Läs gratis den bruksanvisning för Vemer SRG.4 (2 sidor) i kategorin Gasdetektor. Guiden har ansetts hjälpsam av 14 personer och har ett genomsnittsbetyg på 5.0 stjärnor baserat på 7 recensioner. Har du en fråga om Vemer SRG.4 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/2
ON
SRG.4
12
34
TEST
RESET
Mod.SRG.4
V3IS00460–010
159.5
50.5
58.0
50.5 50.5
C1
S1
A1C2
S2
A2
C3
S3
A3C4
S4
A4
12
3
4
SENSORS
+
1
2345678
91011121314151617181920
8A / 250V
8A / 250V
1
2
V
a
c
/
d
c
FaultAlarm
Power supply
Description
g
h
j
User manual
SRG.4 - CONTROL UNIT FOR GAS DETECTOR
Read all the instructions carefully
TheSRG.44isacontrolunitforthecreationofgasdetectionsystemsinareas
suchasboilerrooms,workshops,warehouses,laboratories,etc.Itisdesignedto
workwithprobessuchasCOSensor,CH4SensorandLPGSensor.Itoffersthe
possibilitytocontrolasolenoidvalveoranauxiliarydevice(siren,flasher,etc.)
usinganalarmrelaycontainedinside.ThealarmorfailureisdisplayedbyLED.
SAFETY WARNINGS
To ensure correct installation, you must comply with the following
indications:
1) The device must be installed by a competent person
2) The device must be installed in a panel where, after installation, the terminals
can no longer be accessed
3) In the electrical system up the line from the energy meter there must be a
device to protect against overloads
4) Connect the instrument following the diagrams shown in this sheet and in the
product marking
5) Before accessing the terminals, make sure the leads to connect to the
instrument are not electrically live
6) Do not power and connect the instrument if any part of it is damaged or
missing.
Codice Model Description
VE203600 SRG.4 Gasdetectorwith4connectingsensor
VE205100 CH4 SENSOR Methanedetectionsensor
VE206900 LPG SENSORLPG sensor
VE207700 CO SENSOR Carbonmonoxidesensor
TECHNICAL CHARACTERISTICS
Control unit SRG.4
•Powersupply:
−Voltage:12Vac/dc±10%
−Powerconsumptionwith1probe:~160mA
−Powerconsumptionwith4probes:~280mA
−Connection:terminalsof2.5mm
2
−Protection:fuse1A5x20mm
•Inputs:
−4inputsforCH4Sensor(methane),LPGSensor(LPG),COSensor(CO).
−Connectionofprobes:terminalsof2.5mm
2
per probe
−Max.connectionlength:50mforeachprobe
−Cross-sectionoftheleads:1.5mm
2
•Output:
−Alarm:relaywithexchangecontact8A/250VAC
−Failure:relaywithexchangecontact8A/250VAC
−Connection:terminalsof2.5mm
2
forrelayC-NC-NO
•Luminoussignals:1greenLED:powersupplied
1yellowLED:generalfailure
4yellowLED’s:failureforeachprobeline
4redLED’s:gasalarmforeachprobeline
•Reset/testbuttonforalarmresetandprobetestfunctions
•Degreeofprotection:IP20;IP40whencorrectlyinstalledinanelectricalpanel
•Ambienttemperature:0÷+50°C
•Humidity:90%R.H.withoutcondensation
•Productforassemblyon9-moduleDINrails
Sensors for SRG.4 control units
•Powersupply:fromthecontrolunitSRG.4
−Currentinput(at6.5V):40mA
−Connections:terminalsof2.5mm
2
forprobeC(common),S(signal),A(power6.5Vdc)
•Modelsandcalibration:
−Methanegas:CH4Sensor,(default)10%LIEofmethane
−LPG:LPGSensor,(default)12%LIEofisobutene
−Carbonmonoxide:COSensor,(default)200ppmofCO
•Container:inself-extinguishingplasticmaterial
•Fastenedtowallusingscrewsandplasticplugs
•Protection:IP30
•Ambienttemperature:0÷+50°C
•Humidity:90%R.H.withoutcondensation
INSTRUMENT DESCRIPTION
Ledpowersupply
Led signaling general failure
Reset/Testbutton
Led signaling failure probes
Led signaling gas alarm
Powersupplyterminals
g
Connection probes terminals
h
Protectionfuse1A
Set-upjumper
j
Terminalsforalarmoutputrelay
Terminalsforfailureoutputrelay
INSTALLATION
Do not use the device in excess of the limits set forth in the technical data. The installer is
responsible for correct, safe installation of the product. Use care during shipping, storage
and handling.
1)Protectionofthedevice.
Toensuretheproperdegreeofprotectionoftheunit,itisnecessarytoinstallthecontrol
unitinanelectricalpanelconstructedinaccordancewithcurrentstandardsforthe
workplace,andinsideofwhichthepowersupplysystemcanalsobehoused.Thecontrol
unitcanbeinstalledatthebottomofthepanelorinDINmodularpanels.
TheLPG,COandCH4Sensorsaredesignedtobewall-mounted(vertically),usingscrews
andplasticplugs.Toproceedwithinstallation,openthecontainerbyunscrewingthe
screwlocatedontheside.Makesurenottodamagethesensorandnottotouchthe
calibration devices.
2)Installationoftheproduct.
Thecorrectinstallationoftheprobeisessentialtoproperoperationofthesystem.
Therefore,itmustbeinstalled:
–Inareaswithcirculationofnaturalair;
–Inareasthatarenotsubjecttodustordirtthatmayrenderthesensorinoperative;
–Nearjetsofwater,intakegrilles,openings,etc.
–Atanadequatedistancefromusersofgassoastopreventthesystemfromintervening
improperlyduetofunctionalleakage.
Also,positioningdependsonthetypeofgastobedetected,specifically:
–CH4:Methanegas-attop,about20-30cmfromtheceiling
–LPG:LPG-atbottom,about20-30cmfromthefloor
–CO:carbonmonoxide–about1.5mfromthefloor
Fornewsystems,theprobemustbeinstalledaslateaspossible,sothattypical
constructionsiteactivitiesdonotdamagethedetector.
Attention: make sure you check operation at least once a year, and in any case
whenever there is an extended period of disuse or in the event of replacement.
Any tampering may compromise correct operation of the system.
3)Connectionsanduseoftheproduct.
Normalelectricalcablescanbeusedforconnections.Inanycase,wheninstallationis
inplacesthatarestronglyexposedtoelectromagneticdisturbances,itisadvisableto
useshieldedcables.Thedetectionsystemmustalwaysbeinoperation.Therefore,the
electricalpowersupplyofthedetectormustnotincludeswitchesorotherdevicesthat
mayaccidentallyshutitoff.Thepowersupplyofthecontrolunitmustcomplywiththe
requiredvaluesandthecurrentinputofanydeviceconnecttotheterminalsoftherelay
mustbelessthanorequaltothemaximumcapacityofthecontacts.Theaveragelifespan
oftheprobesis5yearsfromthedateofinstallation.Therefore,attheendofthattime
theywillneedtobereplaced.
Attention: in the case in which in every single terminal block of the control
unit missed the probes, there must be a resistence of 18KOhm 1/4 W 5%
between C ans S furnisced in the box.
OPERATION
Oncethedevicehasbeeninstalled,youwillneedtoselecttheoperatinglogicusing
jumperE1.Itcanbeeitherpositiveornegative.Thecontrolunitsignalsitsoperating
statusbymeansofLED’s.
A
Position A
Positive logic
Position B
Negative logic
B
A
B
E1
E1
E1
A
B
DependingonthelogicselectedusingjumperE1,inanormalsituation(noalarms),the
LED’sandtherelaywillbe:
–positivelogic:LEDon,relayenergized
–negativelogic:LEDoff,relayde-energized
Ifnegativeoperatinglogicisselected,thealarmrelaymaybecontrolledinpermanentor
impulsivemode,dependingonthepositionofjumperE2:
A
Position A
Alarm relay
Permanent control
Position B
Alarm relay
Impulsive control
B
A
B
E2
E2
E2
A
B
Dimensions
Connection diagram
Oncepoweredon,thecontrolunitperformsthefollowingphasesinsequence:
•Buzzertest(durationabout5seconds)whichcausessequentiallightingoftheLED’sand
abriefringingofthebuzzer.
•Pre-heatingoftheprobe(whichlastsabout1minute),duringwhichthedetection
systemisnotoperationalbecausethisallowstheprobestoreachthecorrectoperating
temperature.
•Operationaltest(whichlastsabout3minutes)duringwhichthepowersupplyLED
flasheswithafrequencyof2Hzandalltimesettingsareresettozerotomakeiteasierto
checktheprobes.PresstheReset/Testforaboutonesecondtointerrupttheoperational
testphaseandchecktheprobes.
•Gasalarmtest,whichoccursbyplacingthetestspraycanneartheprobeandreleasing
asmallamountofgas.Donotdirectthespraydirectlyontothesensoroftheprobe,
asitmaydamageitirreparably.Thecontrolunitwillsignalthealarminthefollowing
manner:
InterfacePositive logicNegative logic
Led for alarm (red)
of concerned probe
OffOn
AlarmbuzzerContinuous soundContinuous sound
AlarmrelayDe-energizedEnergized(permanentlyor
in impulsive mode)
PresstheReset/Testkeyforonesecondtosilencethealarm(ifthegasisnolonger
present)andendthetestphase.Torestartthetestphase,pressthecorrespondingbutton
for about 6 seconds.
•Probeanomalytest,whichistobesimulatedsimplybydisconnectingtheconcerned
probecableandcheckingthefollowingsignals:
InterfacePositive logicNegative logic
Led for failure (yellow)
of concerned probe
OffOn
AlarmbuzzerIntermittent soundIntermittent sound
FailurerelayDe-energizedEnergized
Oncethetesthasbeenmade,re-connecttheprobeandpresstheReset/Testbuttonto
restorethecontrolunittonormaloperation.
Normal operation
Duringnormaloperationofthecontrolunit,boththemonitoringforgasalarmand
theself-diagnosisforplantanomalies(probes)andsystemsanomalies(controlunit)are
active.Inthisphaseandwithnoalarmsorfailures,thecontrolunitstatusisasfollows:
InterfacePositive logicNegative logic
Led (green)forpowersupply
On On
Led for general failure(yellow)
On Off
Led for probe failure (4)(yellow)
OnOff
Led for general alarm and (red)
line failure (4)
OnOff
AlarmbuzzerNo soundNo sound
AlarmrelayDe-energizedEnergized
FailurerelayDe-energizedEnergized
Inpresenceofgasalarmorprobefailure,thecentralunitgoesintothesameconditions
describedintherelativestestphase.
REFERENCE STANDARDS
ConformitytotheEUdirectives
2006/95/EC(LowVoltage)
89/336/ECmodifiedby92/31/ECCand93/68/EEC(E.M.C.)
isdeclaredwithreferencetothefollowingharmonisedstandard:
EN 61779-1, EN 50270