Hager HIC440G Bruksanvisning
Hager
strömbrytare
HIC440G
Läs gratis den bruksanvisning för Hager HIC440G (6 sidor) i kategorin strömbrytare. Guiden har ansetts hjälpsam av 2 personer och har ett genomsnittsbetyg på 4.1 stjärnor baserat på 1.5 recensioner. Har du en fråga om Hager HIC440G eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/6

1
Step 1
Cabinet /
Back Plate
Installation
Step 2
Connecting the
power section
Step 3
COMMAND /
CONTROL
terminal
connections
Step 4
Power SUPPLY
and
controller
terminal
connections
Step 5
Check
Step 6
Programming
Step 7A
AUT Mode
(Automatic
Control)
Step 7B
AUT Mode
(Remote
Control)
Step 7C
Emergency
Manual
Operation
Step 7D
Padlocking
6LE001123A.e
Preliminary operations
Check the following upon delivery and after removal
of the packaging:
• Packaging and contents are in good condition.
• The product reference corresponds to the order.
• Contents should include:
- 1 x motorised changeover switch
- 1 x emergency handle and fi xing clip
- 1 x quick start instruction sheet.
Accessories
• Bridging bars and connection kits.
• Terminal shrouds.
• Terminal shield.
• Voltage sensing kit.
• Sealable cover.
This quick start is intended for personnel trained in
the installation and commissioning of this product.
For further details refer to the product instruction
manual available on the hager website.
• This product must always be installed and
commissioned by qualifi ed and approved
personnel.
• Maintenance and servicing operations should be
performed by trained and authorised personnel.
• Do not handle any control or power cables
connected to the product when voltage may be,
or may become present on the product, directly
through the mains or indirectly through external
circuits.
• Always use an appropriate voltage detection
device to confi rm the absence of voltage.
• Ensure that no metal objects are allowed to fall
in the cabinet (risk of electrical arcing).
Failure to observe good enginering practises as
well as to follow these safety instructions may
expose the user and others to serious injury or
death.
Installation and commissioning
Clip
for storage
of the
emergency
handle
z
Motorised changeover switch
125A - 630A
Risk of electrocution, burns or injury to
persons and/or damage to equipment.
Risk of damaging the device.
In case the product is dropped or
damaged in any way it is recommended
to replace the complete product
.
HIC4xxG

2. Power terminal connections
Use terminal lugs, rigid or fl exible busbars.
2 6LE001123A.e
Orientation
Recommended OK
OK NO
M
J1
Fix. 195
Fix. 180
==
T
U
21
C
Ø7
Ø9
Fix. 180
Fix. 195
Dimensions in mm
125A 160A 200A 250A 315A 400A 500A 630A
Minimum Cu
cable section
at Ith
(mm
2
) 35 50 95 120 185 2 x 95 2 x 120
Minimum Cu
busbar section
at Ith
(mm
2
) - 2 x 30 x 5 2 x 40 x 5
Maximum Cu
cable section
(mm
2
) 50 95 120 150 240 2 x 185 2 x 300
Maximum Cu
busbar width
(mm) 25 32 50
Type of screw
M8 M10 M12
Recommended
tightening
torque
(N.m) 8,3 20 40
Maximum
tightening
torque
(N.m) 13 26 45
125A 160A 200A 250A 315A 400A 500A 630A
4P
J1 34 35 34
M150 210 270
T36 50 65
C244 320
U20 25 35 32 45
W9 11 13
CA 10 15 20
CA
W
U
1. Installation
Ensure that the product is installed
on a flat rigid surface.
4.
3.
Door cut-out for front panel
3. CONTROL/COMMAND terminals
Ensure that the product is in Manual Mode.

5. Check
In manual mode,
check the wiring.
If OK power up
the product
LED Green =
“Power”: ON
LED Red =
“Manuel/Defaut”: ON
3 6LE001123A.e
1
Preferred source
2
Alternate source
& Position 0 order
é Position 1 order
" Position 2 order
' Zero position priority order
( Remote Control Enable (Priority over Auto)
§ Product Available output (Motor)
è Position II aux contact
! Position I aux contact
ç Position 0 aux contact
a O/P to HZI910 remote display
z Product Available output (ATS)
e I/P Inhibition of the ATS controls
r I/P Manual retransfer
t S2 Stability Time Bypass: 2AT
y Priority to TEST ON LOAD: TON
u TEST OFF LOAD Signal: TOF
i TEST ON LOAD Signal: TON
o Not used
p Contact “Start/Stop Genset”: if S1
is not available the NC contact le
contact (71-72) is close
q Contact “Start/Stop Genset”: if S1
is not available the NO contact le
contact (71-74) is open
s Voltage Sensing Inputs
d Power Supply Inputs
Example: control wiring for a 400VAC application having a 3 phase and neutral supply
4. Power supply, sensing and control wiring
Use cables with 1,5 to 2,5 mm
2
section. Screw M3 Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm
Recommanded to use
the voltage sensing kit
ATS Power Supply input II
Power Supply II - L
Power Supply II - N
208-277 VAC ±20%:
50/60 Hz
ATS Voltage Sensing input
Source supply II
S II - Phase 1
S II - Phase 2
S II - Phase 3
600 VAC (ph-ph) max
S II - Neutral
332 VAC (ph-n) max
ATS Module Control Inputs
(fi xed)
Contact
Genset Start/Stop
(product available)
Signal
ATS Power Supply input I
Power Supply II - L
Power Supply II - N
208-277 VAC ±20%:
50/60 Hz
ATS Voltage Sensing input
Source supply II
S I - Phase 1
S I - Phase 2
S I - Phase 3
600 VAC (ph-ph) max
S I - Neutral
332 VAC (ph-n) max
ATS Module Control Inputs
(fi xed)
ATS Module Output Contact
(product available)
Remote interface
RJ45 - to HZI910
2
10 1034
312 313 314 315 316 317 63A 64A 24 14 04 13
RJ 10 101210510641 41341 4541641764 63BB
72201 71202 20 20620 54203 210209208207 74
1
F1
F2
L1 L2 L3 N
L1 L2 L3 N
HZI910
Produktspecifikationer
Varumärke: | Hager |
Kategori: | strömbrytare |
Modell: | HIC440G |
Behöver du hjälp?
Om du behöver hjälp med Hager HIC440G ställ en fråga nedan och andra användare kommer att svara dig
strömbrytare Hager Manualer
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
Hager Manualer
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025
17 Juni 2025