Klein Tools CL310 Bruksanvisning

Läs gratis den bruksanvisning för Klein Tools CL310 (56 sidor) i kategorin mätning. Guiden har ansetts hjälpsam av 5 personer och har ett genomsnittsbetyg på 4.8 stjärnor baserat på 3 recensioner. Har du en fråga om Klein Tools CL310 eller vill du ställa frågor till andra användare av produkten? Ställ en fråga

Sida 1/56
Dwg Name: CL310-1390115ART
Dwg No: 1390115
ECO No: 20550 Rev: D
Pkg Dwg Ref: 1290186
Color Reference: N/A
INSTRUCTION MANUAL
ENGLISH
CL310
FRANÇAIS pg. 37
ESPAÑOL pg. 19
400A AC Auto-Ranging
Digital Clamp Meter
400A AC Auto-Ranging
Digital Clamp Meter
400A AC Auto-Ranging
Digital Clamp Meter
True RMS
Measurement
Technology
600V
400A
40M
Ω
auto-ranGinG
Data HolD
ranGe HolD
teMperature
auDible continuity
CL310-1390115ART.indd 1 10/1/2015 3:43:24 PM
Dwg Name: CL310-1390115ART
Dwg No: 1390115
ECO No: 20550 Rev: D
Pkg Dwg Ref: 1290186
Color Reference: N/A
2
GENERAL SPECIFICATIONS
Klein Tools CL310 is an automatically ranging true root mean square
(TRMS) digital clamp meter that measures AC current via the clamp,
AC/DC voltage, resistance, continuity, frequency, capacitance, and
tests diodes via test-leads, and temperature via a thermocouple probe.
Operating Altitude: 6562 ft. (2000m)
Relative Humidity: <95% non-condensing
Operating Temp: 32° to 122°F (0° to 50°C)
Storage Temp: 14° to 122°F (-10° to 50°C)
Accuracy: Values stated at 65° to 83°F (18° to 28°C)
Temp Coefcient: 0.1 x (Quoted Accuracy) per °C above
28°C or below 18°C, corrections are required when ambient
working temp is outside of Accuracy Temp range
Dimensions: 8.66" x 3.03" x 1.61" (220 x 77 x 41 mm)
Weight: 9.88 oz. (280 g) including batteries
Calibration: Accurate for one year
Standards: Conforms to: UL 61010-1, UL 61010-2-032,
UL 61010-2-033.
Certified to: CAN/CSA C22.2 NO. 61010-1,
61010-2-032, 61010-2-033, IEC EN 61010-1,
61010-2-032, 61010-2-033, IEC EN 61326-1.
Pollution degree: 2
Accuracy: ± (% of reading + # of least significant digits)
Drop Protection: 3.3 ft. (1m)
Safety Rating: CATIII 600V, Class 2, Double insulation
Electromagnetic Environment: IEC EN 61326-1. This
equipment meets requirements for use in basic and controlled
electromagnetic environments like residential properties,
business premises, and light-industrial locations.
Specifications subject to change.
ELECTRICAL SPECIFICATIONS
Function Range Resolution Accuracy
AC Voltage
(V AC)
4.000V 1mV ±(1.5% + 5 digits)
40.00V 10mV
±(1.2% + 5 digits)
400.0V 100mV
600V 1V ±(1.5% + 5 digits)
DC Voltage
(V DC)
400.0mV 0.1mV ±(1.0% + 8 digits)
4.000V 1mV
±(0.8% + 3 digits)40.00V 10mV
400.0V 100mV
600V 1V ±(1.0% + 3 digits)
Input Impedance: 10MΩ
Frequency Range: 45 to 400Hz
Maximum Input: 600V AC RMS or 600V DC
AC Current
(A AC)
4.000A 1mA ±(2.5% + 30 digits)
40.00A 10mA ±(2.5% + 10 digits)
400.0A 100mA ±(2.0% + 10 digits)
Frequency Range: 50 to 60Hz
Resistance
400.0Ω 0.1Ω ±(1.2% + 5 digits)
4.000KΩ
±(1.2% + 3 digits)
40.00kΩ 10Ω
400.0kΩ 100Ω
4.000MΩ 1kΩ
40.00MΩ 10kΩ ±(2.0% + 5 digits)
Maximum Input: 600V AC RMS or 600V DC
ENGLISH
CL310-1390115ART.indd 2 10/1/2015 3:43:25 PM

Produktspecifikationer

Varumärke: Klein Tools
Kategori: mätning
Modell: CL310

Behöver du hjälp?

Om du behöver hjälp med Klein Tools CL310 ställ en fråga nedan och andra användare kommer att svara dig