Qubino Flush Heat & Cool Bruksanvisning
Läs gratis den bruksanvisning för Qubino Flush Heat & Cool (2 sidor) i kategorin Termostat. Guiden har ansetts hjälpsam av 25 personer och har ett genomsnittsbetyg på 3.6 stjärnor baserat på 13 recensioner. Har du en fråga om Qubino Flush Heat & Cool eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
                        Sida 1/2
                    
                    
                    
Qubino 
The and  INNOVATIVE  SMALLEST                                                                                       
Flush Heat  Cool Thermostat & 
 ORDERING CODE 
Z-WAVE FREQUENCY 
ZMNHK  D1
868,4 MHz 
ZMNHK  D2
921,4 MHz 
ZMNHK  D3
908,4 MHz 
ZMNHK  D4
869,0 MHz 
ZMNHK  D5
916,0 MHz 
ZMNHKD8 
865,2 MHz 
This  Z-Wave  module  is  used  to  regulate  temperature  in 
heating and cooling mode. Module can be controlled either 
through Z-Wave network or through the wall switch. 
The  module  is  designed  to  be  mounted  inside  a  ush “fl
mounting   and is hidden behind a traditional wall switch. box”
Module measures power consumption of connected device. 
It is designed to act as repeater in order to improve range 
and stability of Z-wave network.                         
Supported switches 
Module supports   switches (push button) and mono-stable
bi-stable switches. The module is factory set to operate 
with bi-stable switches.  
Installation 
  To prevent electrical shock and/or equipment damage, 
disconnect electrical power at the main fuse or circuit 
breaker before installation or any servicing.  
  Make sure, that no voltage is present in the installation.  
  Prevent the disconnecting device from being switched on 
accidentally. 
  Connect the module according to electrical diagram.  
  Locate  the  antenna  far  from  metal  elements  (as  far  as 
possible).  
  Do not shorten the antenna. 
Danger of electrocution!  
  Module  installation  requires  a  great  degree  of  skill  and 
may  be  performed  only  by  a  qualified  and  licensed 
electrician. 
  Even  when  the  module  is  turned  off,  voltage  may  be 
present on its terminals.  
Note! 
Do  not  connect  the  module  to  loads  exceeding 
recommended  values.  Connect  the  module  only  in 
accordance  to  the  below  diagrams.  Improper  connections 
may be dangerous. 
Electrical installation must be protected by directly 
associated over current protection fuse 4A, gG or Time 
lag T, rated breaking capacity 1500A (ESKA 522.723) 
must be used according to wiring diagram to achieve 
appropriate overload protection of the module. The fuse 
must be installed in fuse holder: Adels contact 503 Si / 1DS 
Package contents: 
  Flush  Thermostat + Temperature sensor Heat & Cool 
Electrical diagram 230VAC 
Notes for the diagram: 
N 
Neutral lead 
L 
Live lead 
Q1 
Output for Heating valve 
Q2 
Output for Cooling valve 
I2 
Input for switch /push button or sensor* 
I1 
Input for switch /push button or sensor* 
TS 
Terminal for digital temperature sensor (only for 
Flush Heat & Cool thermostat module compatible 
digital temperature sensor). 
*For details please check parameters 11 and 12 
Electrical diagram 24VDC 
Notes for the diagram: 
N 
+ VDC 
L 
- VDC 
Q1 
Output for Heating valve 
Q2 
Output for Cooling valve 
I2 
Input for switch /push button or sensor* 
I1 
Input for switch /push button or sensor* 
TS 
Terminal for digital temperature sensor (only for 
Flush Heat & Cool thermostat module compatible 
digital temperature sensor). 
*For details please check parameters 11 and 12 
WARNING: Service button S   when must NOT be used
module is connected to 110-230V power supply. 
Durability  of  the  device  depends  on  applied  load.  For 
resistive load (light bulbs, etc.) and 4A current consumption 
of  each individual  electrical  device,  the durability  exceeds 
70.000 switches of each individual electrical device. 
Module Inclusion (Adding to Z-wave network) 
  Connect module to power supply (with  
temperature sensor connected), 
  auto-inclusion  (works  for  about  5  seconds  after 
connected to power supply) or 
  press  push  button  I1  three  times  within  3s  (3  times 
change switch state within 3 seconds) or 
  press  service  button    (only  applicable  for  24  V  SELV S
supply voltage) for more than 2 second. 
NOTE1:  For  auto-inclusion  procedure,  first  set  main 
controller into inclusion  mode and then connect module to 
power supply. 
NOTE2:  When  connecting  temperature  sensor  to  module 
that  has  already  been  included,  you  have  to  exclude 
module  first.  Switch  off  power supply,  connect the  sensor 
and re-include the module  .
Module  Exclusion/Reset  (Removing  from  Z-
Wave network) 
  Connect module to power supply  
  bring  module  within  maximum  1  meter  (3  feet)  of  the 
main controller, 
  enable add/remove mode on main controller, 
  press push button  five times within 3s (5 times change I1 
switch  state  within  3  seconds)  in  the  first  60  seconds 
after the module is connected to the power supply   or
  press  service  button    (only  applicable  for  24  V  SELV S
supply voltage)  for more than 6 second. 
By  this  function  all  parameters  of  the  module  are  set  to 
default values and own ID is deleted. 
If push button I1 is pressed three times within 3s (or service 
button S is pressed more than 2 and less than 6 seconds) 
module  is  excluded,  but  configuration  parameters  are  not 
set to default values.  
NOTE:  If  the  module  is  included  with  parameters  100  or 
101 with value different to default and module reset is done, 
wait at least 30s before next inclusion. 
Association 
Association enables Flush  thermostat module Heat & Cool 
to transfer commands inside Z-Wave network directly 
(without main controller) to other Z-Wave modules. 
Associated Groups:  
Group 1: Lifeline group (reserved for communication with 
the main controller), 1 node allowed. 
Group 2: basic on/off (triggered at change of the output Q1 
or Q2 state and reflecting its state) up to 16 nodes. 
Group 3: SENSOR_MULTILEVEL_GET (triggered once per 
minute if parameter 121 is not 0) up to 16 nodes. 
Group 4: basic on/off (triggered by Too high temperature 
limit, it send  , triggered by To Low temperature, it send 0x00
0xFF) up to 16 nodes. 
Group 5: THERMOSTAT_SETPOINT_G  (triggered once ET
per minute if parameter 121 is not 0) up to 16 nodes. 
Group 6: basic on/off (trigged by change of I1 if window 
sensor functionality is selected by parameter no. 11) up to 
16 nodes. 
Group 7: basic on/off (trigged by change of I2 if condense 
sensor functionality is selected by parameter no. 12) up to 
16 nodes. 
Group 9: sensor multilevel report (trigged by change of 
temperature) up to 16 nodes. 
Configuration parameters 
Parameter no. 1   Input I1 switch type –
Available config. parameters (data type is 1 Byte DEC): 
  default value 1 
  - mono-stable switch type (push button) 0 
  -  -stable switch type  1  bi
Parameter no. 2   Input I2 switch type –
See parameter 1 (valid for I2 instead of I1) 
Parameter no. 4   Input 1 contact type –
Available config. parameters (data type is 1 Byte DEC): 
  default value 0 
  - NO (normally open) input type 0 
  - NC (normally close) input type 1 
NOTE: This parameter has influence only when parameter 
no. 11 is set to  the value  “2”.  After  setting  this parameter, 
switch the  window  sensor once,  so that  the module could 
determine the input state. 
Parameter no. 5   Input 2 contact type –
See parameter 4 (valid for I2 instead of I1) 
NOTE: This parameter has influence only when parameter 
no.  12  is  set  to  the  value  “2000”.  After  setting  this 
parameter,  switch  the  condense  sensor  once,  so  that  the 
module could determine the input state. 
Parameter no. 10 - Activate / deactivate functions ALL 
ON/ALL OFF 
Available config. parameters (data type is 2 Byte DEC): 
  default value 255 
  - ALL ON active, ALL OFF active. 255 
  - ALL ON is not active ALL OFF is not active 0 
  - ALL ON is not active ALL OFF active 1 
  - ALL ON active ALL OFF is not active 2 
Flush  thermostat module responds to Heat & Cool 
commands ALL ON / ALL OFF that may be sent by the 
main controller or by other controller belonging to the 
system.  
Parameter no. 11- I1 Functionality selection 
Available config. parameters (data type is 2 Byte DEC): 
  default value 1 
     input  I1  does  influence  on the  Heat  & Cool 32767 – n’t
process 
  - input I1 changes the mode of the thermostat between 1 
Off and Auto. In this case function on window sensor is 
disabled 
  -  input  I1  influences  on  cooling  and  heating  valves 2  
according  to  status  of  window    sensor.  In  this  case 
function of Off and Auto selection by I1 is disabled. 
NOTE:  If  "Window  Sensor"  selected  (value  set  to  "2"), 
parameter  100  (enable/disable  endpoint)  must  be  set  to 
non-zero value and module re-included! 
Parameter no. 12   I2 Functionality selection –
Available config. parameters (data type is 2 Byte DEC): 
  default value   32767
   - input I2  does not influence on the  Heat &  Cool 32767
process 
  From  0  to  990  -  Temperature  set  point  from  0.0  °C  to 
99.0  °C.  When  I2  is  pressed,  it  automatically  set  Heat 
and  Cool  temperature  setpoint according  to  value s 
defined here. In this case function of condense sensor is 
disabled  
  From 1001 to 1150 - Temperature set point from -0.1  °C 
to  - .  When  I2  is  pressed,  it  automatically  set 15.0  °C
temperature setpoint according to value defined here. In 
this case function of condense sensor is disabled 
  - Input I2 influences on the cooling valve according 2000 
to  status  of  condense  sensor,  In  this  case  function  of 
setpoint selection with I2 is disabled 
NOTE: If "Condense Sensor" selected (value set to "2000"), 
parameter  101  (enable/disable  endpoint)  must  be  set  to 
non-zero value and module re-included! 
Parameter no. 40   Power reporting in Watts on power –
change 
Set value means percentage, set value from 0 - 100=0% - 
100%. Available configuration parameters (data type is 1 
Byte DEC):  
  default value 0 
  - reporting disabled 0 
  1-100 = 1%-100% Reporting enabled. Power report is 
send (push) only when actual power in Watts in real time 
changes for more than set percentage comparing to 
previous actual power in Watts, step is 1%. 
NOTE  If power changed is less than 1W, the report is not :
send (pushed), independent of percentage set. 
Parameter no. 42   Power reporting in Watts by time –
interval 
Set value means time interval (0    ) in seconds, –32767
when power report is send. Available config. parameters 
(data type is 2 Byte DEC): 
  default value 0 (power report is disabled) 
  - reporting disabled 0 
  -    =  1  second  -    seconds.  Reporting 1  32767 32767
enabled.  Power  report  is send  with  time interval  set by 
entered value.  
Parameter no. 43   Hysteresis Heating  –   On
This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
heating on. Available configuration parameters (data type is 
2 Byte DEC):  
  default value 1010 (-1.0   °C)
  -  25,5   0  255  =  0,0°C to  °C  
  - 1 =  -  - 25,5   1001  255   0,1°C to  °C
Parameter no. 44 - Hysteresis Heating Off    
This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
heating off. Available configuration parameters (data type is 
2 Byte DEC):  
   default value 2 (+0.2 °C)
  -  25,5   0  255  =  0,0°C to  °C  
  - 1 =  -  - 25,5   1001  255   0,1°C to  °C
Parameter no. 45   Hysteresis Cooling  – On
This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
cooling on. Available configuration parameters (data type is 
2 Byte DEC):  
   default value 5 (+0.5 °C)
  -  25,5   0  255  =  0,0°C to  °C  
  - 1 =  -  - 25,5   1001  255   0,1°C to  °C
Parameter no. 46   Hysteresis Cooling Off –
This parameter defines temperature difference between 
measured temperature and set-point temperature to turn 
cooling off. Available configuration parameters (data type is 
2 Byte DEC):  
   default value 1002 (-  0.2 °C)
  -  25,5   0  255  =  0,0°C to  °C  
  - 1 =  -  - 25,5   1001  255   0,1°C to  °C
Parameter no. 47   –Antifreeze 
Set value means at which temperature the device will be 
turned on even if the thermostat was manually set to off. 
Available config. parameters (data type is 2 Byte DEC):  
   default value 50 (5,0 °C)
  -   0  127  =  0,0°C  to 12,7 °C  
  - 1127  =  -  -   1001  0,1°C to  12,7 °C
  - Antifreeze functionality disabled 255 
NOTE: Antifreeze is activated only in heating mode. It uses 
a hysteresis determined   parameters no. 43 and 44. in
Parameter no. 60   Too low temperature limit –
Available config. parameters (data type is 2 Byte DEC): 
  default value   (too low temperature limit is 5  50 .0°C)
  -  -   1  1000 = 0.1°C  100.0°C, step is 0.1°C. 
   1150 = -  -  1001 – 0.1°C to  15.0°C
NOTE: Too  l  temperature limit is  used with Association ow
Group 4. 
Parameter no. 61   Too high temperature limit –
Available config. parameters (data type is 2 Byte DEC): 
  d  efault value 700 (too high temperature limit is 70.0°C)
  -  - 1   1000  =  0.1°C   100.0°C,  step  is  0.1°C.  Too  high 
temperature limit is used with Association Group 4. 
Parameter no. 64   Output Switch selection   –Q1
Set value means the type of the device that is connected to 
the   output. The device type can be normally open (NO) Q1
or normally close (NC).  
Available config. parameters (data type is 1 Byte DEC): 
  default value 0  
  - When system is turned off the output is 0 V. 0 
  - When system is turned off the output is 230 V. 1 
Parameter no. 65   Output Switch selection   –Q2
Set value means the type of the device that is connected to 
the   output. The device type can be normally open (NO) Q2
or normally close (NC).  
Available config. parameters (data type is 1 Byte DEC): 
  default value 0  
  - When system is turned off the output is 0 V. 0 
  - When system is turned off the output is 230 V. 1 
Parameter no. 70   Input 1 status on delay  –
Available config. parameters (data type is 2 Byte DEC): 
  default value 0 
  - 32000 seconds 1 
If the value of parameter is different to 0, means that the 
Influence of this input to heating or cooling will react after 
inserted time. This parameter has influence only when the 
S 
Service  button  (used  to  add 
or  remove  module  from  the 
Z-Wave  network  in  case  of 
24 V SELV power supply). 
Produktspecifikationer
| Varumärke: | Qubino | 
| Kategori: | Termostat | 
| Modell: | Flush Heat & Cool | 
Behöver du hjälp?
Om du behöver hjälp med Qubino Flush Heat & Cool ställ en fråga nedan och andra användare kommer att svara dig
Termostat Qubino Manualer
                        
                         16 September 2024
                        
                    
                                                            
                        
                         16 September 2024
                        
                    
                                                            Termostat Manualer
- Intertechno
- Bulex
- Bosch
- H-Tronic
- Trotec
- Schneider
- HomeMatic
- Magnum
- ORNO
- Fibaro
- Techno Line
- Coati
- ACV
- Grasslin
- Siemens
Nyaste Termostat Manualer
                        
                         13 Oktober 2025
                        
                    
                                                            
                        
                         12 Oktober 2025
                        
                    
                                                            
                        
                         12 Oktober 2025
                        
                    
                                                            
                        
                         5 Oktober 2025
                        
                    
                                                            
                        
                         2 Oktober 2025
                        
                    
                                                            
                        
                         2 Oktober 2025
                        
                    
                                                            
                        
                         29 September 2025
                        
                    
                                                            
                        
                         28 September 2025
                        
                    
                                                            
                        
                         28 September 2025
                        
                    
                                                            
                        
                         28 September 2025