Megger 210170 Bruksanvisning
Läs gratis den bruksanvisning för Megger 210170 (6 sidor) i kategorin mätning. Guiden har ansetts hjälpsam av 4 personer och har ett genomsnittsbetyg på 4.3 stjärnor baserat på 2.5 recensioner. Har du en fråga om Megger 210170 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/6

M210170
Insulation &
Low Resistance Tester
User Guide
SAFETY WARNINGS
✱Safety Warnings read and understoodand must be Precautions
before the instrument is used. They must be during use.observed
✱The circuit under test must be switched o, de - energized and
isolated
before Insulation or Continuity tests are made.
✱Circuit connections be touched during a test.must not
✱The test button be pressed while connecting the test must not
leads or while changing ranges.
✱The ‘Test not’button must be pressed when making a voltage test.
✱The Default Voltmeter Automatic discharge, and are additional
safety features and
should not be regarded as a substitute for
normal safe working practice.
✱The 210170 is protected for connection to Power distribution
systems up to 300 V
Line Ground Line Line- , and 500 V - for
Installation Category III .*
✱It is recommended that fused test leads are used when measuring
voltage on high energy systems.
✱After insulation tests, capacitive circuits must be allowed to
discharge
before disconnecting the test leads.
✱Test leads, prods and alligator clips in good order; clean, must be
and with no broken or cracked insulation.
✱Replacement fuses of the correct size, type and rating.must be
Symbols used on the instrument
Caution: risk of electric shock
Caution: refer to accompanying notes
Equipment protected throughout by Double
Insulation (Class
II)
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT
PERSONS.

OPERATION
Default Voltage measurement
The 210170 will act as a default voltmeter (0 to 600 V a.c.) with any of the
Insulation test positions selected. The ‘Test’push must not be pressed when
making a voltage test. Note:- The 210170 is internally fuse protected to 500
V. For fuse protection with supplies above 500 V, use Fuse Probe Kit FPK5.
1. Select any Insulation test position with the rotary selector switch.
2. Carefully connect the test leads to the circuit under test.
Do not press the
‘Test push’.
3. Read the voltage measurement from the voltmeter scale.
4. Carefully disconnect the test leads.
Low Resistance measurement (Ω)
1. Select Ωwith the rotary selector switch.
2. Ensure that all test leads are clean and in good condition, and connect
them to the
isolated circuit under test.
3. Any pointer deection indicates a live circuit
, and testing should be
aborted.
4. Press the ‘
Test’push, and keep it pressed while turning the generator
handle.
5. Read the measurement from the
kΩscale.
6. Disconnect the test leads.
Insulation Testing (MΩ)
Automatic circuit discharge is eective when the test button is released, and
decaying voltage is indicated by the scale needle until the circuit is
discharged.
1. Select
MΩwith the rotary selector switch.
2. Ensure that all test leads are clean and in good condition, and connect
them to the
isolated circuit under test.
3. Any pointer deection indicates a live circuit
, and testing should be
aborted.
4. Press the ‘
Test’button, and keep it pressed while turning the generator
handle.
5. Read the measurement from the
MΩscale.
6. Release the ‘
Test’push and monitor any scale needle movement to
confirm when any discharging voltage decays to zero.
7. When the circuit has discharged, disconnect the test leads.
Refer to Safety Warnings before using the instrument
MEASUREMENT SCALES

Using the Guard Terminal
For basic insulation tests and where there is little possibility of surface
leakage aecting the measurement, it is unnecessary to use the guard
terminal.
In cable testing, there may be surface leakage paths across the insulation
between the bare cable and the external sheathing due to the presence of
moisture or dirt. Where it is required to remove the eect of this leakage,
particularly at high testing voltages, a bare wire may be bound tightly around
the insulation and connected via the third test lead to the guard terminal ‘G’.
The guard terminal is at the same potential as the negative terminal. Since the
leakage resistance is eectively in parallel with the resistance to be
measured, the use of the guard causes the current owing through surface
leakage to be diverted from the measuring circuit. The instrument therefore
reads the leakage of the insulator, ignoring leakage across its surface.
SPECIFICATION
Insulation Ranges
Measuring Ranges: 0 - 20,000 M at all test voltagesΩ
Test Voltages (d.c.): 100 V; 250 V; 500 V; 1kV on open circuit
Test V. Accuracy: ±5%
Short Cct. Current: 220 µA nominal on all ranges
Accuracy: ±3% of scale length on a 3.08 inch arc length
Low resistance Range
Measuring Range: 0 - 5000 Ω
Open Cct. Voltage: 3 V ± 5%
Short Cct. Current: 30 mA ± 10%
Accuracy: ±3% of scale length on a 3.08 inch arc length
Default Voltage measurement
Range: 0 - 600 V a.c.
Accuracy: ±2.5% of scale length
General Specications
Overload rating: The 210170 is protected for connection to Power
distribution systems up to 300 V , and Line Ground-
500 V for Installation Category Line Line- III*.
Terminal Characteristics
Leakage path
to ‘+’ve
terminal
to ‘G’
terminal
to ‘-’ve
terminal
Tightly bound bare wire
Produktspecifikationer
Varumärke: | Megger |
Kategori: | mätning |
Modell: | 210170 |
Behöver du hjälp?
Om du behöver hjälp med Megger 210170 ställ en fråga nedan och andra användare kommer att svara dig
mätning Megger Manualer
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
2 Augusti 2025
mätning Manualer
- Flir
- Chauvin Arnoux
- Uni-T
- Blackmagic Design
- Owon
- Nebula
- Emko
- GW Instek
- Hager
- Milwaukee
- Eastron
- Ade
- Tektronix
- Phoenix Contact
- PCE Instruments
Nyaste mätning Manualer
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025
31 Juli 2025