Läs gratis den bruksanvisning för Haws 9001 (6 sidor) i kategorin ej kategoriserat. Guiden har ansetts hjälpsam av 2 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 1.5 recensioner. Har du en fråga om Haws 9001 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/6
10/17 9001 Alarm Series Page 1 of 6
No. 2080202(31)
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
Model 9001, 9001.5 Alarm
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
LIMITED WARRANTY
HAWS warrants that this specific product is guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under this
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods,
or part thereof, which shall appear to the Company upon inspection to be of defective
material or not of first class workmanship, provided that claim is made in writing to Haws
within a reasonable period after receipt of the product. Where claims for defects are made,
the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS
will not be liable for the cost of repairs, alterations or replacements, or for any expense
connected therewith made by the owner or his agents, except upon written authority from
HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective
materials or poor workmanship, except for replacements, as provided above. Buyer agrees
that Haws has made no other warranties either expressed or implied in addition to those
above stated, except that of title with respect to any of the products or equipment sold
hereunder and that HAWS shall not be liable for general, special, or consequential damages
claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. The units also must be used for the
purpose for which they were intended. This product is intended to supplement first-aid
treatment. Due to widely varying conditions, Haws cannot guarantee that the use of this
emergency equipment will prevent serious injury or the aggravation of existing or prior
injuries
.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED OR
GIVEN BY HAWS.
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
MODEL PLEASE CALL:
TECHNICAL SUPPORT: 1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
10/17 9001 Alarm Series Page 2 of 6
RECOMMENDED TOOLS: Pipe joint sealant, screwdriver, pipe wrench, 14 AWG wire,
1/2"conduit and basic electricians’ tools for power connection.
LOCATION OF UNIT: The Model 9001 Alarm Series may be mounted directly to the upper
standpipe of a safety shower or wall mounted next to a shower or eyewash. The alarm should
be clearly visible from several directions.
ELECTRICAL SUPPLY:
Model 9001 & 9001.5 120 VAC 50/60 HZ.
14 watts average power consumption. WARNING: Power shall be supplied by a dedicated
circuit through a 10 AMP maximum breaker or fuse and should not supply power to any other
devices. NOT FOR USE IN CLASSIFIED AREAS.
WATER SUPPLY:
Model 9001 2.4 gpm minimum required to activate flow switch.
Model 9001.5 1.5 gpm minimum required to activate flow switch.
Mount flow switch in supply line with flow in horizontal direction and switch stem extending
vertically from tee. Mount switch with at least 6” of straight pipe on both sides to minimize
turbulence in switch.
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1. Alarm horn and light do not
operate.
1. a. Check incoming circuit for power and power
from flow switch.
b. Check that the direction of water flow
corresponds to the arrow on the flow switch
body.
c. Check that the switch located on the junction
box is in the onposition.
d.
Check for continuity through the switch.
e.
Check all electrical connections.
f.
Check that water flow is sufficient.
g. Faulty flow switch. Replace entire switch
assembly.
2. Horn sounds but light does not
flash.
2. a. Check wiring connections.
b.
Replace flashing light.
3. Light flashes but horn does not
sound.
3.
a. Check wiring connections.
b. Make sure the alarm silencing switch is in
the “on” position.
4.
Alarm stays on.
4.
a.
Check wiring connections.
b. Disconnect flow switch wires and test for
continuity.