Läs gratis den bruksanvisning för Megger 21017 (6 sidor) i kategorin mätning. Guiden har ansetts hjälpsam av 37 personer och har ett genomsnittsbetyg på 4.4 stjärnor baserat på 4 recensioner. Har du en fråga om Megger 21017 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/6
M210170
Insulation &
Low Resistance Tester
User Guide
SAFETYWARNINGS
Safety Warningsread and understoodand mustbe Precautions
before the instrument is used. They must be during use.observed
The circuit under test mustbe switched o, de - energized and
before Insulation or Continuity tests are made.
Circuit connections be touched during a test.must not
The test button be pressed while connecting the test must not
leads or while changing ranges.
The Testnotbutton must be pressed when making a voltage test.
The Default VoltmeterAutomatic discharge, andare additional
safety features and
should notbe regarded as a substitute for
normal safe working practice.
The 210170is protected for connection to Power distribution
systems up to 300 V
LineGroundLineLine- , and 500 V - for
Installation Category III.*
It is recommended that fused test leads are used when measuring
voltage on high energy systems.
After insulation tests, capacitive circuits must be allowed to
discharge
beforedisconnecting the test leads.
Test leads, prods and alligator clips in good order; clean, must be
and with no broken or cracked insulation.
Replacement fuses of the correct size, type and rating.must be
Symbols used on the instrument
Caution: risk of electric shock
Caution: refer to accompanying notes
Equipment protected throughout by Double
Insulation (Class
II)
NOTE
THEINSTRUMENTMUSTONLYBEUSEDBYSUITABLYTRAINEDANDCOMPETENT
PERSONS.