Sauermann KH 50 Bruksanvisning
Läs gratis den bruksanvisning för Sauermann KH 50 (2 sidor) i kategorin mätning. Guiden har ansetts hjälpsam av 10 personer och har ett genomsnittsbetyg på 4.6 stjärnor baserat på 5.5 recensioner. Har du en fråga om Sauermann KH 50 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/2

Conguration and data viewing
software freely downloadable
KT 50 - KH 50
KISTOCK Data logger
or HVAC - Temperature, Humidity
Conguration and data processing
software available as option
16,000 measurement points
Measure up to 2 parameters
• 2 congurable setpoint alarms
• 1 line LCD display
• Fast data download (1,000 values/second)
• IP65 (KT 50) and IP20 (KH 50) housing
DATA SHEET
KT 50 KH 50
Units displayed °C, °F °C, °F, %RH
Resolution 0.1 °C, 0.1 °F 0.1 °C, 0.1 °F, 0.1 %RH
External inputs Micro-USB connector
Internal sensor Temperature Humidity, temperature
Setpoints alarm 2 setpoint alarms on each channel
Frequency of measurement From 1 minute to 24 hours
Operating temperature
(1)
From -40 to +70 °C
-40 to +158 °F
From -20 to +70 °C
-4 to +158 °F
Storage temperature From -20 to +50 °C / -4 to +122 °F
Battery life 500 days
(2)
365 days
(2)
Standards
2014/30/EU EMC; 2014/35/EU Low Voltage;
2011/65/EU RoHS II; 2012/19/EU WEEE;
FCC part 15; UL 61010
General features
Magnetic
mounting
(1)
The screen can be hard to read, and its display speed often slows down at temperatures lower than 0 °C / 32 °F. This has no effect on the accuracy of measurements.
(2)
Non-contractual value. Based on 1 measurement each 15 minutes at 25 °C / 77 °F. A correct operation of the device and the storage conditions must be respected.
°C
°F
Housing
Dimensions 61.3 x 40 x 21.9 mm / 2
13
/
32
’’ x 1
9
/
16
’’ x
7
/
8
’’
Weight 40 g / 1.42 oz
Display
1 line LCD screen
Screen dimensions: 26.5 x 22.5 mm / 1
3
/
64
‘‘ x
57
/
64
’’
Control 1 OK key
Material
Compatible with food industry environment
ABS housing. Caps made of Elastomer
Protection rating IP65: KT 50. IP20: KH 50
PC communication 1 micro USB input
Battery power supply 2 x CR2032 (lithium 3 V)
Environmental
conditions of use
Hygrometry: in non-condensing condition
Maximum altitude: 2000 m / 2188 yd
Air and neutral gases
KT 50 TemperatureInternal sensor
Type of sensor NTC
Measuring range From -40 to +70 °C / -40 to +158 °F
Accuracy*
±0.4 °C from -20 to 70 °C ±0.8°C below -20 °C
±0.8 °F from -4 to 158 °F ±1.5 °F below -4 °F
Technical specications
* All accuracies indicated in this document were stated in laboratory conditions and can be guaranteed for
measurements carried out in the same conditions, or carried out with calibration compensation.
** Factory calibration uncertainty: ±0.88 %RH. Temperature dependence: ±0.04 x (T-20) %HR if T<15 °C or T>
25 °C / ±0.04 x [((T°F - 32) x 5/9) -20] %RH (if T<59°F or T>77°F).
KH 50 Hygrometry TemperatureThermo-hygrometer
Type of sensor Capacitive NTC
Measuring range From 0 to 100% RH
From -20 to +70 °C
-4 to 158 °F
Accuracy*
±2.5 %RH (from +15
to +25°C / +59 to
+77 °F from 5 to 95
%RH)**
±0.4 °C from 0 to +50 °C
±0.8 °F from +32 to +122 °F
±0.8 °C below 0 °C or
above +50 °C
±1.5 °F below 32 °F or
above 122 °F
EN 12830
KT 50
Produktspecifikationer
| Varumärke: | Sauermann |
| Kategori: | mätning |
| Modell: | KH 50 |
Behöver du hjälp?
Om du behöver hjälp med Sauermann KH 50 ställ en fråga nedan och andra användare kommer att svara dig
mätning Sauermann Manualer
20 September 2025
20 September 2025
20 September 2025
20 September 2025
18 September 2025
2 September 2025
1 September 2025
31 Augusti 2025
31 Augusti 2025
28 Augusti 2025
mätning Manualer
- Emko
- Phoenix Contact
- Ideal
- PHABRIX
- Chauvin Arnoux
- Testboy
- Hager
- Senseca
- Blackmagic Design
- Sungrow
- Fluke
- Uni-T
- Danfoss
- Greisinger
- Ade
Nyaste mätning Manualer
21 Oktober 2025
18 Oktober 2025
13 Oktober 2025
11 Oktober 2025
8 Oktober 2025
8 Oktober 2025
8 Oktober 2025
7 Oktober 2025
7 Oktober 2025
7 Oktober 2025