Vemer SRG Bruksanvisning


Läs gratis den bruksanvisning för Vemer SRG (1 sidor) i kategorin gas detektor. Guiden har ansetts hjälpsam av 2 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 1.5 recensioner. Har du en fråga om Vemer SRG eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/1
ON
SRG
TEST
RESET
Mod. SRG
V3IS00461–010
86.7
106.0
86.7
50.5
12.0
C S A
+
1
2
5 6 7 8
15 16
17
8 9 10
3 4
5
5
6 7
300mA max
12V
8A / 250V
1
2
V
a
c
/
d
c
Fault
Alarm
g
h
j
P
o
w
e
r
s
u
p
p
l
y
Power supply
User manual
SRG - CENTRAL UNIT FOR GAS DETECTOR
Read all the instructions carefully
TheSRGisacontrolunitforthecreationofgasdetectionsystemsinareas
suchasboilerrooms,workshops,warehouses,laboratories,etc.Itisdesignedto
workwithprobessuchasCOSensor,CH4SensorandLPGSensor.Itoffersthe
possibilitytocontrolasolenoidvalveoranauxiliarydevice(siren,flasher,etc.)
usinganalarmrelaycontainedinside.ThealarmorfailureisdisplayedbyLED.
SAFETY WARNINGS
To ensure correct installation, you must comply with the following
indications:
1) The device must be installed by a competent person
2) The device must be installed in a panel where, after installation, the terminals
can no longer be accessed
3) In the electrical system up the line from the energy meter there must be a
device to protect against overloads.
4) Connect the instrument following the diagrams shown in this sheet and in the
product marking
5) Before accessing the terminals, make sure the leads to connect to the
instrument are not electrically live
6) Do not power and connect the instrument if any part of it is damaged or
missing.
Code Model Description
VE204400 SRG Gasdetectorwith1connectingsensor
VE205100 CH4 SENSOR Methanedetectionsensor
VE206900 LPG SENSOR LPG sensor
VE207700 CO SENSOR Carbonmonoxidesensor
TECHNICAL CHARACTERISTICS
SRG control unit
• Powersupply:
−Voltage:12Vac/dc±10%
−Powerconsumption:~160mA
−Connection:terminalsof2.5mm
2
−Protection:fuse1A5x20mm
• Input:
−1inputforCH4Sensor(methane),LPGSensor(LPG)orCOSensor(CO)
−Sensorconnection:terminalsof2.5mm
2
C(common),S(signal),A(powersupply)
−Max.lengthofconnection:50m
−Cross-sectionoftheleads:1.5mm
2
• Output:
−Alarm:relaywithexchangecontact8A/250VAC
−Failure:opencollector12Vdc/300mAmax
−Outputconnection:terminalsof2.5mm
2
• Luminoussignals: greenLED:powersupplied
yellowLED:failure
redLED:gasalarm
• Reset/testbuttonforalarmresetandprobetestfunctions
• Degreeofprotection:IP20;IP40whencorrectlyinstalledinanelectricalpanel
• Degreeofpollution:II
• Ambienttemperature:0÷+50°C
• Humidity: 90%R.H.withoutcondensation
• Productforassemblyon6-moduleDINrails
Sensors for SRG control units
• Powersupply:fromthecontrolunitSRG
−Currentinput(at6.5V):40mA
−Connection:terminalsof2.5mm
2
C(common),S(signal),A(powersupply)
• Modelsandcalibration:
−Methanegas:CH4Sensor,(default)10%LIEofmethane
−LPG:LPGSensor,(default)12%LIEofisobutene
−Carbonmonoxide:COSensor,(default)200ppmofcarbonmonoxide
• Container:inself-extinguishingplasticmaterial
• Fastenedtowallusingscrewsandplasticplugs
• Protection:IP30
• Ambienttemperature:0÷+50°C
• Humidity: 90%R.H.withoutcondensation
INSTRUMENT DESCRIPTION
Ledpowersupply
Led signaling failure
Led signaling gas alarm
Reset/Testbutton
Powersupplyterminals
Terminals for open collector failure
g
Terminalsforalarmoutputrelay
h
Terminals for gas sensor connection
Set-upjumper
j
Protectionfuse1A
INSTALLATION
Do not use the device in excess of the limits set forth in the technical data. The installer is
responsible for correct, safe installation of the product. Use care during shipping, storage
and handling.
1) Protectionofthedevice.
Toensuretheproperdegreeofprotectionoftheunit,itisnecessarytoinstallthecontrol
unitinanelectricalpanelconstructedinaccordancewithcurrentstandardsforthe
workplace,andinsideofwhichthepowersupplysystemcanalsobehoused.Thecontrol
unitcanbeinstalledatthebottomofthepanelorinDINmodularpanels.
TheLPG,COandCH4Sensorsaredesignedtobewall-mounted(vertically),usingscrews
andplasticplugs.Toproceedwithinstallation,openthecontainerbyunscrewingthe
screwlocatedontheside.Makesurenottodamagethesensorandnottotouchthe
calibration devices.
2) Installationoftheproduct.
Thecorrectinstallationoftheprobeisessentialtoproperoperationofthesystem.
Therefore,itmustbeinstalled:
–Inareaswithcirculationofnaturalair;
–Inareasthatarenotsubjecttodustordirtthatmayrenderthesensorinoperative;
–Nearjetsofwater,intakegrilles,openings,etc;
–Atanadequatedistancefromusersofgassoastopreventthesystemfromintervening
improperlyduetofunctionalleakage.
Also,positioningdependsonthetypeofgastobedetected,specifically:
– CH4 Sensor: Methane gas - at top, about 20-30 cm from the ceiling
– LPG Sensor: LPG - at bottom, about 20-30 cm from the floor
– CO Sensor: carbon monoxide – about 1.5 m from the floor
Fornewsystems,theprobemustbeinstalledaslateaspossible,sothattypical
constructionsiteactivitiesdonotdamagethedetector.
3) Connectionsanduseoftheproduct.
Normalelectricalcablescanbeusedforconnections.Inanycase,wheninstallationis
inplacesthatarestronglyexposedtoelectromagneticdisturbances,itisadvisableto
useshieldedcables.Thedetectionsystemmustalwaysbeinoperation.Therefore,the
electricalpowersupplyofthedetectormustnotincludeswitchesorotherdevicesthat
mayaccidentallyshutitoff.Thepowersupplyofthecontrolunitmustcomplywiththe
requiredvaluesandthecurrentinputofanydeviceconnecttotheterminalsoftherelay
mustbelessthanorequaltothemaximumcapacityofthecontacts.Theaveragelifespan
oftheprobesis5yearsfromthedateofinstallation.Therefore,attheendofthattime
theywillneedtobereplaced.
Attention: make sure you check operation at least once a year, and in any case
whenever there is an extended period of disuse or in the event of replacement.
Any tampering may compromise correct operation of the system.
OPERATION
Oncethedevicehasbeeninstalled,youwillneedtoselecttheoperatinglogicusing
jumperE1.Itcanbeeitherpositiveornegative.Thecontrolunitsignalsitsoperating
statusbymeansofLED’s.
A
Position A
Positive logic
Position B
Negative logic
B
A
B
E1
E1
E1
A
B
DependingonthelogicselectedusingjumperE1,inanormalsituation(noalarms),the
LED’sandtherelaywillbe:
–positivelogic:LEDon,relayenergized
–negativelogic:LEDoff,relayde-energized
Ifnegativeoperatinglogicisselected,thealarmrelaymaybecontrolledinpermanentor
impulsivemode,dependingonthepositionofjumperE2:
A
Position A
Alarm relay
Permanent control
Position B
Alarm relay
Impulsive control
B
A
B
E2
E2
E2
A
B
Oncepoweredon,thecontrolunitperformsthefollowingphasesinsequence:
• Buzzertest(durationabout5seconds)whichcausessequentiallightingoftheLED’sand
abriefringingofthebuzzer.
• Pre-heatingoftheprobe(whichlastsabout1minute),duringwhichthedetection
systemisnotoperationalbecausethisallowstheprobetoreachthecorrectoperating
temperature.
Dimensions
Connection diagram
Description
• Operationaltest(whichlastsabout3minutes)duringwhichthepowersupplyLED
flasheswithafrequencyof2Hzandalltimesettingsareresettozerotomakeiteasierto
checktheprobe.PresstheReset/Testforaboutonesecondtointerrupttheoperational
testphaseandchecktheprobe.
• Gasalarmtest,whichoccursbyplacingthetestspraycanneartheprobeandreleasing
asmallamountofgas.Donotdirectthespraydirectlyontothesensoroftheprobe,
asitmaydamageitirreparably.Thecontrolunitwillsignalthealarminthefollowing
manner:
Interface Positive logic Negative logic
Led for probe alarm(red)
Off On
Alarmbuzzer Continuous sound Continuous sound
Alarmrelay De-energized Energized(permanentlyor
in impulsive mode)
PresstheReset/Testkeyforonesecondtosilencethealarm(ifthegasisnolonger
present)andendthetestphase.Torestartthetestphase,pressthecorrespondingbutton
for about 6 seconds.
• Probefailuretest,whichistobesimulatedsimplybydisconnectingtheprobecableand
checkingthefollowingsignals:
Interface Positive logic Negative logic
Led for probe failure(yellow)
Off On
Alarmbuzzer Intermittent sound Intermittent sound
Faulureoutput Off On
Oncethetesthasbeenmade,re-connecttheprobeandpresstheReset/Testbuttonto
restorethecontrolunittonormaloperation.
Normal operation
Duringnormaloperationofthecontrolunit,boththemonitoringforgasalarmandthe
self-diagnosisforplantanomalies(probe)andsystemsanomalies(controlunit)areactive.
Inthisphaseandwithnoalarmsorfailures,thecontrolunitstatusisasfollows:
Interface Positive logic Negative logic
Led (green)forpowersupply
On On
Led for failure(yellow)
On Off
Led for gas alarm(red)
On Off
Alarmbuzzer Nosound Nosound
Alarmrelay De-energizedEnergized
Faulureoutput On Off
Inpresenceofgasalarmorprobefailure,thecentralunitgoesintothesameconditions
describedintherelativestestphase.
REFERENCE STANDARDS
ConformitytotheEUdirectives
2006/95/EC(LowVoltage)
89/336/ECmodifiedby92/31/ECCand93/68/EEC(E.M.C.)
isdeclaredwithreferencetothefollowingharmonisedstandard:
EN 61779-1, EN 50270


Produktspecifikationer

Varumärke: Vemer
Kategori: gas detektor
Modell: SRG

Behöver du hjälp?

Om du behöver hjälp med Vemer SRG ställ en fråga nedan och andra användare kommer att svara dig




gas detektor Vemer Manualer

gas detektor Manualer

Nyaste gas detektor Manualer