Läs gratis den bruksanvisning för Megger VF6 EX (6 sidor) i kategorin Detektor. Guiden har ansetts hjälpsam av 2 personer och har ett genomsnittsbetyg på 4.3 stjärnor baserat på 1.5 recensioner. Har du en fråga om Megger VF6 EX eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/6

VF6 EX
AC VOLTAGE DETECTOR WITH TORCH
USER GUIDE

www.megger.com
Product Name
2
The Megger VF6 EX Voltage Detector is intended to check
for the presence of AC voltage, indicated by a bright red
LED situated within the white nylon tip and an audible
sounder plus vibration alert.
The product is EX rated for use on gas platforms and other
petrochemical environments.
The detector has both low voltage (12 V - 1000 V) and
medium voltage (100 V - 1000 V) ranges.
The VF6 EX has the added advantage of a bright-white LED
torch for use in poor light.
The Megger VF6 EX is useful for identifying live conductors,
finding a break in a wire, verifying a blown fuse while in
circuit, and detecting AC voltage at:
Socket outlets
Switches
Circuit breakers
Fuses
Wires and cables
Luminaires
Hazardous areas, gas platforms and petrochemical
installations
Features
Non-contact detection of AC voltage
12 V ~ 1000 V AC and 100 V ~ 1000 V AC 50 Hz / 60
Hz CAT IV 1000 V
EX rated for use in explosive atmospheres /
petrochemical locations
Visual, audible and vibration warning of low and
medium voltages
Durable rubber over-moulded body
Built-in bright-white LED torch
Low power consumption
Convenient pocket-size
Safety Warnings
Read, understand and follow Safety Warnings and
Operating Instructions in the manual before using this
product.
The detector’s safety features may not protect the
user if not used in accordance with the manufacturer’s
instructions.
Check on a known live source within the rated AC voltage
range of the detector before use to ensure it is in working
order.
Insulation type and thickness, distance from the voltage
source, shielded wires, and other factors may affect reliable
operation.
The VF6 EX may help in the indication of live AC circuits
only and must not be used as verification of a de-energised
circuit. This is not a Safety Test Lamp.
Do not use if the detector appears damaged or if it is not
operating property. If in doubt replace the product.
Do not use on voltages that are higher than as marked on
the VF6 EX.
Use caution with voltages above 30 V AC as a shock
hazard may exist.
Comply with all applicable safety codes. Use approved
personal protective equipment when working near live
electrical circuits-particularly with regard to arc-flash
potential.
Do not operate detector if Low Battery warning occurs.
Replace batteries immediately.
Use only GP AAA / LR03 batteries; do not replace batteries
when an explosive atmosphere is present.
NOTE: The VF6 EX is unable to detect voltage on armoured
or sheathed cable, cable in conduit, behind panels or in
metallic enclosures.
CATIV
Measurement category IV: Equipment connected between
the origin of the low-voltage mains supply outside the
building and the consumer unit.
CATIII
Measurement category III: Equipment connected between
the consumer unit and the electrical outlets.
CATII
Measurement category II: Equipment connected between
the electrical outlets and the user’s equipment.
International Safety Symbols
G
Potential danger. Indicates the user must refer
to the manual for important safety information
F Indicates hazardous voltages may be present
t Equipment is protected by double or reinforced
insulation
Equipment complies with current EU directives
End of life disposal
EX Rating

www.megger.com Product Name
3
Detector Description
1. Screw on battery cover
2. Torch
3. Torch button
4. 12 V button
5. On/Off button
6. LED indicators
7. Detector tip
8. Work light
Operation
1. Turning the VF6 EX on: Momentarily press the
detector
On/Off button. The detector will beep
once, vibrate once and the green LED will illuminate to
indicate that the detector is on and ready for use.
2. Turning the VF6 EX off: Momentarily press the
On/Off button. The VF6 EX will beep twice and vibrate
twice and the green LED will turn off.
3. Turning the Sounder off and Vibrating motor off:
Turn the VF6 EX on as described above. The VF6 EX will
now operate with both the sounder and the vibrating
motor. To turn the sounder and vibrating motor off, press
and hold the On/Off button until the green LED flashes
once. To turn the sounder and vibrating motor back on
press and hold the
On/Off button until the green
LED flashes, the sounder beeps and the unit vibrates.
4. Verify Operation: Before using VF6 EX, (1) Make sure
the green LED is on, (2) Check VF6 EX on a known live
AC voltage that is within the defined detection range
of the VF6 EX.
5. Low Voltage Mode (12 to 1000V AC): Press and
hold the 12 V button. The green LED will change to
orange to indicate the VF6 EX is in the low voltage
mode. While pressing the 12 V button place the tip of
the VF6 EX near an AC voltage. When AC voltage is
detected the LED will turn red and flash, the sounder
will beep and the detector will vibrate. The flash,
beeping and vibration rate will increase as the VF5 gets
closer to the voltage source. If the VF6 EX detects a
medium voltage (100 V – 1000 V) it will automatically
change over to the medium voltage mode, the red LED
will change to a steady glow, the sounder will beep
rapidly and the detector will vibrate constantly.
6. Medium Voltage Mode (100 to 1000V AC): Place
the tip of the VF6 EX near an AC voltage. If the VF6 EX
detects voltage within the defined detection range the
green LED will turn off, the red LED will turn on, the
sounder will beep rapidly and the detector will vibrate
constantly.
NOTE: The detector cannot determine the actual voltage.
The voltage level where the detector switches from the
low to medium voltage mode is affected by insulation type
and thickness, distance from the voltage source, and other
factors.
7. Replace the batteries if the Low Battery Indication:
green LED does not turn on. When the detector is on
and the batteries are too low for reliable operation,
the sounder will beep three times and the green LED
will turn off indicating the detector Is not operational.
Replace the batteries to restore operation.
8. f: To conserve battery life the detector Auto Power Of
will automatically turn off after approximately 5
minutes of inactivity. When powering down the
detector will beep twice, vibrate twice and the green
LED will turn off.
9. Torch: Momentarily press the torch button to
turn the torch on or off. To conserve battery life, the
torch will automatically turn off after approximately 5
minutes.
NOTE: If the battery voltage is too low to operate the
torch, the detector will indicate this condition by beeping
three times and the torch will turn off. The voltage
detector has its own low battery threshold and may remain
operational. Refer to Verify Operation (Step 4) in this guide
before using detector.
Produktspecifikationer
Varumärke: | Megger |
Kategori: | Detektor |
Modell: | VF6 EX |
Behöver du hjälp?
Om du behöver hjälp med Megger VF6 EX ställ en fråga nedan och andra användare kommer att svara dig
Detektor Megger Manualer
2 Augusti 2025
1 Augusti 2025
31 Juli 2025
Detektor Manualer
- Brennenstuhl
- Resideo
- Winland
- Olympia
- DSC
- Guardian Avionics
- Metrix
- Astralpool
- Gossen Metrawatt
- AcuRite
- ZKTeco
- Steinel
- Safescan
- GEV
- Inovonics
Nyaste Detektor Manualer
31 Juli 2025
30 Juli 2025
29 Juli 2025
29 Juli 2025
29 Juli 2025
27 Juli 2025
27 Juli 2025
27 Juli 2025
27 Juli 2025
27 Juli 2025