Läs gratis den bruksanvisning för Honeywell Fire-Lite BG-12L (2 sidor) i kategorin Växla. Guiden har ansetts hjälpsam av 20 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 10.5 recensioner. Har du en fråga om Honeywell Fire-Lite BG-12L eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/2

BG-12L Manual Pull Station
Patented, U.S. Patent No. Des. 428,351; 6,380,846; Other Patents Pending
Document 50964 I56-2263-004
Description
The BG-12L pull station is a non-coded, dual-action manual pull station with a key-lock
reset feature. It provides Fire•Lite control panels with one normally open (N/O) alarm initi-
ating input. The BG-12L meets the ADAAG controls and operating mechanisms guidelines
(section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate
the pull station. Operating instructions are molded into the pull station handle along with
Braille text. Molded Terminal numbers are also present.
Ratings
Switch contact (N/O) is gold plated for reliability and rated at 0.25 A at 30 volts (AC or
DC).
Installation
The BG-12L pull station can be surface mounted to an SB-10 or SB-I/O surface backbox
or semi-ush mounted on a standard single-gang, double-gang or 4 (10.16 cm) square ″
electrical box. The optional BG-TR trim ring can be used if the BG-12L is to be semi-ush
mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word
‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull sta-
tion is reset.
The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O)
switch which closes upon activation of the pull station.
Resetting the Pull Station
1. Insert the key into the lock and rotate 1/4 turn counterclockwise.
2. Open the door until the handle returns to normal.
3. Close and lock the door.
Note: Closing the door automatically resets the switch to the ‘Normal’ position. Opening
the door will not activate or deactivate the alarm switch.
STRIP GAUGE
1 2 3 4
IDC –
FROM
FACP + TO NEXT
DEVICE
– IDC
+
WARNING: DO NOT LOOP WIRING
UNDER ANY TERMINALS. BREAK WIRE
RUN MAINTAIN IDC SUPERVISION.TO
P0205-00
Wiring
CAUTION! Do not detach the door of the pull station during installation. The door of
the pull station cannot be reattached to the backplate after the backplate has already been
installed onto an electrical box.
CAUTION!
Install the Fire•Lite BG-12L pull station in accordance with these instructions,
applicable NFPA standards, national and local Fire and Electrical codes and the requirements
of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be con-
ducted in accordance with the appropriate NFPA standards. Failure to follow these directions
may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for
devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear oor space only allows forward approach to an object, the
maximum forward reach height allowed is 48 inches (121.92 cm). If the clear oor space
allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
54 inches (137.16 cm).
BG-12L
Manual Pull Station
WARNING! Do not loop wiring under any
terminals. Break wire run to
maintain IDC supervision.
Document 50964 I56-2263-004
P0194-01
Produktspecifikationer
| Varumärke: | Honeywell |
| Kategori: | Växla |
| Modell: | Fire-Lite BG-12L |
Behöver du hjälp?
Om du behöver hjälp med Honeywell Fire-Lite BG-12L ställ en fråga nedan och andra användare kommer att svara dig
Växla Honeywell Manualer
21 September 2024
21 September 2024
31 Augusti 2024
24 Augusti 2024
24 Augusti 2024
20 Augusti 2024
19 Augusti 2024
18 Augusti 2024
17 Augusti 2024
15 Augusti 2024
Växla Manualer
- Leviton
- Audiovox
- Basetech
- Legrand
- Mercusys
- Grasslin
- Inverto
- Tork
- Atlantis Land
- Equip
- Ebode
- Smart-AVI
- Rule
- Pizzato Elettrica
- Gefen
Nyaste Växla Manualer
9 April 2025
9 April 2025
7 April 2025
5 April 2025
5 April 2025
5 April 2025
5 April 2025
3 April 2025
3 April 2025
2 April 2025