Läs gratis den bruksanvisning för EBERLE Easy 3 st (3 sidor) i kategorin Termostat. Guiden har ansetts hjälpsam av 23 personer och har ett genomsnittsbetyg på 4.7 stjärnor baserat på 8 recensioner. Har du en fråga om EBERLE Easy 3 st eller vill du ställa frågor till andra användare av produkten? Ställ en fråga
Sida 1/3

1. Applications
The easy 3s electronic clock thermostat is designed for room
temperature control in conjunction with:
•heatingsystems,e.g.hot-waterheaters,convectorheaters
or oor heating
•electricconvectorheaters,ceilingandstorageheating
•night-storageheaters
•chillers
•circulationpumps
•burnersandboilers
•heatpumps,etc.
•airconditioningapplications(coolingonly)
Features
•
verysimpleoperation
•comfortandsetbacktemperatureadjustable
•
5operatingmodes(byrotaryswitch)for:
➩permanentcomforttemperature(5…30°C)
➩permanentsetbacktemperature(5…30°C)
➩clockmode(automatic)
➩frostprotection(5°Cxed)
➩ OFF
•
Indicator lamps for: ➩heat demand
➩setbackmode
•
availablewithdailyorweeklytimer
•
controlbyphoneremoteswitchpossible
•
outputsignalPWMorON/OFFregulation(adjustablevia
jumper)
•
relayoutput,1xchangeovercontact
•
remote sensor optional
•
emergency operation at sensor failure
•
hingedcover
•
newdesign2000
2. Function description
The clock thermostat is designed to control the room tem-
perature.
Intheautomaticmode,achangeoveriseectedbetween
comfortandsetbackmodebythebuiltintimer.
Optionallyremotesensorcanbeusedinsteadofbuilt-in
sensor.
Insetbackmodethegreenindicatorlamplightsup.
Ifroomtemperaturedropsbelowsetvalue,heatingwillstart,
theredindicatorlampwilllightup.
Indicator lamps
Redindicateswhencontrollerdemandsheat,
Greenindicateswhensetbackmodeisactivated.
Redashingforfailure.Operatingvoltagetobeswit-
chedOFFandONagain.
Controller heat demand at PWM
Ifroomtemperaturedropsbelowthesetvalue,heatingmode
willstart.Thecontrolleroutputisintheformofpulsesof
varyinglength(PWM).Thelengthofthepulsesdependson
thedierencebetweensetandactualroomtemperature.
ThesumofpulseandpausetimescanbeselectedwithJ4
(between10or25min.).
Iftherearelargetemperaturedierences,thecontrollerwill
switchONorOFFpermanent,e.g.whenchangingoverto
temperaturesetbackmode.PWMshouldonlybeusedfor
current≤10A
On
Off
Temperature
10/25 min
set temperature
Fig.1:Characteristicofimpulsepauseratiodependingon
temperature
Cycle time setting
Forinertapplications(e.g.burners)werecommendthelong
cycletime.
Forquickapplications(e.g.electricdirectheaters)werecom-
mendtheshortcycletime.
Plug-in jumper J4
(rightsideofboard)
Time
Double-polejumper
connection
25 min
(as-deliveredcondition)
Single-polejumper
connection
10min
Heat demand of the controller at ON/OFF regulation
Whenroomtemperaturedropsbelowsettemperaturethe
outputwillbeswitchedon,whereasitwillbeswitchedo,
whensetvalueisexceeded.
set temperature
temperature
OFF
ON
Hysteresis
Fig.2:ON/OFFregulation
Plug-in jumper J3
(rightsideofboard)
Regulation
Double-polejumper
connection
ON/OFF
Single-polejumper
connection
PWM (asdeliveredcondition)
Phone remote switch (onlyavailableatspecialvariants)
Viaanexternalphoneswitchingdevicetheconrollercanbe
putintomodeofcomfortorsetbacktemperature.Aslong
ascontact(terminal19)isclosed,thecomforttemperature
willbe“used“.Thisfunctionistactivatedinthemodes2
automatic,setbacktemperaturepermanentandÑP
Frostprotection.
3. Installation
Thecontrollershouldbearrangedinaplacewithintheroom
which:
•iseasilyaccessibleforoperation
•isfreefromcurtains,cupboards,shelves,etc.
•enablesfreeaircirculation
•isfreefromdirectsunradiation
•isfreefromdraughts(e.g.openingofwindowsanddoors)
•isnotaecteddirectlybythesourceofheat
•isnotlocatedonanexternalwall
•islocatedapprox.1,5maboveoorlevel
MountingdirectlyonconduitboxorwithadapterframeARA
easy.
Electric connection
Warning!Disconnectelectriccircuitfromsupply.
Proceed as follows:
•pullotemperaturesettingknob
•pushretaininghookoutwardsusingscrewdriver
•removehousingcover
•makeconnectionincompliancewithwiringdiagram
(seehousingcover).
•watchnotes
Remote sensor
Havingconnectedtheremotesensor,theintegralsensing
componentwillbeswitchedoautomatically.
Thesensorcableisextendableuptoalengthofmax.50m.
Pleaseuseatwo-core230Vcablewithacrosssectionof1.5
mm.
Thesensorcable(F193720)shouldbeinstalledintoaprotecti-
ontube(pocket).Thisfacilitateslaterreplacement.
Incaseoffailure(breakorshort-circuit)thecontrollerswitches
into emergency operation:
atPWM:30%heatingcapacitiy
at ON/OFF: Relay OFF
Warning! Sensor cables carry operating voltage.
4. Technical data
Temperature setting range:
comfort temperature
setback temperature
frost protection
5…30°C
5…30°C
approx. 5°C xed
Regulationproportional controller
(due to PWM quasi-continuous, see Fig.1)
Cycle periodadjustable 10 or 25 min.
(sum of PWM ON and OFF times)
Proportional band1,5K
Hysteresis~0,5K, ≤ 10A see Fig. 2
~0,5K at 16A and use with remote sensor
~2,5K, at 16A without remote sensor
ON/OFF regulationadjustable via jumper
Outputrelay, 1 volt-free* changeover contact
Switching current
Heating
Cooling
10mA…16 A cos = 1ϕ
max. 4 A cos = 0,6ϕ
10mA ...10A cos = 1ϕ
max. 1,5 A cos = 0,6ϕ
Switching voltage24…250V AC
Mode selector switchcomfort / automatic / setback /
frost protection / OFF
Phone remote switch
(as variant)
Input for 230V AC (via an external
phone switching device)
Indicator lamp: red
green
controller demands heat
setback mode
Temperature sensor:internal
Remote sensor
Sensor characteristics
type F190021 (wall mounting)
type F193720 length 4m
both extendable up to 50m
42kΩ at 20°C
26kΩ at 30°C
Range limitationinside setting knob
Clock:
accuracy
switching time setting
power reserve
<10 min./year
every 15 min. with daily timer
every hour with weekly timer
approx. 100 h
Protection class of housingIP 30
Degree of protectionII (see Warning 1)
Ambient temperature0…40°C, without condensation
Storage temperature–25…65°C
Pollution degree 2
Rated impulse voltage4 kV
Ball pressure test
temperature
75 ± 2 °C
Voltage and Current for the
for purposes of interfernce
measurements
230 V, 0,1 A
Dimensions160 x 80 x 36 mm
Weightapprox. 220 g
Energy classIV = 2 %
(acc. EU 811/2013, 812/2013, 813/2013, 814/2013)
* The volt-free contact of this mains-operated unit does
not ensure the requirement for the use of safety ext-
ra-low voltage (SELV).
For units with 230 V supply voltage
Type easy 3st with daily timer
easy 3sw with weekly timer
Article-Nr. easy 3st 517 2701 51 100
easy 3sw 517 2702 51 100
Operating voltage 195…253V AC 50/60Hz
Power consumption < 1,5 W
For units with low voltage output
Type easy 3st 1mA with daily timer
easy 3sw 1mA with weekly timer
Article No. easy 3st 1mA 517 2711 51 100
easy 3sw 1mA 517 2712 51 100
Operating voltage 195...253V AC 50/60Hz
Switching current >1mA, >1V or max. 10(4)A AC
Power consumption < 1,5 W
5. Wiring diagram
Symbol explanation
U Heaing PCooling
Remote sensor
%
Phone remote switch
Note
For heating applications
•connectn/cactuatorstoterminal2.
•connectn/oactuatorstoterminal3.
For cooling applications
•connectn/cactuatorstoterminal3
•connectn/oactuatorstoterminal2
•Tousetheredlampasindicatorfor“coolingON”,connectn/o
actuators to terminal 2
•WhenmodeselectorswitchisinOFFposition
n/c and n/o
actuatorswillbeclosedlogically.
6. Operation
Temperature setting
1
Comfort temperature (daytimetemperature)
issetbymeansofexternallyvisiblesetingknob(1)
2
Setback temperature (nighttemperature)
issetbymeansofadjustmentknob(2)beneathcover.
Time setting
3
byputtingonengerondial(3)andturninginanydirec-
tion,youcansetthetime.
4
Arrow(4)pointstotheselectedtime.
Switching time setting
5
Bringmovabletappets(5)intorequiredpositionusinga
pointedobject.
Outer ring = comfort temperature
Innerring=setbacktemperature
6
Mode selector switch (6)–externally
ÉComforttemperature,permanent
2Automaticmode,time-controlledchangeover
betweencomfortandsetbacktemperature
ÑSetbacktemperature,permanent
PFrostprotection,permanent(5°C)
OFF,thereisnocontrolactivity.Thecontrolleritselfisnot
disconnectedfromoperatingvoltage.
12
456
3
U4693101911-0882
Installation and
Operation Instructions
Electronic
Clock Thermostat
easy 3s
Warning!
Thedevicemayonlybeopenedandinstalledaccor-
dingtothecircuitdiagramonthedeviceorthese
instructionsbyaqualiedelectrician.Theexisting
safetyregulationsmustbeobserved.
Appropriateinstallationmeasuresmustbetakento
achievetherequirementsofprotectionclassII.
Thisindependentlymountableelectronicdeviceis
de-signedforcontrollingthetemperatureindryand
enclosedroomsonlyundernormalconditions.The
deviceconrmstoEN60730,itworksaccording
operatingprinciple1C.
Thisproductshouldnotbedisposedofwith
householdwaste.
Please recycle the products where facilities for
electronicwasteexist.Checkwithyourlocal
authoritiesforrecyclingadvice.
Produktspecifikationer
| Varumärke: | EBERLE |
| Kategori: | Termostat |
| Modell: | Easy 3 st |
| Vikt: | 220 g |
| Bredd: | 160 mm |
| Djup: | 36 mm |
| Höjd: | 80 mm |
| Nattläge: | Ja |
| Måttenhet: | °C |
| Driftspänning: | 230 V |
| Fjärrkontroll ingår: | Nej |
| Temperatursensor: | Ja |
| Smart termostat: | Nej |
| Produktens färg: | Vit |
| Internationellt skydd (IP) kod: | IP30 |
| Displaytyp: | Analog |
| Strömkälla: | AC |
| Antal: | 1 |
| Kylning: | Ja |
| Temperaturintervall för börvärde: | 5 - 30 ° C |
| Temperaturområde (T-T): | 0 - 40 ° C |
| Maximal växlingsström: | 16 A |
Behöver du hjälp?
Om du behöver hjälp med EBERLE Easy 3 st ställ en fråga nedan och andra användare kommer att svara dig
Termostat EBERLE Manualer
24 Augusti 2025
24 Augusti 2025
24 Augusti 2025
24 Augusti 2025
24 Augusti 2025
24 Augusti 2025
23 Augusti 2025
23 Augusti 2025
23 Augusti 2025
23 Augusti 2025
Termostat Manualer
Nyaste Termostat Manualer
13 Oktober 2025
12 Oktober 2025
12 Oktober 2025
5 Oktober 2025
2 Oktober 2025
2 Oktober 2025
29 September 2025
28 September 2025
28 September 2025
28 September 2025