Fantini Cosmi L02A Bruksanvisning
                    Fantini Cosmi
                    
                    Termostat
                    
                    L02A
                
                                
    Läs gratis den bruksanvisning för Fantini Cosmi L02A (1 sidor) i kategorin Termostat. Guiden har ansetts hjälpsam av 22 personer och har ett genomsnittsbetyg på 3.8 stjärnor baserat på 11.5 recensioner. Har du en fråga om Fantini Cosmi L02A eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
                        Sida 1/1
                    
                    
                    
To get access to the parameter configuration menu, press button   ■ +    for 5 seconds.
With button   ■
 or     select the parameter to be modified.
Press button   ■
 to display the value.
By keeping button   ■
 pressed, use button    to set the desired value.  or 
When button   ■
 is released, the newly programmed value is stored and the following parameter is displayed.
To exit from the setup, press button  ■
 or wait for 30 seconds.
PAR RANGE DESCRIPTION
SCL
1°C;
2°C;
°F
Readout scale (see table of input specifications)
Caution: upon changing the   value, it is then absolutely necessary to   the param-SCL reconfigure
eters relevant to the absolute and relative temperatures ( ,  ,  ,    etc..)SPL SPH 1SP 1HY
SPL
-50°...SPH Minimum limit for   setting1SP
SPH
SPL...150° Maximum limit for   setting.1SP
1SP
SPL... SPH Setpoint (value to be maintained in the room).
1CM
HY; PID Control mode.
With  =H  you select control with hysteresis: parameters  ,   are used.1CM Y1HY 1T0 1T1 and 
With  =PID you select a Proportional-Integral-Derivative control mode: parameters  ,  , 1CM 1PB 1IT
1DT 1AR 1CT,  ,   will be used
1CH
REF; HEA Refrigerating (REF) or Heating (HEA) control mode.
1CM=HY
1HY
0...19.9° OFF/ON thermostat di ferential.  With  =0 the output is always of   1HY ff. 
1T0
0...30min Minimum o f time.f
After output been turned f, it remains inactive minutes    1  has      of           for   1T0   regardless  of  the 
temperature value measured.
1T1
0...30min Minimum on time. ( ).the following parameter will be 1PF
After output 1 has   been turned on,      it remains active   for 1T1 minutes regardless of the temperature 
value measured.
1CM=PID
1PB
0...19.9° Proportional bandwidth.   
Temperature takes by changing  control    place      the 
ON   of the   the closer the time output: temperature 
to the   the less   of   setpoint, time activation. A small 
proportional band increases      the  promptness  of 
response of the   to   system temperature variations, 
but make it stable. A  tends  to      less      purely 
proportional stabilises temperature   control    the 
within proportional band but  the        does not  cancel 
the deviation from setpoint. 
With  =0 the output is always o1PB ff.
1IT
0...999s Integral action time.    
The   error   cancelled     an steady-state is by inserting
integral action. integral action time, determines    The       
the speed     the   with which steady-state temperature 
is achieved, but high ( low) may be     a   speed  1IT       the 
cause overshoot instability in of   and     the response. 
With  =0 the integral control is disabled.1IT
1DT
0...999s Derivative action time.   
Response         overshoot may be reduced
by inserting  
a     derivative Action. A         high derivative action (1DT
high) makes system very sensitive    the        to  small 
temperature variation causes instability  s  and    .  With 
1DT=0 the derivative control is disabled.
1AR
0...100% Reset of integral action time referred to 1PB
Decreasing reduces integral action zone, consequently the parameter   1AR  the   control     and   the 
overshoot (see figure on paragraph  ).1IT
1CT
1...255s Cycle time. 
It’s the        the    ON   changes. The    the    to    controlled period in which output time quicker system be
reacts  to      the  smaller the            order  to   temperature variations, cycle time must be, in obtain higher 
temperature stability and less sensitivity to load variations.
1PF
ON/OFF Output state in case of probe failure.
OAU
NON;
THR;
AL0;
AL1
AUX output operation.
NON : output disabled (always o f). (fthe next parameter will be ATM)
THR: output programmed for second thermostat control ( ).the next parameter will be 2SM
AL0: contacts open when an alarm condition occurs (the next parameter will be ATM).
AL1: contacts make when an alarm condition occurs (the next parameter will be ATM).
OAU=THR
2SM
ABS;
REL
Setpoint 2 mode.
Channel 2 set nt ma   e a solpoi y b b u (te  2SM=ABS), or a d fferenti ial relat e to setiv poi (nt 1  2SM=REL)
2SM=ABS
2SP
SPL...SPH Auxiliary output switchover temperature ( )the next parameter will be 2CH
2SM=REL
2DF
-19.9...19.9° Temperature di ferential relative to  The auxiliary output setpoint is equal to f1SP.  1SP 2DF+
ON/OFF refrigerating control 
( =H1CM Y,  =REF)1CH
ON/OFF heating control 
( =H1CM Y,  =HEA)1CH
1SP
1SP+1HY
T[°]
ON
OFF
1SP1SP-1HY
T[°]
ON
OFF
Time
T erutarepme
Process
temperature
Overshoot
S teady-st ate error
1PB
1SP
Time
T erutarepme
Process
temperature
Overshoot
1PB
1PBx1AR%
integral control
action area
1SP
Time
T erutarepme
Process
temperature
Overshoot
1PB
1SP
2SP
2SP+2HY
T[°]
ON
OFF
2SP2SP-2HY
T[°]
ON
OFF
ON/OFF control in refrigeration
( =ABS,  =REF)2SM 2CH
ON/OFF control in heating
( =ABS,  =HEA)2SM 2CH
1SP+2DF
1SP
2DF>0
1SP+2DF+2HY
T[°]
ON
OFF
1SP
1SP+2DF
2DF<0
1SP+2DF-2HY
T[°]
ON
OFF
ON/OFF control in refrigeration. Setpoint 2
relative to setpoint 1 ( =THR,  =REF)OAU 2CH
ON/OFF control in heating. Setpoint 2
relative to setpoint 1 ( =THR,  =HEA)OAU 2CH
Power supply
 12Vac/dc ±10%, 2W (L02AI-/L02CI-/L02DI-)
 110 - 230 ac±10%, 50/60Hz, 3W (L02AM-/L02CM-/L02DM-)V
Relay outputs
Inputs
see table of input specifications
Measurement range
see table of input specifications
Measurement accuracy
see table of input specifications
Operating conditions
-10 … +50°C; 15%...80% U.R.
CE (Reference Norms)
EN60730-1; EN60730-2-9;
EN55022 (Class B); EN50082-1
Front protection
IP55
OAU=THR
2CH
REF; HEA Refrigerating control (REF) or heating control mode (HEA) for the auxiliary output.
2HY
0...19.9° Di ferential of thermostat 2. With  =0 the auxiliary output always remains of2HY ff.
2T0
0...30min Minimum o f time.f
After output 2 has been turned of  f, it remains inactive for 2T0 minutes regardless of the temperature 
value measured.
2T1
0...30min Minimum on time.
After output 2 has been turned   on, it remains   active for 2T1   regardless of the minutes temperature 
value measured.
2PF
ON/OFF Auxiliary output state in case of probe failure.
ATM
NON;
ABS;
REL
Alarm threshold management.
NON  all temperat: ure alarms are inhibi (ted  the following parameter will be SB).
ABS: the values programmed  n iALA and   represent the real alarm thresholds.AHA
REL: the values programmed in ALR and AHR are alarm differentials referred to 1SP and 1SP+1HY.
ATM=ABS
ALA
-50°...AHA Low temperature alarm threshold.
AHA
ALA...150° High temperature alarm threshold.
ATM=REL
ALR
-12.0...0° Low temperature alarm di ferential. f
With  =0 the low temperature alarm is excludedALR
AHR
0...12.0° High temperature alarm di ferential. f
With  =0 the high temperature alarm is excludedAHR
ATD
0...120min Delay before alarm temperature warning.
SB
NO/YES Stand-by button enabling.
INP
0mA/4mA,
T1/T2
ST1/SN4
Sensor input selection (see table of input specifications).
WARNING: “0mA/4mA”, and “T2” are not available
In the models L02A--/L02D-- only.
RLO
-19.9...RHI Minimum range value (function not available)
RLO takes the minimum value measured by the transmitter (i.e. the value matching 0V, 0/4mA).
RHI
RLO...99.9 Maximum range value (function not available)
RHI takes the maximum value measured by the transmitter (i.e. the value matching 1V, 20mA)
OS1
-12.5...12.5°  T1 offset.Probe
TLD
1...30min Delay for minimum temperature (TLO) and maximum temperature (THI) logging.
SIM
0...100 Display slowdown
ADR
1...255 address for PC communication (function not available)
1SP
1SP-ALR
T[°]
ON
OFF
1SP+1HY+AHR
1SP1SP-1HY -ALR
1SP+AHR
T[°]
ON
OFF
Temperature alarm with relative thresholds, 
refrigerating control (ATM 1CH=REL,  =REF)
Temperature alarm with relative thresholds, 
heating control (ATM 1CH=REL,  =HEA).
DISPLAY
During normal operation, the display shows either the temperature measured or one of the following indications:
OFF
Controller in stand-by
TUN/xx.x
Controller in autotuning
OR
Probe T1 overrange or failure 
E1
In tuning: timeout1 error
HI
Room high temperature alarm
E2
In tuning: timeout2 error
LO
Room low temperature alarm 
E3
In tuning: overrange error
MENU INFO
The information available in this menu is:
THI
Maximum temperature recorded
LOC
Keypad state lock
TLO
Minimum temperature recorded
Access to menu and information displayed.
Press and immediately release button  ■
. 
With button  ■
 or    select the data to be displayed.
Press button  ■
 to display value.
To exit from the menu, press button  ■
 or wait for 10 seconds.
Reset of THI, TLO recordings
With button  ■
 or   select the data to be reset.
Display the value with button  ■
.
While keeping button  ■
 pressed, use button  . 
CHANNEL 1 SETPOINT (display and modification of desired temperature value) 
Press and release button  ■
 : the  ED L L bli1  nks, the d spla  shoi y ws 1 P for 1 second and then the set nt assocS poi iated value.
Press buttons  ■
 or   to set the desire valud  e (adjustment  s i within the minimum SPL and maximum SPH limit .)
To store the new value press button  ■
, or wait for 10 seconds.
To go back to normal mode without saving the new value, press  ■
. 
CHANNEL 2 SETPOINT
With auxiliary output ( the     set as thermostat control  ■ =THR), itOAU  ’s   to     2   the normal possible modify setpoint during operation 
of the controller.
Press and  release button  ■
: LED L2 blinks, display shows 2S if setpoint is absolute the       the      P for  1 second      2    an   threshold 
( =ABS), alternatively display shows2SM     the      2DF, if setpoint is relative setpoint ( =REL), value      2   a  threshold   to   1  2SM  then  the 
associated to the parameter appears.
Press buttons  ■
 or   to set the desired value.
To store the new value press button  ■
 or wait for 10 seconds.
To go back to normal mode without saving the new value, press  ■
.
STAND-BY
Button   , when pressed for 3 seconds, allows the controller to  e pb ut on a standby or output control to be resumed (with SB=YES only).
KEYPAD LOCK
The                     attempted   the controllers   keypad lock avoids undesired, potentially dangerous operations, which might be when is operating 
in public menu, =YES inhibit functions buttons. a   place. In the INFO   set parameter LOC  to   all   of the   To   normal resume operation 
of keypad, adjust setting so that LOC=NO.
CONTROLLER AUTOTUNING IN PID MODE
Before starting
In  the    mode        set  =PID;      that    matches  the      mode setup (see configuration parameters): 1CM make sure 1CH desired operation
( =REF for refrigerating control,  =HEA for heating control); then adjust setpoint   at the desired value.1CH 1CH 1SP
Start autotuning
During operation, keep buttons  normal     
 +   pressed for   seconds. 1CT   on the 3 blinks display.   +   or   set the With  cycle 
time in define dynamic be   order to   the   of the process to   controlled. To   the     press abort autotuning function,
; to start autotuning 
press 
 +   or wait for 30 seconds.
During autotuning
During entire autotuning phase, display TUN with actual temperature measured. power failure,  the       the   alternates     the       In case of   
when power is resumed, initial autotest phase, resumes autotuning function.       after the       the controller   the     To   the abort autotuning, 
without modifying previous parameters, keep button    the   control     
 pressed for   seconds.   the   has   place 3 After autotuning taken
successfully, the controller updates the control parameters and start to control.
Errors
If the autotuning function failed, the display shows an error code:
E1     the controller   not   the     the     Increase   timeout1 error: could bring temperature within proportional band.■ in heating 1SP   case of 
control, vice versa, decrease   in case of refrigerating control and re-start the process.1SP
E2     the   has not ended   the             Re-start the timeout2 error: autotuning within maximum time allowed (1000 cycle times). autotuning  ■
process and set a longer cycle time 1CT.
E3 temperature overrange: check was caused by probe malfunction,       that the error   not     a     then decrease  ■ in heating 1SP   case of 
control, vice versa increase   in case of refrigerating control and then re-start the proce1SP ss.
To eliminate the error indication and return to the normal mode, press button  ■
.
Control improvement
To reduce overshoot, reduce the integral action reset  ■1AR
To increase the response speed of the system, reduce the proportiona banl  d  ■1PB. Ca tu ion: doin  g this makes the system less stable.
To     reduce swings in steady-state temperature, increase       the integral action time     ■ system stability1IT;     is thus increased, although      
its response speed is decreased.
To   the speed of response to the         the     increase variations in temperature, increase derivative action time  ■ Caution: high 1DT.   a 
value makes the system sensitive to small variations and it may be a source of instability.
RECALIBRATION
Have a precision reference thermometer or a calibrator to hand. Ensure that  ■ =0 and  =0.OS1 SIM
Switch the controller o f then on again.f ■
During the auto-test phase, press buttons  ■ 
  0AD+    and keep them pressed till the controller shows  .
With buttons   ■
 and    select   or     a   of     a constant     the   scale 0AD SAD 0AD:  allows calibration 0, inserting correction over whole
of     a   of the top part of the   scale   a       the measurement. SAD allows calibration measurement with proportional correction between
calibration point and 0.
Press  ■
 to   the   and then      +   or    to   the read       the       the display value use make value coincide with value measured by
reference instrument. 
Exit from calibration by pressing button  ■
.
Insert the controller through a hole measuring 71x29 mm; ■
Make sure electrical connections comply with “wiring diagrams”.   that         the paragraph     To   the effects of reduce electromagnetic  ■
disturbance, keep the sensor and signal cables well separate from the power wires. 
Fix the controller to the panel   means of the   by suitable clips, by pressingly gently;       if fitted, check     that the     adheres   rubber gasket■
to the panel perfectly, in order to prevent debris and moisture infiltration to the back of the instrument.
Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.  ■
OUT1
OU T2
L1
L2
Channel 1 output
Channel 2 output
Alarm
Channel 1 setpoint modification
Channel 2 setpoint modification
Info / Enter button
Fig.1 - Front panel
Modify Setpoint 1 / Decrease button
Increase / Modify Setpoint 2 button
Exit / Stand-by button.
Thank you for having chosen a Fantini Cosmi product. Before installing the instrument, please read these instructions carefully
to ensure maximum performance and safety.
INSTRUCTION FOR USE
L02DM- / L02DI-
115... ~ (L02DM-) o 12Vac/dc (L02DI-)230V
OUT 2OUT 1
+
-
10
11
1 2 3 4
5
6 7
L02CM- / L02CI-
115... ~ (L02CM-) o 12Vac/dc (L02CI-)230V
OUT 2
W R W
9
10
11
4
5
6 7
L02AM2 / L02AI2B
115... ~ (L02AM2) o 12Vac/dc (L02AI2B)230V
OUT 2OUT 1
10
11
1 2 3 4
5
6 7
OUT 1
123
MODEL INPUT
RANGE [MEASUREMENT ACCURACY]
SCL=1°C SCL=2°C SCL=°F
L02D--
INP=T1 ---TC “J” 0÷450°C [ < ±3°C ]
32÷842°F [ < ±5°F ]
L02C-- PT100
-50/-19.9÷99.9/150°C
[ < ±0.3°C ]
0÷400°C
[ <±1°C(0÷400°), ±2°C ]
32÷752°F
[ <±2°F(32÷752°), ±4°F]
L02A--
INP=ST1
PTC 1000 Ω
(LS120)
-40/-19.9 ÷ 99.9/105°C
[<±0.3°C(-40÷130°),±1°C]
-40 ÷ 105°C
   [<±0.3°C (-40÷130°),±1°C]
-40 ÷ 221°F 
[<±0.6°F (-40÷221°),±2°F] 
INP=SN4
NTC 10K Ω 
(LS130)
-40/-19.9 ÷ 99.9/105°C
[<±0.3°C(-40÷100°), ±1°C]
-40 ÷ 105°C
   [<±0.3°C (-40÷100°),±1°C]
-40 ÷ 221°F
[<±0.6°F (-40÷210°),±2°F] 
OUT1
10A 24Vac/dc
(L02AI2B/L02CI2B/L02DI2B)
OUT2
1A 24Vac/dc
OUT1
12(4)A 240Vac
(L02AM2/L02CI1B/L02CM-/L02DI1B/L02DM-)
OUT2
7(2)A 240Vac
DESCRIPTION
INDICATIONS
CONFIGURATION PARAMETERS
INPUT SPECIFICATIONS
TECHNICAL DATA
WIRING DIAGRAMS
INSTALLATION
OPERATION
GB79193B
FANTINI COSMI S.p.A.
Via dell’Osio, 6
20090 Caleppio di Settala,  Milano, ITALY
Ph. +39 02 956821  |  Fax +39 02 95307006
info@fantinicosmi.it
export@fantinicosmi.it
L02...
Produktspecifikationer
| Varumärke: | Fantini Cosmi | 
| Kategori: | Termostat | 
| Modell: | L02A | 
Behöver du hjälp?
Om du behöver hjälp med Fantini Cosmi L02A ställ en fråga nedan och andra användare kommer att svara dig
Termostat Fantini Cosmi Manualer
                        
                         13 Oktober 2025
                        
                    
                                                            
                        
                         12 Oktober 2025
                        
                    
                                                            
                        
                         12 Oktober 2025
                        
                    
                                                            
                        
                         18 Augusti 2025
                        
                    
                                                            
                        
                         19 Juli 2025
                        
                    
                                                            
                        
                         18 Juli 2025
                        
                    
                                                            
                        
                         1 April 2025
                        
                    
                                                            
                        
                         1 April 2025
                        
                    
                                                            
                        
                         1 April 2025
                        
                    
                                                            Termostat Manualer
- Elro
 - EasyTemp
 - Vemer
 - Yokis
 - Lowes
 - Crestron
 - Arnold Rak
 - Coati
 - Netatmo
 - Radson
 - Baxi
 - Hornbach
 - Innogy
 - Max
 - Intergas
 
Nyaste Termostat Manualer
                        
                         5 Oktober 2025
                        
                    
                                                            
                        
                         2 Oktober 2025
                        
                    
                                                            
                        
                         2 Oktober 2025
                        
                    
                                                            
                        
                         29 September 2025
                        
                    
                                                            
                        
                         28 September 2025
                        
                    
                                                            
                        
                         28 September 2025
                        
                    
                                                            
                        
                         28 September 2025
                        
                    
                                                            
                        
                         27 September 2025
                        
                    
                                                            
                        
                         26 September 2025
                        
                    
                                                            
                        
                         26 September 2025