Läs gratis den bruksanvisning för Schneider WDE002963 (75 sidor) i kategorin Termostat. Guiden har ansetts hjälpsam av 14 personer och har ett genomsnittsbetyg på 4.9 stjärnor baserat på 7.5 recensioner. Har du en fråga om Schneider WDE002963 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/75
KNX room temperature controller
Application 705C/0.1
© 2011 Schneider Electric
Application: Continuous-action controller with pushbutton interface, 4-fold 705C
Executable from mask version: 7.1
Number of addresses (max): 120 dynamic table handling Yes No
Number of assignments (max): 120 maximum length of table 120
Communication objects: 59
Pushbutton interface functions:
Function: Binary input / switching (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name DPT-ID Type Flag
0-3 Switching object X.1 PBI input X 1.001 1 bit C, T
4-7 Switching object X.2 PBI input X 1.001 1 bit C, T
8-11 Disable switching object X.1 PBI input X 1.001 1 bit C, W
12-15 Disable switching object X.2 PBI input X 1.001 1 bit C, W
Function: Binary input / dimming (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Switching PBI input X 1.001 1 bit C, T
4-7 dimming PBI input X 3.007 4 bit C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / blind/shutter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Short-time operation PBI input X 1.007 1 bit C, T
4-7 Long-time operation PBI input X 1.008 1 bit C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / dimming value transmitter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Value PBI input X 5.001 1 byte C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / light-scene extension (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Light-scene extension PBI input X 18.001 1 byte C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / brightness value transmitter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Brightness value PBI input X 9.004 2 bytes C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / temperature value transmitter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Temperature value PBI input X 9.001 2 bytes C, T
8-11 Disabling PBI input X 1.001 1 bit C, W