and after the valve.
NEVER USE AN OPEN FLAME TO
CHECK FOR GAS LEAKS.
ATTENTION!! ATTENTION!!
This is very important
Correct gas pressure is essential for efficient and
safe operation of the Allagash B-Vent gas stove.
It is important that the correct gas pressure be
established at the time of the installation. For
more details, see the Gas Pressure section of this
manual on page 13.
ALWAYS REFER TO THE LIGHTING
INSTRUCTIONS ON PAGE 23 OF THIS
MANUAL WHEN LIGHTING YOUR
ALLAGASH.
11
11. Change the variable regulator on the valve (Hi/
Lo knob). Using a Torx t-20 screwdriver, remove
the three specialty screws from the front of the
valve regulator. See Figure 4.
12. Remove the regulator tower and the gasket.
BE SURE TO REMOVE THE BLACK
RUBBER GASKETS FROM THE VALVE!!!
See Figure 4.
13. Install the new variable regulator tower with
the new rubber gasket.
Thoroughly tighten new
regulator to valve body.
BURNER TUBE
AIR SHUTTER
ATTENTION: Air shutter should never be
LESS than 1/8 open.
Figure 2
Figure 4.
BE SURE TO REMOVE
THE BLACK RUBBER
GASKET FROM THE
VALVE!!!
Figure 3.
PILOT HOOD
PILOT ORIFICE
SCREWS INTO
BASE
PILOT
ORIFICE
Secure all joints tightly using appropriate tools
and sealing compounds (for propane units, be sure
to use compounds that are propane resistant).
Turn on gas supply and test for gas leaks using a
soapy water solution. Never use an open flame
to check for leaks.
Leak test:
·Mix a 50-50 solution of water and dish soap.
·Light appliance- see lighting instructions on
page 23 of this manual or on the stoves rating
plate.
·Brush or spray all joints and connections with
the soapy water solution.
·If bubbles appear at any connection or seam
or a gas odor is detected, immediately turn
gas control knob to the OFF position.
Tighten or reconnect the leaking joint and retest
for any gas leaks.
GAS PRESSURE:
Correct gas pressure is essential for efficient and
safe operation of the Allagash gas stove. It is
important that the correct pressure is established
at the time of the installation.
Proper gas pressure provides a consistent flow of
gas to the appliance and is instrumental in
checking for gas leaks.The gas control valve on
the stove is equipped with pressure test points
for gauge connections. The gauge connections
are located on the front of the valve under the
On/Off/Pilot- knob. Gauge connections are
identified by:
E for inlet or supply pressure (the amount of
gas coming to the valve.)
A for manifold pressure (the amount of gas that
is coming out of the valve to the burner.)
MAKING THE GAS CONNECTION:
NOTE: IF THE OPTIONAL FORCED BLOWER KIT
(PART # 129161) IS TO BE INSTALLED ON THE
STOVE AT THE TIME OF THE INSTALLATION
OR IN THE FUTURE, THE GAS SUPPLY LINE
SHOULD BE INSTALLED AS CLOSE TO THE
FLOOR AS POSSIBLE.
USE OF A 90° ELBOW DIRECTLY OFF THE VALVE
WILL ALLOW FOR PROPER CLEARANCE FOR
THE BLOWER.
The gas supply line connection is made to the valve
just inside the left rear leg. The Gas supply line
should be a minimum of 3/8" in diameter, or
the appropriate size to provide sufficient gas
pressure to the valve regardless of the input
setting.
The use of Flexible Gas Appliance Connectors is
acceptable in many areas in the U.S.; However,
Canadian methods vary depending on local code.
ALL INSTALLATIONS MUST COMPLY
WITH LOCAL CODE OR IN THE ABSENCE
OF LOCAL CODE, MUST COMPLY WITH
THE MOST RECENT EDITION OF THE
NATIONAL FUEL GAS CODE ANSI Z223.1/
NFPA 54 OR CAN-B149.
All codes require: a gas shut-off valve (gas cock)
and union, to be installed in the supply line, and
in the same room as the appliance. This allows
for the disconnection of the stove for servicing
and maintenance. See Figure 5.
Figure 5
T-handle gas cocks are required in Massachusetts
in compliance with code 248CMR.
E A
Pressure test point as located on the front of the valve.
12